ATC-N144-V/Q [MSYSTEM]

Limit Alarms (potentiometer adj.) A-UNIT;
ATC-N144-V/Q
型号: ATC-N144-V/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Limit Alarms (potentiometer adj.) A-UNIT

文件: 总4页 (文件大小:134K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: ATC  
0: Specify  
Limit Alarms (potentiometer adj.) A-UNIT  
SETPOINT ADJUSTMENTS  
1: Single-turn screws  
THERMOCOUPLE ALARM  
Functions & Features  
• Providing SPDT relay outputs at preset input levels  
• Direct input from a thermocouple  
• Dual (Hi/Lo) trip  
[2] SETPOINT 1 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
• Burnout protection  
• High-accuracy cold junction compensation  
• Energized or de-energized coil at a tripped condition  
selectable  
• Hysteresis (deadband) adjustable  
• Enclosed relays  
[3] SETPOINT 2 OUTPUT  
1: Hi (coil energized at alarm)  
2: Hi (coil de-energized at alarm)  
3: Lo (coil energized at alarm)  
4: Lo (coil de-energized at alarm)  
• Relays can be powered 110 V DC  
• High-density mounting  
Typical Applications  
• Annunciator  
• Various alarm applications  
[4] POWER INPUT  
AC Power  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
50  
(1.97)  
80  
(3.15)  
132  
(5.20)  
DC Power  
S: 12 V DC  
mm (inch)  
R: 24 V DC  
V: 48 V DC  
MODEL: ATC-[1]1[2][3]-[4][5]  
P: 110 V DC  
ORDERING INFORMATION  
• Code number: ATC-[1]1[2][3]-[4][5]  
Specify a code from below for each of [1] through [5].  
(e.g. ATC-2111-B/BL/Q)  
[5] OPTIONS (multiple selections)  
Burnout  
blank: Upscale burnout  
/BL: Downscale burnout  
/BN: No burnout  
• Temperature range (e.g. 0 – 800°C)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
[1] INPUT THERMOCOUPLE  
1: (PR) (Usable Range 0 to 1760°C, 32 to 3200°F)  
2: K (CA) (Usable range -270 to +1370°C, -454 to +2498°F)  
3: E (CRC) (Usable range -270 to +1000°C, -454 to +1832°F)  
4: J (IC) (Usable range -210 to +1200°C, -346 to +2192°F)  
5: T (CC) (Usable range -270 to +400°C, -454 to +752°F)  
6: B (RH) (Usable range 0 to 1820°C, 32 to 3308°F)  
7: R (Usable range -50 to +1760°C, -58 to +3200°F)  
8: S (Usable range -50 to +1760°C, -58 to +3200°F)  
N: N (Usable range -270 to +1300°C, -454 to +2372°F)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
ATC SPECIFICATIONS  
ES-2111 Rev.7 Page 1/4  
http://www.m-system.co.jp/  
MODEL: ATC  
240 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 1 A (resistive load)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Maximum switching voltage: 380 V AC or 125 V DC  
Maximum switching power: 120 VA or 30 W  
Minimum load: 5 V DC @ 10 mA  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
Mechanical life: 5 x 10 cycles  
7
Housing material: Flame-resistant resin (black)  
Isolation: Input to output 1 to output 2 to power  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
Setpoint adjustments: 270°-turn screwdriver adjustments  
(front); 0 – 100 % independently  
For maximum relay life with inductive loads, external  
protection is recommended.  
Alarm Trip Operation Terminal No. in parentheses  
(9-11)ON  
Output 1  
(9-10)ON  
Hysteresis (deadband) adjustments: 1 – 100 % (front)  
Linearization: Not provided  
(1-3)ON  
Output 2  
(1-2)ON  
Cold junction compensation: CJC sensor attached to the  
input terminals  
Input  
(%)  
Front LEDs: LED turns on at a tripped condition; red for  
output 1, green for output 2  
0
50  
100  
Output 2  
Setpoint  
Output 1  
Setpoint  
Power ON timer: Relays de-energized for approx. 2 seconds  
after power is turned on.  
Trip Operation in Power Failure  
Output Code: 1 & 4: Terminals 1 – 2, 9 – 10 turn ON  
Output Code: 2 & 3: Terminals 1 – 3, 9 – 11 turn ON  
INPUT SPECIFICATIONS  
