60M-161-R/Q [MSYSTEM]
Field Network Modules 60-UNIT Series;型号: | 60M-161-R/Q |
厂家: | M-SYSTEM |
描述: | Field Network Modules 60-UNIT Series |
文件: | 总5页 (文件大小:185K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 60M
Field Network Modules 60-UNIT Series
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
ANALOG I/O MODULE
(Modbus; RS-485)
/C02: Polyurethane coating
/C03: Rubber coating
Functions & Features
TERMINAL SCREW MATERIAL
/S01: Stainless steel
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK
modules with Modbus
• Saving power and I/O wiring inside an instrumentation
panel
RELATED PRODUCTS
•Special cable (model: MCN34)
72
(2.83)
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.25 W)
80
(3.15)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection
153
(6.02)
Modbus: Euro type connector terminal (applicable wire
mm (inch)
size: 0.2 to 2.5 mm , stripped length 7 mm)
2
I/O: 34-pin connector (OMRON XG4A-3434)
Power input: M3.5 screw terminal
Screw terminal: Chromated steel (standard) or stainless
steel
MODEL: 60M-16[1]-[2][3]
Housing material: Flame-resistant resin (black)
Isolation: I/O to Modbus to power to FG1
Power indicator: Green LED turns on with power supplied.
ORDERING INFORMATION
• Code number: 60M-16[1]-[2][3]
Specify a code from below for each [1] through [3].
(e.g. 60M-161-K/Q)
MODBUS COMMUNICATION
Communication: Conforms to TIA/EIA-485-A
Transmission setting: DIP switch
• Specify the specification for option code /Q
(e.g. /C01/S01)
Data: RTU (Binary) or ASCII
NO. OF CHANNELS
Parity: none, even or odd
16: 16 points
Baud rate: 4800, 9600, 19.2 k, 38.4 k (bps)
Node address setting: Rotary switch; 01 – F7
(factory setting: 00)
[1] I/O TYPE
1: Input
L RUN indicator: Red LED turns on for 10 sec. when the
module receives data.
2: Output
L ERR. indicator: Red LED turns on at errors in parity,
framing, overrun, CRC or LRC.
[2] POWER INPUT
AC Power
SD indicator: Red LED turns on when transmitting.
RD indicator: Red LED turns on when receiving.
Analog input: Programming Unit (model: PU-2x) or via
Modbus
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
Moving averaging: None, every 2 or 4 samples
Sampling rate: 400, 240, or 160 (msec.)
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
60M SPECIFICATIONS
ES-6606 Rev.12 Page 1/5
http://www.m-system.co.jp/
MODEL: 60M
•Floating data (4-byte data)
INPUT SPECIFICATIONS
■ Analog Input
Initial signal range 0 – 100 % is proportional to 0 – 10000,
that is possible to be scaled into a specific range.
Input range: 1 – 5 V DC
Input resistance: ≥ 1 MΩ
• Output Connector Pin Assignment
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
PIN NO.
1
ASSIGNMENT
PIN NO.
2
ASSIGNMENT
COM
Output
Output
Output
Output
Output
Output
Output
Output
Output
1
2
3
4
5
6
7
8
9
3
4
COM
5
6
COM
■ A/D Conversion Output
7
8
COM
•Signed binary (2-byte data)
9
10
12
14
16
18
20
22
24
26
28
30
32
34
COM
Signal range 0 – 100 % is proportional to hexadecimal 0000
– 2710 (0 – 10000). -15 to 0 % is a negative range
represented by 2's complements.
11
13
15
17
19
21
23
25
27
29
31
33
COM
COM
COM
COM
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
•Floating data (4-byte data)
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
No connection
COM
COM
COM
Initial signal range 0 – 100 % is proportional to 0 – 10000,
that is possible to be scaled into a specific range.
COM
COM
COM
• Input Connector Pin Assignment
COM
PIN NO.
1
ASSIGNMENT
PIN NO.
2
ASSIGNMENT
COM
No connection
Input
Input
Input
Input
Input
Input
Input
Input
Input
1
2
3
4
5
6
7
8
9
3
4
COM
5
6
COM
INSTALLATION
Power consumption
7
8
COM
9
10
12
14
16
18
20
22
24
26
28
30
32
34
COM
•AC: Approx. 4 VA
11
13
15
17
19
21
23
25
27
29
31
33
COM
•DC: Approx. 4 W (160 mA)
COM
COM
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
COM
Input 10
Input 11
COM
COM
Input 12
COM
Weight: 450 g (0.99 lb)
Input 13
COM
Input 14
COM
Input 15
COM
PERFORMANCE in percentage of span
A/D conversion: ±0.1 %
Input 16
COM
No connection
No connection
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output
to Modbus to power)
OUTPUT SPECIFICATIONS
■ Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled
before failure is held.
2000 V AC @ 1 minute (input or output or Modbus or power
to FG1)
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types.
Non-isolated modules such as 10BW and 18BW are not
usable.
