AS4T-2-P/UL [MSYSTEM]

Plug-in Signal Conditioners M-UNIT;
AS4T-2-P/UL
型号: AS4T-2-P/UL
厂家: M-SYSTEM    M-SYSTEM
描述:

Plug-in Signal Conditioners M-UNIT

文件: 总4页 (文件大小:166K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: AS4T  
R: 24 V DC  
Plug-in Signal Conditioners M-UNIT  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
P: 110 V DC  
THERMOCOUPLE ALARM  
(dual or quad alarm trip; field-configurable)  
Functions & Features  
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)  
[3] OPTIONS (multiple selections)  
Standards & Approvals  
• Provides relay outputs at preset temperature levels  
• Quad or dual trip  
blank: CE marking  
• Setting and display in engineering unit values  
• Setpoint adjustments with the front keypad  
• Software lock  
/UL: UL approval, CE marking  
Other Options  
blank: none  
• Adjustable hysteresis (deadband)  
• On-delay timer  
/Q: Option other than the above (specify the specification)  
• Hi/Lo trip and energized/de-energized coil independently  
selectable for each setpoint  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
• Enclosed relays  
• Relays can be powered by 200 V AC and 100 V DC  
• High-density mounting on DIN rail  
/C02: Polyurethane coating  
/C03: Rubber coating (UL not available)  
TERMINAL SCREW MATERIAL  
Typical Applications  
• Annunciator  
/S01: Stainless steel (UL not available)  
EX-FACTORY SETTING  
• Various alarm applications  
50  
(1.97)  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-1608)  
80  
(3.15)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
132  
(5.20)  
mm (inch)  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
Burnout: Upscale standard; downscale optional by  
programming  
MODEL: AS4T–[1]–[2][3]  
Sampling cycle: 100 msec.  
User-configurable items: Front key pad  
• Alarm setpoint  
ORDERING INFORMATION  
• Code number: AS4T-[1]-[2][3]  
Specify a code from below for each of [1] through [3].  
(e.g. AS4T-2-R/UL/Q)  
• Power ON-delay time  
• Alarm ON-delay time  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
• Moving average  
• Hi/Lo trip operation  
• Coil at alarm  
[1] OUTPUT  
• Hysteresis (deadband)  
• Temperature range  
2: 4 points; N.O. or make contact  
3: 4 points; N.C. or break contact  
5: 2 points; SPDT or transfer contact  
• Temperature unit  
• Thermocouple  
• Others  
(Refer to the instruction manual)  
DISPLAY  
[2] POWER INPUT  
AC Power  
LED: 8 mm (.31”) 7 segment, red  
Number of display digits: 4 digits for DATA display;  
2 digits for ITEM display  
M2: 100 – 240 V AC, 50 – 60 Hz  
(Operational voltage range 85 – 264 V, 47 – 66 Hz)  
DC Power  
AS4T SPECIFICATIONS  
ES-1608 Rev.16 Page 1/4  
https://www.m-system.co.jp/  
MODEL: AS4T  
PV indication: Temperature in engineering unit  
Overrange indication: LEDs blinking  
Mechanical life: 5 × 10 cycles  
7
Power saving mode: Displays turn off if the keys are  
untouched for a preset time period  
(Note): The value indicate capacity of output relay in  
equipment.  
LEDs: Red LEDs turn on when coils are energized.  
(L1 and L2 for 2-point alarm. L1, L2, L3 and L4 for 4-point  
alarm.)  
Use within relay rating for EU and UL.  
Alarm Trip Operation  
Terminal No. in parentheses  
Example with quad N.O. contacts (LL, L, H, HH)  
ON OFF  
L1 (9–10)  
INPUT SPECIFICATIONS  
Input resistance: 1 MΩ min.  
ON OFF  
L2 (1–2)  
Burnout sensing: 45 nA ±10 %  
Default setting: K (CA) -100.0 – +999.9°C  
Minimum step:  
OFF ON  
L3 (1–3)  
OFF ON  
L4 (9–11)  
Input  
(%)  
-199.9 to 999.9: 0.1  
0
50  
100  
Not greater than -200, not lower than 1000: 1  
LL  
L
H
HH  
Temperature range  
Trip Operation in Power Failure  
• Output code 2: All relays turn off.  
• Output code 3: All relays turn on.  
CONFORMANCE  
USABLE RANGE  
T/C  
LIMIT  
• Output code 5: Terminals 1 – 3, 9 – 11 turn on.  
°C  
-52 to +1860  
°F  
-61.6 to +3380  
°C  
150  
°F  
302  
(PR) *  
K (CA) *  
E (CRC) *  
J (IC)  
-272 to +1472  
-272 to +1020  
-260 to +1300  
-272 to +500  
24 to 1920  
-458 to +2682  
-458 to +1868  
-436 to +2372  
-458 to +932  
75.2 to 3488  
-148 to +3380  
-148 to +3380  
-61.6 to +4381  
-458 to +2552  
-422 to +1112  
-422 to +1832  
-61.6 to +2725  
-200  
-200  
-260  
-200  
450  
150  
-328  
-328  
-436  
-328  
842  
INSTALLATION  
Power consumption  
AC: ≤ 6 VA  
T (CC) *  
B (RH) *  
R *  
DC: ≤ 3.5 W  
-100 to +1860  
-100 to +1860  
302  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
S *  
150  
