ARB-5113-J/Q 概述
Limit Alarms (potentiometer adj.) A-UNIT
ARB-5113-J/Q 数据手册
通过下载ARB-5113-J/Q数据手册来全面了解它。这个PDF文档包含了所有必要的细节,如产品概述、功能特性、引脚定义、引脚排列图等信息。
PDF下载MODEL: ARB
5: Pt 50 Ω (JIS'81)
Limit Alarms (potentiometer adj.) A-UNIT
(Usable range: -200 to +500°C, -328 to +932°F; min.span: 100°C, 180°F)
6: Ni 508.4 Ω
RTD ALARM
Functions & Features
(Usable range: -50 to +200°C, -58 to +392°F; min.span: 30°C, 54°F)
0: Specify
• Providing SPDT relay outputs at preset input levels
• Direct input from an RTD
Note: Consult M-System for 2-wire RTD
• Dual (Hi/Lo) trip
SETPOINT ADJUSTMENTS
• Linearization
1: Single-turn screws
• Burnout protection
• "Active bridge" circuit containing two constant current
sources allows large leadwire resistances up to 200 Ω
• Energized or de-energized coil at a tripped condition
selectable
[2] SETPOINT 1 OUTPUT
1: Hi (coil energized at alarm)
2: Hi (coil de-energized at alarm)
3: Lo (coil energized at alarm)
4: Lo (coil de-energized at alarm)
• Hysteresis (deadband) adjustable
• Enclosed relays
• Relays can be powered 110 V DC
• High-density mounting
[3] SETPOINT 2 OUTPUT
1: Hi (coil energized at alarm)
2: Hi (coil de-energized at alarm)
3: Lo (coil energized at alarm)
4: Lo (coil de-energized at alarm)
Typical Applications
• Annunciator
• Various alarm applications
50
(1.97)
[4] POWER INPUT
AC Power
B: 100 V AC
C: 110 V AC
D: 115 V AC
F: 120 V AC
G: 200 V AC
H: 220 V AC
J: 240 V AC
80
(3.15)
132
(5.20)
mm (inch)
DC Power
S: 12 V DC
MODEL: ARB-[1]1[2][3]-[4][5]
R: 24 V DC
V: 48 V DC
ORDERING INFORMATION
• Code number: ARB-[1]1[2][3]-[4][5]
Specify a code from below for each of [1] through [5].
(e.g. ARB-1111-B/BL/Q)
P: 110 V DC
[5] OPTIONS (multiple selections)
Burnout
• Temperature range (e.g. 0 – 200°C)
• Specify the specification for option code /Q
(e.g. /C01/S01)
blank: Upscale burnout
/BL: Downscale burnout
Other Options
blank: none
[1] INPUT RTD (2- or 3-wire)
1: JPt 100 (JIS'89)
/Q: Option other than the above (specify the specification)
(Usable range: -200 to +500°C, -328 to +932°F; min.span: 50°C, 90°F)
3: Pt 100 (JIS'89)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
(Usable range: -200 to +650°C, -328 to +1202°F; min.span: 50°C, 90°F)
4: Pt 100 (JIS'97, IEC)
/C02: Polyurethane coating
(Usable range: -200 to +650°C, -328 to +1202°F; min.span: 50°C, 90°F)
/C03: Rubber coating
ARB SPECIFICATIONS
ES-2113 Rev.8 Page 1/4
http://www.m-system.co.jp/
MODEL: ARB
TERMINAL SCREW MATERIAL
INSTALLATION
Power input
/S01: Stainless steel
• AC: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 2 VA
GENERAL SPECIFICATIONS
Construction: Plug-in
• DC: Operational voltage range: rating ±10 %, or 85 – 150
V for 110 V rating (ripple 10 % p-p max.)
approx. 2 W (80 mA at 24 V)
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Housing material: Flame-resistant resin (black)
Isolation: Input to output 1 to output 2 to power
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
Setpoint adjustments: 270°-turn screwdriver adjustments
(front); 0 – 100 % independently
Weight: 450 g (0.99 lb)
PERFORMANCE in percentage of span
Trip point repeatability: ±0.5 %
Hysteresis (deadband) adjustments: 1 – 100 % (front)
Linearization: Standard
Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)
Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint)
Burnout response: ≤ 10 sec.
