B3HU-1 [MSYSTEM]
Space-saving Two-wire Signal Conditioners B3-UNIT;型号: | B3HU-1 |
厂家: | M-SYSTEM |
描述: | Space-saving Two-wire Signal Conditioners B3-UNIT |
文件: | 总5页 (文件大小:141K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: B3HU
Space-saving Two-wire Signal
Conditioners B3-UNIT
RELATED PRODUCTS
• USB interface Bell202 modem (model: COP-HU)
Usable in ‘non-hazardous’ area only.
• Hand-held communicator
2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER
(HART communication, intrinsically safe)
Functions & Features
(Consult HART Communication Foundation (HCF) web
site: www.hartcomm.org. )
• AMS (version 6.0 or higher)
• Universal input: mV, V, T/C, RTD, resistance,
potentiometer and DC voltage
• Simatic PDM (version 6.0 or higher)
• PC configurator software (model: B3HUCFG)
Downloadable at M-System’s web site.
• High accuracy
• HART communication
• Intrinsically safe approval
GENERAL SPECIFICATIONS
Construction: Small-sized front terminal structure
• Programming via hand-held communicator or via PC
• A wide variety of T/C and RTD types
• User’s temperature table can be used
• Self diagnostics
Connection: Euro type connector terminal
(Applicable wire size: 0.2 - 2.5 mm
2
(pin terminals: 0.2 - 1.5
mm ), stripped length 8 mm)
2
• Input-output isolated
Housing material: Flame-resistant resin (gray)
Isolation: Input to output
18 (.71)
Burnout (except DC voltage input): Upscale, downscale or
no burnout selectable (standard: upscale);
Also detects wire breakdown and overrange input
exceeding the electrical design limit for DC voltage input.
Cold junction compensation (T/C): CJC sensor (included) to
be attached to the input terminals
User-configurable items:
106
(4.17)
• Input sensor type
110.5
(4.35)
• Number of wires (RTD & resistance)
• Input range
mm (inch)
• Inverted output
• Burnout
• Damping time (via HART only, standard: 0)
• Sensor calibration (via HART only)
• Output calibration
MODEL: B3HU–[1]/A
ORDERING INFORMATION
• Code number: B3HU-[1]/A
• Special linearization data (via HART only)
• HART communication mode
Specify a code from below for [1].
(e.g. B3HU-0/A)
HART COMMUNICATION
• Use Ordering Information Sheet (No. ESU-7502). Factory
standard setting will be used if not otherwise specified.
• Specify the country in which the product is to be used with
the Safety Approval code 2.
Protocol: HART communication protocol
HART address range: 0 – 15 (factory set to 0)
Transmission speed: 1200 bps
Digital current: Approx. 1 mAp-p when communicating
Character format: 1 Start Bit, 8 Data Bits, 1 Odd Parity Bit,
1 Stop Bit
[1] SAFETY APPROVAL
0: None
Distance: 1.5 km (0.9 miles)
1: FM intrinsically safe
2: ATEX intrinsic safety
HART communication mode: Master-Slave Mode and Burst
Mode (factory set to Master-Slave)
HART network mode: Point-to-Point Mode and Multi-drop
Mode; automatically set to Multi-drop Mode when the
address is set to other than 0.
OPTIONS
CJC Sensor
/A: External Sensor (must be specified)
B3HU SPECIFICATIONS
ES-7502 Rev.14 Page 1/5
http://www.m-system.co.jp/
MODEL: B3HU
INPUT SPECIFICATIONS
The input type is factory-set to K thermocouple, and the
input range to 0 to 100°C.
EXPLANATIONS OF TERMS
■ ACCURACY
This transmitter’s accuracy is theoretically defined as the
addition of A/D and D/A conversion errors:
See Table 1 for the available input type, the minimum span,
and the maximum range.
■ DC mV & V
Accuracy = A/D Conversion Error + D/A Conversion Error
Input resistance: ≥ 1 MΩ
■ Thermocouple
The A/D conversion error means that measured as HART
signal which is A/D converted from the analog input signal.
The D/A conversion error of this transmitter is relatively
very small so that it does not really affect the unit’s overall
performance.
