MODEL: ALTG  
U: Specify voltage (See INPUT SPECIFICATIONS)  
Limit Alarms (rotary switch adj.) AL-UNIT  
(0 % input must be 0 V.)  
TACHOGENERATOR ALARM  
Functions & Features  
[2] SETPOINT 1 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
• Providing SPDT relay outputs at preset AC voltage levels  
from a tachogenerator  
• Dual (Hi/Lo) trip  
• Energized or de-energized coil at a tripped condition  
selectable  
• Rotary switch setpoint adjustments  
• Enclosed relays  
[3] SETPOINT 2 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
• Relays can be powered 110 V DC  
• High-density mounting  
Typical Applications  
• Annunciator  
[4] POWER INPUT  
AC Power  
• Various alarm applications  
50  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
(1.97)  
80  
(3.15)  
132  
(5.20)  
DC Power  
mm (inch)  
S: 12 V DC  
R: 24 V DC  
MODEL: ALTG-[1][2][3]-[4][5]  
V: 48 V DC  
P: 110 V DC  
ORDERING INFORMATION  
• Code number: ALTG-[1][2][3]-[4][5]  
Specify a code from below for each of [1] through [5].  
(e.g. ALTG-111-B/Q)  
[5] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
• Special input range (For code U)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
[1] INPUT  
/C02: Polyurethane coating  
Voltage  
/C03: Rubber coating  
1: 0 – 35 V AC (Input resistance 100 kΩ min.)  
2: 0 – 50 mV AC (Input resistance 100 kΩ min.)  
3: 0 – 60 mV AC (Input resistance 100 kΩ min.)  
4: 0 – 100 mV AC (Input resistance 100 kΩ min.)  
5: 0 – 1 V AC (Input resistance 100 kΩ min.)  
6: 0 – 10 V AC (Input resistance 100 kΩ min.)  
7: 0 – 100 V AC (Input resistance 100 kΩ min.)  
8: 0 – 110 V AC (Input resistance 100 kΩ min.)  
9: 0 – 150 V AC (Input resistance 100 kΩ min.)  
A: 0 – 200 V AC (Input resistance 100 kΩ min.)  
B: 0 – 250 V AC (Input resistance 100 kΩ min.)  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output 1 to output 2 to power  
Setpoint adjustments: 10-position rotary switches (front); 0  
ALTG SPECIFICATIONS  
ES-2739 Rev.8 Page 1/4  
http://www.m-system.co.jp/  
MODEL: ALTG  
– 99 % independently; 1 % increments  
PERFORMANCE in percentage of span  
Setpoint accuracy: ±0.9 %  
Hysteresis (deadband): 0.7 – 2.5 %  
Front LEDs: Red LED turns on when the coil is energized.  
Power ON timer: Relays de-energized for approx. 2 seconds  
after power is turned on.  
Trip point repeatability: ±0.05 %  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: Approx. 0.5 sec. (0 – 100 % at 90 %  
setpoint)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output 1  
to output 2 to power to ground)  
INPUT SPECIFICATIONS  
AC Voltage: 0 – 250 V AC  
Minimum span: 50 mV  
Frequency: 15 Hz min., 1 kHz max. with 100 % input  
Input resistance: ≥ 100 kΩ  
OUTPUT SPECIFICATIONS  
Relay Contact: 100 V AC @ 1 A (cos ø = 1)  
120 V AC @ 1 A (cos ø = 1)  
240 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 1 A (resistive load)  
Maximum switching voltage: 380 V AC or 125 V DC  
Maximum switching power: 120 VA or 30 W  
Minimum load: 5 V DC @ 10 mA  
Mechanical life: 5 x 10 cycles  
7
For maximum relay life with inductive loads, external  
protection is recommended.  
Alarm Trip Operation Terminal No. in parentheses  
(9-11)ON  
Output 1  
(9-10)ON  
(1-3)ON  
Output 2  
(1-2)ON  
Input  
(%)  
0
50  
100  
Output 2  
Setpoint  
Output 1  
Setpoint  
Trip Operation in Power Failure  
Output Code: 1 & 4: Terminals 1 – 2, 9 – 10 turn ON  
Output Code: 2 & 3: Terminals 1 – 3, 9 – 11 turn ON  
INSTALLATION  
Power input  
AC: Operational voltage range: rating ±10 %,  
50/60 ±2 Hz, approx. 2 VA  
DC: Operational voltage range: rating ±10 %, or 85 – 150  
V for 110 V rating (ripple 10 % p-p max.)  
approx. 2 W (80 mA at 24 V)  
Operating temperature: -5 to +60°C (23 to 140°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 370 g (0.82 lb)  
ALTG SPECIFICATIONS  
ES-2739 Rev.8 Page 2/4  
http://www.m-system.co.jp/  
MODEL: ALTG  
EXTERNAL VIEW  
No.1 LED  
No.1 Setpoint Rotary SW (x10%)  
No.1 Setpoint Rotary SW (x1%)  
No.2 Setpoint Rotary SW (x10%)  
No.2 Setpoint Rotary SW (x1%)  
No.2 LED  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
8
7
6
5
4
2
4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
9
3
2
10 11  
1
11  
M3.5  
SCREW  
50 (1.97)  
103 (4.06)  
132 (5.20)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
D / A  
Converter  
ROTARY  
SWITCH  
*
11  
10  
9
H
AC  
Amplifier  
R.M.S.  
Operation  
5
6
4
Comparator  
Comparator  
Ry  
Ry  
SETPOINT 1  
OUTPUT  
L
INPUT  
C
*
3
H
SETPOINT 2  
OUTPUT  
2
L
D / A  
Converter  
ROTARY  
SWITCH  
1
C
7
U(+)  
V(–)  
POWER  
8
Base Socket  
*Relay status for output codes “1” & “4”, at power OFF.  
Relay Protection  
• AC Powered  
• DC Powered  
Inductive  
Load (Coil)  
Inductive  
Load (Coil)  
Varistor or Spark  
Quenching Circuit  
Diode, Varistor or  
CR Circuit  
LOAD  
LOAD  
U
ALTG SPECIFICATIONS  
ES-2739 Rev.8 Page 3/4  
http://www.m-system.co.jp/  
MODEL: ALTG  
Specifications are subject to change without notice.  
ALTG SPECIFICATIONS  
ES-2739 Rev.8 Page 4/4  
http://www.m-system.co.jp/  

ALTG-312-S/Q 相关器件

型号 制造商 描述 价格 文档
ALTG-312-V MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALTG-312-V/Q MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALTG-313- MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALTG-313-/Q MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALTG-313-B MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALTG-313-B/Q MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALTG-313-C MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALTG-313-C/Q MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALTG-313-D MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALTG-313-D/Q MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格

ALTG-312-S/Q 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8