Front LEDs: LED turns on at a tripped condition; red for
output 1, green for output 2
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output 1
to output 2 to power to ground)
Power ON timer: Relays de-energized for approx. 2 seconds
after power is turned on.
INPUT SPECIFICATIONS
Maximum leadwire resistance: 200 Ω per wire (3-wire)
Sensing current: 2 mA
OUTPUT SPECIFICATIONS
■ Relay Contact: 100 V AC @ 1 A (cos ø = 1)
120 V AC @ 1 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 380 V AC or 125 V DC
Maximum switching power: 120 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Mechanical life: 5 x 10 cycles
7
For maximum relay life with inductive loads, external
protection is recommended.
Alarm Trip Operation Terminal No. in parentheses
(9-11)ON
Output 1
(9-10)ON
(1-3)ON
Output 2
(1-2)ON
Input
(%)
0
▲
50
▲
100
Output 2
Setpoint
Output 1
Setpoint
Trip Operation in Power Failure
• Output Code: 1 & 4: Terminals 1 – 2, 9 – 10 turn ON
• Output Code: 2 & 3: Terminals 1 – 3, 9 – 11 turn ON
ARB SPECIFICATIONS
ES-2113 Rev.8 Page 2/4
http://www.m-system.co.jp/
MODEL: ARB
EXTERNAL VIEW
No.1 Setpoint Adj.
No.1 LED
Span Adj.
Zero Adj.
No.1 Deadband (Hysteresis) Adj.
No.2 Deadband (Hysteresis) Adj.
No.2 LED
No.2 Setpoint Adj.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
8
7
6
5
4
2
–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
9
3
2
10 11
1
11
–M3.5
SCREW
50 (1.97)
103 (4.06)
132 (5.20)
40 (1.57)
50 (1.97)
[3.3 (.13)]
• When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Burnout
HYSTERESIS
SETPOINT (DEADBAND)
RTD
*
4
5
6
A
B
B
Z
S
11
10
9
H
Reference
Resistor
+
–
Differential
Amplifier
Comparator
Ry
SETPOINT 1
OUTPUT
L
2mA
2mA
C
*
Linearizer
3
H
Comparator
Ry
SETPOINT 2
OUTPUT
2
L
1
C
HYSTERESIS
(DEADBAND)
SETPOINT
7
U(+)
V(–)
POWER
8
Base Socket
*Relay status for output codes “1” & “4”, at power OFF.
■ Relay Protection
• AC Powered
• DC Powered
Inductive
Load (Coil)
Inductive
Load (Coil)
Varistor or Spark
Quenching Circuit
Diode, Varistor or
CR Circuit
LOAD
LOAD
U
ARB SPECIFICATIONS
ES-2113 Rev.8 Page 3/4
http://www.m-system.co.jp/
MODEL: ARB
Specifications are subject to change without notice.
ARB SPECIFICATIONS
ES-2113 Rev.8 Page 4/4
http://www.m-system.co.jp/
ARB-5113-J/Q 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
ARB-5113-P | MSYSTEM | Limit Alarms (potentiometer adj.) A-UNIT | 获取价格 | |
ARB-5113-P/BL | MSYSTEM | Limit Alarms (potentiometer adj.) A-UNIT | 获取价格 | |
ARB-5113-P/Q | MSYSTEM | Limit Alarms (potentiometer adj.) A-UNIT | 获取价格 | |
ARB-5113-R | MSYSTEM | Limit Alarms (potentiometer adj.) A-UNIT | 获取价格 | |
ARB-5113-R/BL | MSYSTEM | Limit Alarms (potentiometer adj.) A-UNIT | 获取价格 | |
ARB-5113-R/Q | MSYSTEM | Limit Alarms (potentiometer adj.) A-UNIT | 获取价格 | |
ARB-5113-S | MSYSTEM | Limit Alarms (potentiometer adj.) A-UNIT | 获取价格 | |
ARB-5113-S/BL | MSYSTEM | Limit Alarms (potentiometer adj.) A-UNIT | 获取价格 | |
ARB-5113-S/Q | MSYSTEM | Limit Alarms (potentiometer adj.) A-UNIT | 获取价格 | |
ARB-5113-V | MSYSTEM | Limit Alarms (potentiometer adj.) A-UNIT | 获取价格 |
ARB-5113-J/Q 相关文章
- 2024-09-20
- 5
- 2024-09-20
- 8
- 2024-09-20
- 8
- 2024-09-20
- 6