61C-081-K [MSYSTEM]

Field Network Modules 61-UNIT Series;
61C-081-K
型号: 61C-081-K
厂家: M-SYSTEM    M-SYSTEM
描述:

Field Network Modules 61-UNIT Series

文件: 总4页 (文件大小:111K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 61C  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
(Specify power suffix code R (24 V DC) when the 61C is to be  
combined with the M8BS2.)  
Field Network Modules 61-UNIT Series  
ANALOG I/O MODULE  
(CC-Link)  
[4] OPTIONS  
Functions & Features  
blank: none  
• Interfacing analog I/O signals from/to Mini-M, Pico-M and  
other signal conditioner modules with CC-Link  
• Saving power and I/O wiring inside an instrumentation  
panel  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
50  
(1.97)  
/C02: Polyurethane coating  
/C03: Rubber coating  
100  
(3.94)  
RELATED PRODUCTS  
• Installation Base (model: M2BS2)  
• Installation Base (model: M8BS2)  
3 4  
2
9
1
0
5
6
7
8
3 4  
2
9
1
0
5
6
7
8
3 4  
2
9
1
0
5
6
7
8
115  
(4.53)  
mm (inch)  
PACKAGE INCLUDES...  
• Terminating resistor (110 Ω, 0.5 W)  
MODEL: 61C-[1][2]-[3][4]  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection  
ORDERING INFORMATION  
• Code number: 61C-[1][2]-[3][4]  
Specify a code from below for each [1] through [4].  
(e.g. 61C-161-K/Q)  
CC-Link: Euro type connector terminal (applicable wire  
size: 0.2 to 2.5 mm , stripped length 7 mm)  
2
I/O: Via Installation Base (model: MxBS2)  
Power input: Via Installation Base (model: MxBS2)  
Housing material: Flame-resistant resin (black)  
Isolation: I/O to CC-Link to power  
• Specify the specification for option code /Q  
(e.g. /C01)  
Power indicator: Green LED turns on with power supplied.  
[1] NO. OF CHANNELS  
04: 4 points  
CC-Link COMMUNICATION  
CC-Link: Conforms to Version 1.10  
Station type: Remote device station  
Station No. setting: Rotary switch; 1 – 64  
Number of occupied stations:  
08: 8 points  
16: 16 points  
[2] I/O TYPE  
1: Input  
61C-04x: 1 station  
2: Output  
61C-08x: 2 stations  
3: Input/output (Select 16 for no. of channels)  
(8 points for input, 8 points for output)  
(Use Installation Base model: M8BS2-164)  
61C-161: 4 stations  
61C-162: 4 stations  
61C-163: 2 stations  
Remote I/O (RX, RY) is fixed to 32 points.  
Baud rate setting: Rotary switch  
(156kbps(factory setting), 625kbps, 2.5Mbps, 5Mbps,  
10Mbps)  
[3] POWER INPUT  
AC Power  
K: 85 – 132 V AC  
Transmission cable: Approved for CC-Link  
L RUN indicator: Red LED turns on in an normal condition.  
L ERR. indicator: Red LED turns on or flashes in an  
abnormality; off with wire breakdown.  
(Operational voltage range 85 – 132 V, 47 – 66 Hz)  
DC Power  
R: 24 V DC  
61C SPECIFICATIONS  
ES-6627 Rev.8 Page 1/4  
http://www.m-system.co.jp/  
MODEL: 61C  
SD indicator: Red LED turns on when transmitting.  
RD indicator: Red LED turns on when receiving.  
0000 – 2710 (0 – 10000).  
-15 to 0 % is a negative range represented by 2's  
complements.  
Overall range is represented by hexadecimal FA24 – 2CEC  
(-1500 – +11500), for -15 – +115 %.  
D/A CONVERSION DATA  
INPUT SPECIFICATIONS  
Analog Input  
Input range: 1 – 5 V DC  
15  
14 13 12 11 10  
9
8
7
6
5
4
3
2
1
0
Input resistance: ≥ 1 MΩ  
SIGN  
BIT  
RWw n+0  
RWw n+1  
RWw n+2  
RWw n+3  
OUTPUT 1 D/A CONVERSION DATA  
OUTPUT 2 D/A CONVERSION DATA  
OUTPUT 3 D/A CONVERSION DATA  
OUTPUT 4 D/A CONVERSION DATA  
(Each input must be isolated by signal conditioners. Non-  
isolated modules such as M2BW and M8BW are not usable.)  
A/D conversion  
SIGN  
BIT  
Moving averaging: 4 samples  
SIGN  
BIT  
Sampling rate: 160 ms  
SIGN  
BIT  
A/D conversion output: Signed binary  
Signal range 0 – 100 % is converted into hexadecimal 0000  
– 2710 (0 – 10000). -15 to 0 % is a negative range  
represented by 2's complements.  
Overall range is represented by hexadecimal FA24 – 2CEC  
