60F-162-K/Q [MSYSTEM]

Field Network Modules 60-UNIT Series;
60F-162-K/Q
型号: 60F-162-K/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Field Network Modules 60-UNIT Series

文件: 总4页 (文件大小:134K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 60F  
Field Network Modules 60-UNIT Series  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
ANALOG I/O MODULE  
(Fuji Electric T-Link use)  
/C02: Polyurethane coating  
/C03: Rubber coating  
Functions & Features  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK  
modules with T-Link  
• Saving power and I/O wiring inside an instrumentation  
panel  
RELATED PRODUCTS  
•Special cable (model: MCN34)  
72  
(2.83)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection  
80 (3.15)  
T-Link: Euro type connector terminal (applicable wire size:  
0.2 to 2.5 mm , stripped length 7 mm)  
2
I/O: 34-pin connector (OMRON XG4A-3434)  
Power input: M3.5 screw terminal  
153 (6.02)  
Screw terminal: Chromated steel (standard) or stainless  
steel  
mm (inch)  
Housing material: Flame-resistant resin (black)  
Isolation: I/O to T-Link to power to FG1  
Power indicator: Green LED turns on with power supplied.  
MODEL: 60F-16[1]-[2][3]  
T-Link SPECIFICATIONS  
Configuration: Multi-drop  
ORDERING INFORMATION  
• Code number: 60F-16[1]-[2][3]  
Specify a code from below for each [1] through [3].  
(e.g. 60F-161-K/Q)  
Communication: Half-duplex  
Baud rate: 500 kbps  
Transmission media/distance:  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
KPEV-SB 0.75 mm  
2
× 1 pair, 700 m  
× 1 pair, 1000 m  
T-KPEV-SB, 1.25 mm  
2
Station No.: Rotary switch; 00 - 99  
NO. OF CHANNELS  
16: 16 points  
(Factory default setting: 00)  
L RUN indicator: Red LED ON at normal communication  
L ERR. indicator: Red LED ON/blinking at communication  
abnormality  
[1] I/O TYPE  
1: Input  
L I/O indicator: Red LED blinking at normal I/O  
L COM indicator: RED LED blinking at T-Link normal  
communication  
2: Output  
NUMBER OF CONNECTABLE UNITS WITH T-Link  
Up to a maximum of 32 T-Link devices can be connected in  
a single T-Link system. There is a limit of 100 words in  
processor memory. Make sure that the configured word  
area to be occupied does not exceed the 100-word range.  
(According to the Fuji Electric MICREX-F Users Manual)  
It is necessary to consider these criteria when connecting to  
this device.  
[2] POWER INPUT  
AC Power  
K: 85 – 132 V AC  
(Operational voltage range 85 – 132 V, 47 – 66 Hz)  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
The below describes the number of words occupied per  
device by number of modules.  
[3] OPTIONS  
For input 16 / output 16 modules: 16  
blank: none  
/Q: With options (specify the specification)  
60F SPECIFICATIONS  
ES-6610 Rev.3 Page 1/4  
http://www.m-system.co.jp/  
MODEL: 60F  
INPUT SPECIFICATIONS  
Analog Input  
Output Connector Pin Assignment  
PIN NO.  
1
ASSIGNMENT  
PIN NO.  
2
ASSIGNMENT  
COM  
Input range: 1 – 5 V DC  
Output  
Output  
Output  
Output  
Output  
Output  
Output  
Output  
Output  
1
2
3
4
5
6
7
8
9
3
4
COM  
Input resistance: ≥ 1 MΩ  
5
6
COM  
10-RACK and 18-RACK I/O modules must be isolated types.  
Non-isolated modules such as 10BW and 18BW are not  
usable.  
7
8
COM  
9
10  
12  
14  
16  
18  
20  
22  
24  
26  
28  
30  
32  
34  
COM  
11  
13  
15  
17  
19  
21  
23  
25  
27  
29  
31  
33  
COM  
A/D conversion output: Signed binary  
Signal range 0 – 100 % is converted into hexadecimal 0000  
– 2710 (0 – 10000). -15 to 0 % is a negative range  
represented by 2's complements.  
COM  
COM  
COM  
Output 10  
Output 11  
Output 12  
Output 13  
Output 14  
Output 15  
Output 16  
No connection  
COM  
COM  
Overall range is represented by hexadecimal FA24 – 2CEC  
(-1500 – +11500), for -15 – +115 %.  
COM  
COM  
COM  
Input Connector Pin Assignment  
COM  
