MODEL: ADN  
Limit Alarms (potentiometer adj.) A-UNIT  
[1] SETPOINT 1 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
TWO-WIRE TRANSMITTER ALARM  
(with square root extractor)  
Functions & Features  
• Powering a 4 – 20 mA DC current loop  
• Providing SPDT relay outputs at preset current levels  
• Shortcircuit protection  
[2] SETPOINT 2 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
• Square root extraction  
• Applicable to smart transmitters  
• Dual (Hi/Lo) trip  
• Energized or de-energized coil at a tripped condition  
selectable  
[3] POWER INPUT  
AC Power  
• Deadband (hysteresis) adjustable  
• Enclosed relays  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
• Relays can be powered 110 V DC  
• High-density mounting  
Typical Applications  
• Annunciator  
• Various alarm applications  
DC Power  
S: 12 V DC  
50  
(1.97)  
R: 24 V DC  
V: 48 V DC  
P: 110 V DC  
80  
(3.15)  
[4] OPTIONS  
blank: none  
132  
(5.20)  
/Q: With options (specify the specification)  
mm (inch)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
MODEL: ADN–1[1][2]–[3][4]  
/C02: Polyurethane coating  
ORDERING INFORMATION  
• Code number: ADN-1[1][2]-[3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. ADN-111-B/Q)  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals  
INPUT  
Current  
Screw terminal: Chromated steel (standard) or stainless  
steel  
4 – 20 mA DC (Input resistance 250 Ω)  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output 1 to output 2 to power  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
Setpoint adjustments: 270°-turn screwdriver adjustments  
(front); 0 – 100 % independently  
SETPOINT ADJUSTMENTS  
1: Single-turn screws  
ADN SPECIFICATIONS  
ES-2124 Rev.7 Page 1/4  
http://www.m-system.co.jp/  
MODEL: ADN  
Low-end cutout function: Below 1 % input. A setpoint below  
10 % output equals 0 %.  
approx. 2 W (80 mA at 24 V)  
Operating temperature: -5 to +60°C (23 to 140°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Deadband (hysteresis) adjustments: 1 - 100% of square root  
value (rear)  
Front LEDs: LED turns on at a tripped condition; red for  
output 1, green for output 2  
Weight: 380 g (0.84 lb)  
Power ON timer: Relays de-energized for approx. 2 seconds  
after power is turned on.  
PERFORMANCE in percentage of span  
Trip point repeatability: ±0.5 % with input 1 – 100 %  
Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)  
SUPPLY OUTPUT  
Response time: ≤ 1 sec. (0 – 100 % at 90 % setpoint)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output 1  
to output 2 to power to ground)  
Output voltage: 24 – 28 V DC with no load  
Current rating: ≤ 22 mA DC  
Shortcircuit Protection  
Current limited: 35 mA max.  
Protected time duration: No limit  
INPUT SPECIFICATIONS  
DC Current: Input resistor incorporated  
OUTPUT SPECIFICATIONS  
Relay Contact: 100 V AC @ 1 A (cos ø = 1)  
120 V AC @ 1 A (cos ø = 1)  
240 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 1 A (resistive load)  
Maximum switching voltage: 380 V AC or 125 V DC  
Maximum switching power: 120 VA or 30 W  
Minimum load: 5 V DC @ 10 mA  
Mechanical life: 5 x 10 cycles  
7
For maximum relay life with inductive loads, external  
protection is recommended.  
Alarm Trip Operation Terminal No. in parentheses  
(9-11)ON  
Output 1  
(9-10)ON  
(1-3)ON  
Output 2  
(1-2)ON  
Input  
(%)  
0
50  
100  
Output 2  
Setpoint  
Output 1  
Setpoint  
Trip Operation in Power Failure  
Output Code: 1 & 4: Terminals 1 – 2, 9 – 10 turn ON  
Output Code: 2 & 3: Terminals 1 – 3, 9 – 11 turn ON  
INSTALLATION  
Power input  
AC: Operational voltage range: rating ±10 %,  
50/60 ± 2 Hz, approx. 2.5 VA  
DC: Operational voltage range: rating ±10 %, or 85 – 150  
V for 110 V rating (ripple 10 % p-p max.)  
ADN SPECIFICATIONS  
ES-2124 Rev.7 Page 2/4  
http://www.m-system.co.jp/  
MODEL: ADN  
EXTERNAL VIEW  
No.1 Setpoint Adj.  
No.1 LED  
Span Adj.  
Zero Adj.  
No.1 Deadband (Hysteresis) Adj.  
No.2 Deadband (Hysteresis) Adj.  
No.2 LED  
No.2 Setpoint Adj.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
8
7
6
5
4
2
4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
9
3
2
10 11  
1
11  
M3.5  
SCREW  
50 (1.97)  
103 (4.06)  
132 (5.20)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
2-WIRE  
TRANSMITTER  
HYSTERESIS  
SETPOINT (DEADBAND)  
24V DC  
Supply  
*
+
+
4
5
6
Z
S
11  
10  
9
H
Low Drift  
Amplifier  
Square Root  
Extractor  
+
Comparator  
Ry  
SETPOINT 1  
OUTPUT  
L
MONITOR  
V
(1 – 5V DC)  
C
250Ω  
*
3
H
Comparator  
Ry  
SETPOINT 2  
OUTPUT  
2
L
1
C
HYSTERESIS  
(DEADBAND)  
SETPOINT  
7
U(+)  
V(–)  
POWER  
8
Base Socket  
* Relay status for output codes “1” & “4”, at power OFF.  
Relay Protection  
• AC Powered  
• DC Powered  
Inductive  
Load (Coil)  
Inductive  
Load (Coil)  
Varistor or Spark  
Quenching Circuit  
Diode, Varistor or  
CR Circuit  
LOAD  
LOAD  
U
ADN SPECIFICATIONS  
ES-2124 Rev.7 Page 3/4  
http://www.m-system.co.jp/  
MODEL: ADN  
Specifications are subject to change without notice.  
ADN SPECIFICATIONS  
ES-2124 Rev.7 Page 4/4  
http://www.m-system.co.jp/  

ADN-122-S 相关器件

型号 制造商 描述 价格 文档
ADN-122-S/Q MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT 获取价格
ADN-122-V MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT 获取价格
ADN-122-V/Q MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT 获取价格
ADN-123-B MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT 获取价格
ADN-123-B/Q MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT 获取价格
ADN-123-C MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT 获取价格
ADN-123-C/Q MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT 获取价格
ADN-123-D MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT 获取价格
ADN-123-D/Q MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT 获取价格
ADN-123-E MSYSTEM Limit Alarms (potentiometer adj.) A-UNIT 获取价格

ADN-122-S 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8