ALV-D41-J

更新时间:2024-10-29 23:03:02
品牌:MSYSTEM
描述:Limit Alarms (rotary switch adj.) AL-UNIT

ALV-D41-J 概述

Limit Alarms (rotary switch adj.) AL-UNIT

ALV-D41-J 数据手册

通过下载ALV-D41-J数据手册来全面了解它。这个PDF文档包含了所有必要的细节,如产品概述、功能特性、引脚定义、引脚排列图等信息。

PDF下载
MODEL: ALV  
K: 0 – 100 μA DC (Input resistance 1000 Ω)  
Limit Alarms (rotary switch adj.) AL-UNIT  
GW: -1 – +1 mA DC (Input resistance 1000 Ω)  
FW: -10 – +10 mA DC (Input resistance 100 Ω)  
Z: Specify current (See INPUT SPECIFICATIONS)  
Voltage  
DC ALARM  
Functions & Features  
• Providing SPDT relay outputs at preset DC input levels  
• Dual (Hi/Lo) trip  
1: 0 – 10 mV DC (Input resistance 10 kΩ min.)  
15: 0 – 50 mV DC (Input resistance 10 kΩ min.)  
16: 0 – 60 mV DC (Input resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Input resistance 100 kΩ min.)  
3: 0 – 1 V DC (Input resistance 1 MΩ min.)  
4: 0 – 10 V DC (Input resistance 1 MΩ min.)  
5: 0 – 5 V DC (Input resistance 1 MΩ min.)  
6: 1 – 5 V DC (Input resistance 1 MΩ min.)  
4W: -10 – +10 V DC (Input resistance 1 MΩ min.)  
5W: -5 – +5 V DC (Input resistance 1 MΩ min.)  
0: Specify voltage (See INPUT SPECIFICATIONS)  
• Energized or de-energized coil at a tripped condition  
selectable  
• Rotary switch setpoint adjustments  
• Enclosed relays  
• Relays can be powered 110 V DC  
• Isolation up to 2000 V AC  
• High-density mounting  
Typical Applications  
• Annunciator  
• Various alarm applications  
[2] SETPOINT 1 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
50  
(1.97)  
80  
(3.15)  
[3] SETPOINT 2 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
132  
(5.20)  
mm (inch)  
MODEL: ALV-[1][2][3]-[4][5]  
[4] POWER INPUT  
AC Power  
ORDERING INFORMATION  
• Code number: ALV-[1][2][3]-[4][5]  
Specify a code from below for each of [1] through [5].  
(e.g. ALV-A13-B/Q)  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
• Special input range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
DC Power  
[1] INPUT  
S: 12 V DC  
Current  
R: 24 V DC  
A: 4 – 20 mA DC (Input resistance 250 Ω)  
A1: 4 – 20 mA DC (Input resistance 50 Ω)  
B: 2 – 10 mA DC (Input resistance 500 Ω)  
C: 1 – 5 mA DC (Input resistance 1000 Ω)  
D: 0 – 20 mA DC (Input resistance 50 Ω)  
E: 0 – 16 mA DC (Input resistance 62.5 Ω)  
F: 0 – 10 mA DC (Input resistance 100 Ω)  
G: 0 – 1 mA DC (Input resistance 1000 Ω)  
H: 10 – 50 mA DC (Input resistance 100 Ω)  
J: 0 – 10 μA DC (Input resistance 1000 Ω)  
V: 48 V DC  
P: 110 V DC  
ALV SPECIFICATIONS  
ES-2717 Rev.8 Page 1/4  
http://www.m-system.co.jp/  
MODEL: ALV  
[5] OPTIONS  
Alarm Trip Operation Terminal No. in parentheses  
blank: none  
(9-11)ON  
/Q: With options (specify the specification)  
Output 1  
Output 2  
(9-10)ON  
(1-3)ON  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
(1-2)ON  
Input  
(%)  
0
50  
100  
/C02: Polyurethane coating  
Output 2  
Setpoint  
Output 1  
Setpoint  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
Trip Operation in Power Failure  
Output Code: 1 & 4: Terminals 1 – 2, 9 – 10 turn ON  
Output Code: 2 & 3: Terminals 1 – 3, 9 – 11 turn ON  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
INSTALLATION  
Power input  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
AC: Operational voltage range: rating ±10 %,  
50/60 ±2 Hz, approx. 2 VA  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output 1 to output 2 to power  
Setpoint adjustments: 10-position rotary switches (front); 0  
– 99 % independently; 1 % increments  
Hysteresis (deadband): 0.7 – 2.5 %  
DC: Operational voltage range: rating ±10 %, or 85 – 150  
V for 110 V rating (ripple 10 % p-p max.)  