Minimum span: 3 mV  
Offset: Max. 1.5 times span  
Input resistance: 30 kΩ min.  
Burnout sensing: 0.1 μA  
INSTALLATION  
Power input  
AC: Operational voltage range: rating ±10 %,  
50/60 ±2 Hz, approx. 2 VA  
Minimum span (in °C)  
(PR): min. span 370°C  
K (CA): min. span 75°C  
E (CRC): min. span 50°C  
J (IC): min. span 60°C  
T (CC): min. span 75°C  
B (RH): min. span 780°C  
R: min. span 360°C  
DC: Operational voltage range: rating ±10 %, or 85 – 150  
V for 110 V rating (ripple 10 % p-p max.)  
approx. 2 W (80 mA at 24 V)  
Operating temperature: -5 to +60°C (23 to 140°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 450 g (0.99 lb)  
S: min. span 380°C  
PERFORMANCE in percentage of span  
Trip point repeatability: ±0.5 %  
N: min. span 110°C  
Cold junction compensation error  
Minimum span (in °F)  
(PR): min. span 670°F  
K (CA): min. span 140°F  
E (CRC): min. span 90°F  
J (IC): min. span 110°F  
T (CC): min. span 140°F  
B (RH): min. span 1410°F  
R: min. span 650°F  
(at 20°C ±10°C or 68°F ±18°F)  
K, E, J, T & N: ±0.5°C or ±0.9°F  
S, R & PR: ±1°C or ±1.8°F  
Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)  
Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint)  
Burnout response: ≤ 10 sec.  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output 1  
to output 2 to power to ground)  
S: min. span 690°F  
N: min. span 200°F  
OUTPUT SPECIFICATIONS  
Relay Contact: 100 V AC @ 1 A (cos ø = 1)  
120 V AC @ 1 A (cos ø = 1)  
ATC SPECIFICATIONS  
ES-2111 Rev.7 Page 2/4  
http://www.m-system.co.jp/  
MODEL: ATC  
EXTERNAL VIEW  
No.1 Setpoint Adj.  
No.1 LED  
Span Adj.  
Zero Adj.  
No.1 Deadband (Hysteresis) Adj.  
No.2 Deadband (Hysteresis) Adj.  
No.2 LED  
No.2 Setpoint Adj.  
EXTERNAL DIMENSIONS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
8
7
6
5
4
2
4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
9
3
2
10 11  
1
11  
M3.5  
SCREW  
50 (1.97)  
103 (4.06)  
132 (5.20)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
TERMINAL ASSIGNMENTS unit: mm (inch)  
CJC SENSOR  
(model: CJM)  
8
7
6
5
4
9
3
2
10 11  
1
ATC SPECIFICATIONS  
ES-2111 Rev.7 Page 3/4  
http://www.m-system.co.jp/  
MODEL: ATC  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Relay Protection  
• AC Powered  
HYSTERESIS  
SETPOINT (DEADBAND)  
Inductive  
Load (Coil)  
*
comp. leadwire  
T / C  
Z
S
11  
10  
9
H
Varistor or Spark  
Quenching Circuit  
+
Low Drift  
Amplifier  
LOAD  
+
5
Comparator  
Ry  
SETPOINT 1  
OUTPUT  
L
U
metal leg  
• DC Powered  
C
Inductive  
Load (Coil)  
*
6
4
CJC  
SENSOR  
3
**  
H
Diode, Varistor or  
CR Circuit  
CJC Sensing  
Volt. Generator  
Comparator  
Ry  
SETPOINT 2  
OUTPUT  
LOAD  
2
L
model: CJM  
1
C
HYSTERESIS  
(DEADBAND)  
SETPOINT  
7
U(+)  
V(–)  
POWER  
8
Base Socket  
* Relay status for output codes “1” & “4”, at power OFF.  
**Deleted with B thermocouple  
Specifications are subject to change without notice.  
ATC SPECIFICATIONS  
ES-2111 Rev.7 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

ATC10-3PN

Circular Connector,
AMPHENOL

ATC100A

Ultra-Stable Performance
ETC

ATC100A0R2BT

280W GaN WIDEBAND PULSED POWER
RFMD

ATC100A0R5BT500XT

RF LDMOS Wideband Integrated Power Amplifier
NXP

ATC100A0R7BT

280W GaN WIDEBAND PULSED POWER
RFMD

ATC100A100JP150XT

Gallium Arsenide pHEMT RF Power Field Effect Transistor
NXP

ATC100A100JW150XI

Ultra-Stable Performance
ETC

ATC100A100JW150XT

Ultra-Stable Performance
ETC

ATC100A100JW150XTV

Ultra-Stable Performance
ETC

ATC100A101JP150XT

Gallium Arsenide pHEMT RF Power Field Effect Transistor
NXP

ATC100A120JT

280W GaN WIDEBAND PULSED POWER
RFMD

ATC100A150JT

380W GaN WIDEBAND PULSED
RFMD