■ D/A Conversion Input
•Signed binary (2-byte data)
Signal range 0 – 100 % is proportional to hexadecimal 0000
– 2710 (0 – 10000). -15 to 0 % is a negative range
represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
60M SPECIFICATIONS
ES-6606 Rev.12 Page 2/5
http://www.m-system.co.jp/
MODEL: 60M
EXTERNAL VIEW
CN1
Modular Jack
for Factory Calibration
Power Indicator LED
L RUN
L ERR.
SD
Status Indicator LED
I/O Connector
PWR
RD
4
C
C
Node Address Setting
Transmission Setting
4
Euro Type Connector Terminal
for Modbus
1
2
3
4
5
6
MODBUS FUNCTION CODES & SUPPORTED CODES
■ Data and Control Functions
CODE
01
NAME
Read Coil Status
X
X
X
X
X
X
Digital output from the slave
02
Read Input Status
Read Holding Registers
Read Input Registers
Force Single Coil
Status of digital inputs to the slave
General purpose register within the slave
Collected data from the eld by the slave
Digital output from the slave
03
04
05
06
Preset Single Registers
Read Exception Status
Diagnostics
General purpose register within the slave
07
08
X
09
Program 484
10
Poll 484
11
Fetch Comm. Event Counter
Fetch Comm. Event Log
Fetch a status word and an event counter
A status word, an event counter, a message count and
a eld of event bytes
12
13
14
15
16
17
18
19
20
21
22
23
24
Program Controller
Poll Controller
Force Multiple Coils
Preset Multiple Registers
Report Slave ID
X
X
Digital output from the slave
General purpose register within the slave
Slave type / ‘RUN’ status
Program 884 / M84
Reset Comm. Link
Read General Reference
Write General Reference
Mask Write 4X Register
Read/Write 4X Registers
Read FIFO Queue
■ Exception Codes
CODE NAME
01
02
03
04
05
06
07
08
Illegal Function
X
X
X
Function code is not allowable for the slave
Address is not available within the slave
Data is not valid for the function
Illegal Data Address
Illegal Data Value
Slave Device Failure
Acknowledge
Slave Device Busy
Negative Acknowledge
Memory Parity Error
60M SPECIFICATIONS
ES-6606 Rev.12 Page 3/5
http://www.m-system.co.jp/
MODEL: 60M
■ Diagnostic Subfunctions
CODE NAME
00
01
02
03
04
Return Query Data
X
X
X
X
X
Loop back test
Restart Comm. Option
Return Diagnostic Register
Change ASCII Input Delimiter
Force Listen Only Mode
Reset the slave and clear all counters
Contents of the diagnostic data (2 bytes)
Delimiter character of ASCII message
Force the slave into Listen Only Mode
MODBUS I/O ASSIGNMENT
TYPE
ADDRESS
DATA TYPE
2
DATA
1
X
X
X
X
X
X
Coil (0X)
1 – 16
17 – 32
1 – 16
Averaging SW *
Sampling rate SW **
Inputs (1X)
X
X
Analog channel status (active channel)
Analog status (out of range)
Analog input
17 – 32
1 – 16
Input Registers (3X)
Holding Registers (4X)
I
17 – 48
1 – 16
F
I
Analog input
X
X
X
X
Analog output
17 – 48
49 – 80
81 – 112
F
F
F
Analog output
X
X
Full scale
Zero scale
■ Type
1
2
: Analog input
: Analog output
■ Data Type
F
I
: Floating
: Int 0 – 10000 (0 – 100%)
*Averaging SW
1
2
3
: 4 samples
: 2 samples
: None
**Sampling rate SW
17 : 400 millisec.
18 : 240 millisec.
19 : 160 millisec.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
7
14
6
5
12
4
3
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
8
9
15 10
1
11
2
14–M3.5
SCREW
14
72 (2.83)
(.55)
109 (4.29)
139 (5.47)
60 (2.36)
72 (2.83)
38 (1.50)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
60M SPECIFICATIONS
ES-6606 Rev.12 Page 4/5
http://www.m-system.co.jp/
MODEL: 60M
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
COMMUNICATION MODULE
INDICATOR ROTARY
Terminator
DA
LED
SW
*
To 10-RACK,
18-RACK etc.
DB
To Other
Modbus
Devices
RS-485
INTERFACE
DG
SLD
FG
TRANSMISSION
SETTING
A / D
or
D / A
Conv.
I / O
CPU
Modular Jack
for Factory
Calibration
MODULAR JACK
SERIAL
TRANSMISSION
LINE
U(+)
V(–)
FG1
7
14
8
POWER
*Attach the terminating resistor when the module is
at the termination of a transmission line.
■ COMMUNICATION CABLE CONNECTIONS
HOST PC
TERMINATOR
Tx+ / Rx+
ANALOG I/O MODULE
ANALOG I/O MODULE
DA
DB
DA
DB
Tx– / Rx–
SG
DG
SLD
FG
DG
SLD
FG
Rx+
Rx–
FG
FG
Specifications are subject to change without notice.
60M SPECIFICATIONS
ES-6606 Rev.12 Page 5/5
http://www.m-system.co.jp/