AS4V-Z12-R/Q 概述
Plug-in Signal Conditioners M-UNIT
AS4V-Z12-R/Q 数据手册
通过下载AS4V-Z12-R/Q数据手册来全面了解它。这个PDF文档包含了所有必要的细节,如产品概述、功能特性、引脚定义、引脚排列图等信息。
PDF下载MODEL: AS4V
Plug-in Signal Conditioners M-UNIT
[2] OUTPUT
2: 4 points; N.O. or make contact
3: 4 points; N.C. or break contact
DC ALARM
(dual or quad alarm trip; field-configurable)
5: 2 points; SPDT or transfer contact
2A: 4 points; N.O. or make contact (small load current)
(CE not available. Option /UL Not selectable.)
3A: 4 points; N.C. or break contact (small load current)
(CE not available. Option /UL Not selectable.)
5A: 2 points; SPDT or transfer contact (small load current)
(CE not available. Option /UL Not selectable.)
Functions & Features
• Provides relay outputs at preset DC input levels
• Quad or dual trip
• Setting and display in engineering unit values
• Setpoint adjustments with the front keypad
• Software lock
• Adjustable hysteresis (deadband)
• On-delay timer
[3] POWER INPUT
• Hi/Lo trip and energized/de-energized coil independently
selectable for each setpoint
AC Power
M2: 100 – 240 V AC, 50 – 60 Hz
(Operational voltage range 85 – 264 V, 47 – 66 Hz)
DC Power
• Enclosed relays
• Relays can be powered by 200 V AC and 100 V DC
• High-density mounting on DIN rail
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
Typical Applications
• Annunciator
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
• Various alarm applications
[4] OPTIONS (multiple selections)
Standards & Approvals
50
(1.97)
blank: CE marking
/UL: UL approval, CE marking
Other Options
80
(3.15)
blank: none
/Q: Option other than the above (specify the specification)
132
(5.20)
mm (inch)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
MODEL: AS4V–[1][2]–[3][4]
/C02: Polyurethane coating
/C03: Rubber coating (UL not available)
TERMINAL SCREW MATERIAL
ORDERING INFORMATION
• Code number: AS4V-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. AS4V-S22-R/UL/Q)
/S01: Stainless steel (UL not available)
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-1609)
• Specify the specification for option code /Q
(e.g. /C01/SET)
GENERAL SPECIFICATIONS
Construction: Plug-in
[1] INPUT
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
Current
Z1: Range 0 – 50 mA DC (Input resistance 100 Ω)
Voltage
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Sampling cycle: 100 msec.
S1: Range -1 – +1 V DC (Input resistance 1 MΩ min.)
S2: Range -10 – +10 V DC (Input resistance 1 MΩ min.)
User-configurable items: Front key pad
• Alarm setpoint
AS4V SPECIFICATIONS
ES-1609 Rev.20 Page 1/5
https://www.m-system.co.jp/
MODEL: AS4V
• Display range scaling
120 V AC @ 5 A (cos ø = 1)
240 V AC @ 2.5 A (cos ø = 1)
30 V DC @ 5 A (resistive load)
• Power ON-delay time
• Alarm ON-delay time
• Moving average
Maximum switching voltage(Note): 380 V AC or 125 V DC
Maximum switching power(Note): 600 VA or 150 W
Minimum load: 5 V DC @ 10 mA
• Hi/Lo trip operation
• Coil at alarm
• Hysteresis (deadband)
Mechanical life: 5 × 10 cycles
7
• 0 %, 100 % input setting
• Latching control
■ Small load current type
Relay rating: 30 V DC @ 1 A (resistive load)
Maximum switching voltage(Note): 220 V DC
Maximum switching power(Note): 30 W (resistive load)
Minimum load: 1 V DC @ 1 mA
• Others
(Refer to the instruction manual)
■ DISPLAY
LED: 8 mm (.31”) 7 segment, red
Number of display digits: 4 digits for DATA display; 2 digits
for ITEM display
Mechanical life: 5 × 10 cycles
7
(Note): The value indicate capacity of output relay in
equipment.
Range: -1999 to 9999
(decimal point position selectable)
PV indication: Input signal in engineering unit
Overrange indication: LEDs blinking
Power saving mode: Displays turn off if the keys are
untouched for a preset time period
LEDs: Red LEDs turn on when coils are energized.
(L1 and L2 for 2-point alarm. L1, L2, L3 and L4 for 4-point
alarm.)
Use within relay rating for EU and UL.
Alarm Trip Operation
Terminal No. in parentheses
Example with quad N.O. contacts (LL, L, H, HH)
ON OFF
L1 (9–10)
ON OFF
L2 (1–2)
OFF ON
L3 (1–3)
OFF ON
L4 (9–11)
Input
(%)
INPUT SPECIFICATIONS
■ DC Current: 0 – 50 mA DC; shunt resistor attached to
input terminals (0.5 W)
0
▲
▲
50
▲
▲
100
LL
L
H
HH
Trip Operation in Power Failure
Operational range: 0 – 70 mA DC (with 100 Ω / 0.5 W)
Minimum increment: 0.1 mA
• Output code 2, 2A: All relays turn off.