(-1500 – +11500), for -15 – +115 %.  
A/D CONVERSION DATA  
SIGN  
BIT  
RWw n+7  
RWw n+11  
RWw n+15  
OUTPUT 8 D/A CONVERSION DATA  
OUTPUT 12 D/A CONVERSION DATA  
OUTPUT 16 D/A CONVERSION DATA  
SIGN  
BIT  
15  
14 13 12 11 10  
9
8
7
6
5
4
3
2
1
0
SIGN  
BIT  
RWr n+0  
RWr n+1  
RWr n+2  
RWr n+3  
INPUT 1 A/D CONVERSION DATA  
INPUT 2 A/D CONVERSION DATA  
INPUT 3 A/D CONVERSION DATA  
INPUT 4 A/D CONVERSION DATA  
SIGN  
BIT  
SIGN  
BIT  
SIGN  
BIT  
RWw n+0 through RWw n+3 for 4 outputs.  
RWw n+0 through RWw n+7 for 8 outputs or outputs of 16-input/output.  
RWw n+0 through RWw n+15 for 16 outputs.  
SIGN  
BIT  
INSTALLATION  
Power consumption  
SIGN  
BIT  
RWr n+7  
RWr n+11  
RWr n+15  
INPUT 8 A/D CONVERSION DATA  
INPUT 12 A/D CONVERSION DATA  
INPUT 16 A/D CONVERSION DATA  
AC: Approx. 4 VA  
DC: Approx. 4 W (160 mA)  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: MxBS2)  
Weight: 250 g (0.55 lb)  
SIGN  
BIT  
SIGN  
BIT  
RWr n+0 through RWr n+3 for 4 inputs.  
RWr n+0 through RWr n+7 for 8 inputs or inputs of 16-input/output.  
RWr n+0 through RWr n+15 for 16 inputs.  
PERFORMANCE in percentage of span  
A/D conversion: ±0.1 %  
D/A conversion: ±0.1 %  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Permissible power failure duration: ≤ 10 msec.  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(I/O to CC-Link to power)  
OUTPUT SPECIFICATIONS  
Analog Output  
Output range: 1 – 5 V DC  
Load resistance: 20 kΩ minimum  
(Output must be isolated with signal conditioners.  
When the transmission line is open, the last value sampled  
before failure is held. Non-isolated modules such as M2BW  
and M8BW are not usable. )  
D/A conversion input: Signed binary  
Signal range 0 – 100 % is converted into hexadecimal  
61C SPECIFICATIONS  
ES-6627 Rev.8 Page 2/4  
http://www.m-system.co.jp/  
MODEL: 61C  
EXTERNAL VIEW  
PU-2  
A
L
L
RUN  
ERR.  
E
F
SD  
RD  
PWR  
B
C
D
STATION NO.  
X
10  
X1  
B
RATE  
A: Modular jack for factory calibration  
B: Power LED  
C: Station No. Setting  
D: Baud rate Setting  
E: Status indicator LED  
F: Euro type connector terminal for CC-Link  
COMMUNICATION CABLE CONNECTIONS  
MASTER UNIT  
61C  
I/O UNIT  
TERMINATOR  
blue  
DA  
DB  
DA  
DB  
DA  
DB  
white  
yellow  
DG  
SLD  
FG  
DG  
SLD  
FG  
DG  
SLD  
FG  
EXTERNAL DIMENSIONS unit: mm (inch)  
2–M3 SCREWS  
12  
(.47)  
50 (1.97)  
38 min.  
(1.50)  
103 (4.06)  
61C SPECIFICATIONS  
ES-6627 Rev.8 Page 3/4  
http://www.m-system.co.jp/  
MODEL: 61C  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
INDICATOR ROTARY  
Terminator  
DA  
LED  
SW  
*
DB  
To Other  
CC-Link  
Devices  
CC-Link  
INTERFACE  
DG  
SLD  
FG  
A / D  
or  
D / A  
Conv.  
To  
Installation  
Base  
I / O  
CPU  
Modular Jack  
for Factory  
Calibration  
MODULAR JACK  
SERIAL  
TRANSMISSION  
LINE  
Attach the terminating resistor when the module is  
at the termination of a transmission line.  
*
Specifications are subject to change without notice.  
61C SPECIFICATIONS  
ES-6627 Rev.8 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

61C-081-K/Q

Field Network Modules 61-UNIT Series
MSYSTEM

61C-081-R

Field Network Modules 61-UNIT Series
MSYSTEM

61C-081-R/Q

Field Network Modules 61-UNIT Series
MSYSTEM

61C-082-K

Field Network Modules 61-UNIT Series
MSYSTEM

61C-082-K/Q

Field Network Modules 61-UNIT Series
MSYSTEM

61C-082-R

Field Network Modules 61-UNIT Series
MSYSTEM

61C-082-R/Q

Field Network Modules 61-UNIT Series
MSYSTEM

61C-083-K

Field Network Modules 61-UNIT Series
MSYSTEM

61C-083-K/Q

Field Network Modules 61-UNIT Series
MSYSTEM

61C-083-R

Field Network Modules 61-UNIT Series
MSYSTEM

61C-083-R/Q

Field Network Modules 61-UNIT Series
MSYSTEM

61C-161-K

Field Network Modules 61-UNIT Series
MSYSTEM