302  
C (WRe 5-26) -52 to +2416  
-52  
-61.6  
-328  
-422  
-422  
-61.6  
N
-272 to +1400  
-252 to +600  
-252 to +1000  
-52 to +1496  
-200  
-252  
-252  
-52  
U
Weight: 500 g (1.1 lb)  
L
P (Platinel II)  
* For temperatures ranges near the lower limit of the usable range,  
PERFORMANCE in percentage of FS input  
Setpoint accuracy (trip point accuracy): ±(0.1 % of FS + 1  
digit)  
the transmitter may not satisfy the described accuracy.  
Display accuracy: ±(0.1 % of FS + 1 digit)  
Cold junction compensation error: ±0.5°C or ±0.9°F  
(at 20°C ±10°C or 68°F ±18°F)  
OUTPUT SPECIFICATIONS  
Quad Alarm  
Relay rating:  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: ≤ 1.5 sec. (0 – 100 % at 90 % setpoint)  
Burnout response: ≤ 5 sec.  
120 V AC @ 1 A (cos ø = 1)  
240 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 1 A (resistive load)  
Maximum switching voltage(Note): 380 V AC or 125 V DC  
Maximum switching power(Note): 120 VA or 30 W  
Minimum load: 5 V DC @ 10 mA  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
to power to ground)  
Mechanical life: 5 × 10  
7
cycles  
Dual Alarm  
STANDARDS & APPROVALS  
EU conformity:  
Relay rating:  
120 V AC @ 5 A (cos ø = 1)  
EMC Directive  
240 V AC @ 2.5 A (cos ø = 1)  
EMI EN 61000-6-4  
30 V DC @ 5 A (resistive load)  
EMS EN 61000-6-2  
Maximum switching voltage(Note): 380 V AC or 125 V DC  
Maximum switching power(Note): 600 VA or 150 W  
Minimum load: 5 V DC @ 10 mA  
Low Voltage Directive  
EN 61010-1  
Measurement Category II (output)  
AS4T SPECIFICATIONS  
ES-1608 Rev.16 Page 2/4  
https://www.m-system.co.jp/  
MODEL: AS4T  
Installation Category II (power)  
Pollution Degree 2  
Input to output to power: Basic insulation (300 V)  
RoHS Directive  
Approval:  
UL/C-UL general safety requirements  
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)  
EXTERNAL VIEW  
DATA  
DATA Display  
ITEM  
ITEM No. Display  
ALARM  
L4  
ITEM  
DATA  
L3  
L2  
L1  
*Monitor LEDs  
DATA UP-DOWN Keys  
ITEM No. UP-DOWN Keys  
*L3 or L4 does not turn on for dual output type.  
Refer to the instruction manual for detailed procedures.  
EXTERNAL DIMENSIONS unit: mm [inch]  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
8
9
7
6
5
4
2
4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
3
2
10 11  
1
11  
M3.5  
SCREW  
50 (1.97)  
103 (4.06)  
132 (5.20)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
TERMINAL ASSIGNMENTS unit: mm (inch)  
CJC SENSOR  
(model: CJM)  
8
7
6
5
4
9
3
2
10 11  
1
AS4T SPECIFICATIONS  
ES-1608 Rev.16 Page 3/4  
https://www.m-system.co.jp/  
MODEL: AS4T  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
OUTPUT CODE: 2  
OUTPUT CODE: 3  
• N.O. Relay Output  
• N.C. Relay Output  
L1 L2 L3 L4  
comp. leadwire  
T / C  
+
Low Drift  
Amplifier  
Ry  
Ry  
+
5
11 L4 OUTPUT  
10 L1 OUTPUT  
11 L4 OUTPUT  
10 L1 OUTPUT  
metal leg  
Digital  
Computation  
Circuit  
6
4
CJC  
SENSOR  
9
3
2
1
COM  
9
3
2
1
7
8
COM  
DATA  
ITEM  
Ry  
Ry  
L3 OUTPUT  
L2 OUTPUT  
COM  
L3 OUTPUT  
L2 OUTPUT  
COM  
model: CJM  
U(+)  
POWER  
V(–)  
Base Socket  
Relay Protection  
• AC Powered  
OUTPUT CODE: 5  
• SPDT Relay Output  
Inductive  
Load (Coil)  
Varistor or Spark  
Quenching Circuit  
L1  
L2  
LOAD  
comp. leadwire  
T / C  
11 N.C.  
10 N.O.  
+
Low Drift  
Amplifier  
Ry  
Ry  
+
5
U
L1 OUTPUT  
• DC Powered  
metal leg  
Inductive  
Load (Coil)  
9
3
2
1
7
8
COM  
N.C.  
N.O.  
COM  
U(+)  
V(–)  
Digital  
Computation  
Circuit  
Diode, Varistor or  
CR Circuit  
6
4
CJC  
SENSOR  
LOAD  
DATA  
ITEM  
L2 OUTPUT  
POWER  
model: CJM  
Base Socket  
Specifications are subject to change without notice.  
AS4T SPECIFICATIONS  
ES-1608 Rev.16 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

AS4T-2-R

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-2-R/Q

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-2-R/UL

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-3-M2

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-3-M2/Q

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-3-M2/UL

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-3-P

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-3-P/Q

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-3-P/UL

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-3-R

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-3-R/Q

Plug-in Signal Conditioners M-UNIT
MSYSTEM

AS4T-3-R/UL

Plug-in Signal Conditioners M-UNIT
MSYSTEM