• Output code 3, 3A: All relays turn on.
• Output code 5, 5A: Terminals 1 – 3, 9 – 11 turn on.
Default setting: 4 – 20 mA DC
■ DC Voltage: -1 – +1 V DC for S1;
-10 – +10 V DC for S2
INSTALLATION
Power consumption
•AC: ≤ 6 VA
Operational range: -1.15 – +1.15 V DC for S1;
-11.5 – +11.5 V DC for S2
Minimum increment: 10 mV for S1; 100 mV for S2
Default setting: -1 – +1 V DC for S1;
-10 – +10 V DC for S2
•DC: ≤ 3.5 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 500 g (1.1 lb)
OUTPUT SPECIFICATIONS
■ Quad Alarm
Relay rating:
PERFORMANCE in percentage of FS input
Setpoint accuracy (trip point accuracy): ±(0.1 % of FS + 1
digit)
120 V AC @ 1 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage(Note): 380 V AC or 125 V DC
Maximum switching power(Note): 120 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Display accuracy: ±(0.1 % of FS + 1 digit)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
Mechanical life: 5 × 10
7
cycles
■ Dual Alarm
Relay rating:
AS4V SPECIFICATIONS
ES-1609 Rev.20 Page 2/5
https://www.m-system.co.jp/
MODEL: AS4V
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (output)
Installation Category II (power)
Pollution Degree 2
Input to output to power: Basic insulation (300 V)
RoHS Directive
Approval:
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
EXTERNAL VIEW
DATA
DATA Display
ITEM
ITEM No. Display
ALARM
L4
ITEM
DATA
L3
L2
L1
*Monitor LEDs
DATA UP-DOWN Keys
ITEM No. UP-DOWN Keys
*L3 or L4 does not turn on for dual output type.
Refer to the instruction manual for detailed procedures.
EXTERNAL DIMENSIONS unit: mm [inch]
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
8
9
7
6
5
4
2
–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
3
2
10 11
1
11
–M3.5
SCREW
50 (1.97)
103 (4.06)
132 (5.20)
40 (1.57)
50 (1.97)
[3.3 (.13)]
• When mounting, no extra space is needed between units.
AS4V SPECIFICATIONS
ES-1609 Rev.20 Page 3/5
https://www.m-system.co.jp/
MODEL: AS4V
TERMINAL ASSIGNMENTS unit: mm (inch)
INPUT RESISTOR
(model: REM)
8
7
6
5
4
9
3
2
10 11
1
Input shunt resistor attached
for current input.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
n OUTPUT CODE: 2, 2A
• N.O. Relay Output
n OUTPUT CODE: 3, 3A
• N.C. Relay Output
L1 L2 L3 L4
Low Drift
Ry
Amplifier
+
–
5
6
4
*
11 L4 OUTPUT
10 L1 OUTPUT
11 L4 OUTPUT
10 L1 OUTPUT
INPUT
R
Ry
Digital
Computation
Circuit
DATA
ITEM
9
3
2
1
7
8
COM
9
3
2
1
COM
Ry
Ry
L3 OUTPUT
L2 OUTPUT
COM
L3 OUTPUT
L2 OUTPUT
COM
U(+)
POWER
V(–)
Base Socket
*Input shunt resistor attached for current input.
n OUTPUT CODE: 5, 5A
• SPDT Relay Output
■ Relay Protection
• AC Powered
L1
L2
Inductive
Load (Coil)
11 N.C.
10 N.O.
Low Drift
Amplifier
Varistor or Spark
Quenching Circuit
Ry
Ry
+
–
5
6
4
*
L1 OUTPUT
LOAD
INPUT
R
9
3
2
1
7
8
COM
N.C.
N.O.
COM
U(+)
V(–)
U
Digital
Computation
Circuit
• DC Powered
DATA
ITEM
Inductive
Load (Coil)
L2 OUTPUT
POWER
Diode, Varistor or
CR Circuit
LOAD
Base Socket
*Input shunt resistor attached for current input.
AS4V SPECIFICATIONS
ES-1609 Rev.20 Page 4/5
https://www.m-system.co.jp/
MODEL: AS4V
Specifications are subject to change without notice.
AS4V SPECIFICATIONS
ES-1609 Rev.20 Page 5/5
https://www.m-system.co.jp/
AS4V-Z12-R/Q 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
AS4V-Z12-R/UL | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
AS4V-Z12A-M2 | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
AS4V-Z12A-M2/Q | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
AS4V-Z12A-M2/UL | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
AS4V-Z12A-P | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
AS4V-Z12A-P/Q | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
AS4V-Z12A-P/UL | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
AS4V-Z12A-R | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
AS4V-Z12A-R/Q | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
AS4V-Z12A-R/UL | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 |
AS4V-Z12-R/Q 相关文章
- 2024-10-31
- 6
- 2024-10-31
- 6
- 2024-10-31
- 7
- 2024-10-31
- 8