approx. 2 W (80 mA at 24 V)  
Operating temperature: -5 to +60°C (23 to 140°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Front LEDs: Red LED turns on when the coil is energized.  
Power ON timer: Relays de-energized for approx. 2 seconds  
after power is turned on.  
Weight: 370 g (0.82 lb)  
PERFORMANCE in percentage of span  
Setpoint accuracy: ±0.5 %  
INPUT SPECIFICATIONS  
DC Current:  
Trip point repeatability: ±0.05 %  
Shunt resistor attached to the input terminals (0.5 W)  
Specify input resistance value for code Z.  
DC Voltage: -300 – +300 V DC  
Minimum span: 10 mV  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: Approx. 0.5 sec. (0 – 100 % at 90 %  
setpoint)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output 1  
to output 2 to power to ground)  
Offset: Max. 1.5 times span  
Input resistance  
Span 10 – 100 mV : ≥ 10 kΩ  
Span 0.1 – 1 V : ≥ 100 kΩ  
Span ≥ 1 V : ≥ 1 MΩ  
OUTPUT SPECIFICATIONS  
Relay Contact: 100 V AC @ 1 A (cos ø = 1)  
120 V AC @ 1 A (cos ø = 1)  
240 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 1 A (resistive load)  
Maximum switching voltage: 380 V AC or 125 V DC  
Maximum switching power: 120 VA or 30 W  
Minimum load: 5 V DC @ 10 mA  
Mechanical life: 5 x 10 cycles  
7
For maximum relay life with inductive loads, external  
protection is recommended.  
ALV SPECIFICATIONS  
ES-2717 Rev.8 Page 2/4  
http://www.m-system.co.jp/  
MODEL: ALV  
EXTERNAL VIEW  
No.1 LED  
No.1 Setpoint Rotary SW (x10%)  
No.1 Setpoint Rotary SW (x1%)  
No.2 Setpoint Rotary SW (x10%)  
No.2 Setpoint Rotary SW (x1%)  
No.2 LED  
EXTERNAL DIMENSIONS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
8
7
6
5
4
2
4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
9
3
2
10 11  
1
11  
M3.5  
SCREW  
50 (1.97)  
103 (4.06)  
132 (5.20)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
TERMINAL ASSIGNMENTS unit: mm (inch)  
INPUT RESISTOR  
(model: REM)  
8
7
6
5
4
9
3
2
10 11  
1
Input shunt resistor attached  
for current input.  
ALV SPECIFICATIONS  
ES-2717 Rev.8 Page 3/4  
http://www.m-system.co.jp/  
MODEL: ALV  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Relay Protection  
• AC Powered  
Inductive  
Load (Coil)  
D / A  
Converter  
ROTARY  
SWITCH  
Varistor or Spark  
Quenching Circuit  
**  
11  
10  
9
LOAD  
H
Low Drift  
Amplifier  
+
5
6
4
Comparator  
Comparator  
Ry  
Ry  
SETPOINT 1  
OUTPUT  
*
U
L
INPUT  
R
• DC Powered  
Inductive  
Load (Coil)  
C
**  
Diode, Varistor or  
CR Circuit  
3
H
LOAD  
SETPOINT 2  
OUTPUT  
2
L
D / A  
Converter  
ROTARY  
SWITCH  
1
C
7
U(+)  
V(–)  
POWER  
8
Base Socket  
* Input shunt resistor attached for current input.  
**Relay status for output codes “1” & “4”, at power OFF.  
Specifications are subject to change without notice.  
ALV SPECIFICATIONS  
ES-2717 Rev.8 Page 4/4  
http://www.m-system.co.jp/  

ALV-D41-J 相关器件

型号 制造商 描述 价格 文档
ALV-D41-J/Q MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALV-D41-P MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALV-D41-P/Q MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALV-D41-R MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALV-D41-R/Q MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALV-D41-S MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALV-D41-S/Q MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALV-D41-V MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALV-D41-V/Q MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格
ALV-D42- MSYSTEM Limit Alarms (rotary switch adj.) AL-UNIT 获取价格

ALV-D41-J 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8