PIN NO.  
1
ASSIGNMENT  
PIN NO.  
2
ASSIGNMENT  
COM  
COM  
Input  
Input  
Input  
Input  
Input  
Input  
Input  
Input  
Input  
1
2
3
4
5
6
7
8
9
No connection  
3
4
COM  
5
6
COM  
7
8
COM  
INSTALLATION  
Power consumption  
9
10  
12  
14  
16  
18  
20  
22  
24  
26  
28  
30  
32  
34  
COM  
11  
13  
15  
17  
19  
21  
23  
25  
27  
29  
31  
33  
COM  
AC: Approx. 3 VA  
COM  
COM  
DC: Approx. 4 W (160 mA)  
COM  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Surface or DIN rail  
Input 10  
Input 11  
COM  
COM  
Input 12  
COM  
Input 13  
COM  
Weight: 450 g (0.99 lb)  
Input 14  
COM  
Input 15  
COM  
Input 16  
COM  
PERFORMANCE in percentage of span  
A/D conversion: ±0.1 %  
No connection  
No connection  
D/A conversion: ±0.1 %  
OUTPUT SPECIFICATIONS  
Analog Output  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Permissible power failure duration: ≤ 10 msec.  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input or output  
to T-Link to power)  
Output must be isolated with signal conditioners.  
When the transmission line is open, the last value sampled  
before failure is held.  
Output range: 1 – 5 V DC  
2000 V AC @ 1 minute (input or output or T-Link or power to  
FG1)  
Load resistance: 20 kΩ minimum  
10-RACK and 18-RACK I/O modules must be isolated types.  
Non-isolated modules such as 10BW and 18BW are not  
usable.  
D/A conversion output: Signed binary  
Signal range 0 – 100 % is converted into hexadecimal 0000  
– 2710 (0 – 10000). -15 to 0 % is a negative range  
represented by 2's complements.  
Overall range is represented by hexadecimal FA24 – 2CEC  
(-1500 – +11500), for -15 – +115 %.  
60F SPECIFICATIONS  
ES-6610 Rev.3 Page 2/4  
http://www.m-system.co.jp/  
MODEL: 60F  
EXTERNAL VIEW  
Modular Jack  
for Factory Calibration  
CN1  
L RUN  
L ERR.  
L I/O  
Operating Status Indicator LED  
I/O Connector  
L COM  
Power Indicator LED  
PWR  
Euro Type Connector Terminal  
for T-Link  
Station No. Setting Rotary Switches  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
7
14  
6
5
12  
4
3
2–4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
8
9
15 10  
1
11  
2
14–M3.5  
SCREW  
14  
72 (2.83)  
(.55)  
109 (4.29)  
139 (5.47)  
60 (2.36)  
72 (2.83)  
38 (1.50)  
[3.3 (.13)]  
•When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Transmission  
Station No.  
Setting Rotary  
Switches  
Indicator  
LED  
SHIELDED  
TWISTED-PAIR  
T1  
T2  
+
CPU For T-Link  
Transmission  
To other T-Link devices  
To 10-RACK, 18-RACK etc.  
SD  
A/D  
or  
D/A  
Converter  
RT+  
RT−  
*
JUMPER PIN  
I/O Side  
CPU  
TERMINATING  
RESISTOR  
Modular Jack  
for Factory  
Calibration  
MODULAR  
JACK  
SERIAL  
TRANSMISSION LINE  
7
14  
8
U( + )  
V( )  
POWER  
GROUNDING FG1  
* When the unit is located at the end of transmission line via twisted-pair  
cable (= no cross-wiring), short across terminals RT+, RT- with the  
jumper pin (or wire) provided with the unit.  
Remove the jumper pin for the one not located at the end.  
Note: Use T1, T2, SD terminals for cross-wiring.  
60F SPECIFICATIONS  
ES-6610 Rev.3 Page 3/4  
http://www.m-system.co.jp/  
MODEL: 60F  
Specifications are subject to change without notice.  
60F SPECIFICATIONS  
ES-6610 Rev.3 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

60F-162-R

Field Network Modules 60-UNIT Series
MSYSTEM

60F-162-R/Q

Field Network Modules 60-UNIT Series
MSYSTEM

60F30SAB3

FAST RECOVER DIODE
JSMC

60F30SW3

FAST RECOVER DIODE
JSMC

60F60AB

FAST RECOVER DIODE
JSMC

60F60W

FAST RECOVER DIODE
JSMC

60FD14

Data subject to change without notice Isometric drawing Not to Scale
HAMMOND

60GA01860

Interconnection Device,
SWITCH

60GA03660

Interconnection Device,
SWITCH

60GA04860

Interconnection Device,
SWITCH

60GA07260

Interconnection Device,
SWITCH

60GA12060

Interconnection Device,
SWITCH