Input resistance: ≥ 1 MΩ
Burnout sensing: 130 nA ±10 %
■ RTD (2-wire, 3-wire or 4-wire)
Excitation: 0.2 mA ± 10 %
Allowable leadwire resistance: Max. 20 Ω per wire
■ Resistance (2-wire, 3-wire or 4-wire)
Excitation: 0.2 mA ±10 %
The “Accuracies” given in Table 1 therefore equals the A/D
conversion error.
The temperature drift (coefficient) or the cold junction
compensation error is not included in the “Accuracy.”
Allowable leadwire resistance: Max. 20 Ω per wire
■ Potentiometer
Excitation: 0.2 mA ±10%
■ CALCULATION EXAMPLES OF OVERALL ACCURACY IN %
• DC Voltage
Allowable leadwire resistance: Max. 20 Ω per wire
1) 0 – 200 mV
Absolute value accuracy (Table 1): 40 μV
40 μV ÷ 200000 μV × 100 = 0.02 % < 0.1 %
➠ Overall accuracy = ±0.1% of span
2) 0 – 4 mV
OUTPUT SPECIFICATIONS
Output range: 4 – 20 mA DC
Operational range: 3.8 – 21.6 mA
Load resistance vs. supply voltage:
Load Resistance (Ω) = (Supply Voltage (V) – 12 (V))
Absolute value accuracy (Table 1): 10 μV
10 μV ÷ 4000 μV × 100 = 0.25 % > 0.1%
➠ Overall accuracy = ±0.25 % of span
• Thermocouple
÷ 0.024 (A)
(including leadwire resistance)
INSTALLATION
1) K thermocouple, 0 – 1000°C
Supply voltage
Absolute value accuracy (Table 1): 0.25°C
0.1% × 1000°C = 1°C > 0.25°C
• 12 – 42 V DC (non-approved)
• 12 – 28 V DC (approved)
CJC error (0.5°C) added: 1 + 0.5 = 1.5°C
1.5°C ÷ 1000°C × 100 = 0.15 %
Operating temperature: -40 to +85°C (-40 to +185°F)
(See Safety Parameters for use in a hazardous location.)
Operating humidity: 0 to 95 %RH (non-condensing)
Mounting: DIN rail
➠ Overall accuracy including CJC error = ±0.15 % of span
2) K thermocouple, 50 – 150°C
Absolute value accuracy (Table 1): 0.25°C
0.1 % × (150 – 50)°C = 0.1°C < 0.25°C
CJC error (0.5°C) added: 0.25 + 0.5 = 0.75°C
0.75°C ÷ (150 – 50)°C × 100 = 0.75 %
➠ Overall accuracy including CJC error = ±0.75 % of span
• RTD
Weight: 80 g (2.8 oz)
PERFORMANCE
Accuracy: See Table 1 and ‘Explanations of Terms.’
Cold junction compensation error: ±0.5℃ (±0.9°F)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span
at -5 to +55°C [23 to 131°F]
1) Pt 100, -200 – 800°C
Absolute value accuracy (Table 1): 0.15°C
0.15°C ÷ (800 – -200)°C × 100 = 0.015 % < 0.1 %
➠ Overall accuracy = ±0.1 % of span
2) Pt 100, 0 – 100°C
Start-up time: Approx. 8 sec.
Response time: ≤ 2 sec. (0 – 90 %) with damping time
set to 0 and when not communicating via HART.
Supply voltage effect: ±0.003 % × [Output Span] / 1 V
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @1 minute
(input to output to ground)
Absolute value accuracy (Table 1): 0.15°C
0.15°C ÷ 100°C × 100 = 0.15 % > 0.1 %
➠ Overall accuracy = ±0.15 % of span
B3HU SPECIFICATIONS
ES-7502 Rev.14 Page 2/5
http://www.m-system.co.jp/
MODEL: B3HU
STANDARDS & APPROVALS
EU conformity:
ATEX Directive
Ex ia EN 60079-11
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
Safety approval:
FM: Intrinsically safe
Class I, Div. 1, Groups A, B, C and D
Class I, Zone 0, AEx ia IIC
T4 and T5
(Class 3610)
ATEX: Intrinsic safety
II 1G, Ex ia IIC; T4 and T5
(EN 60079-0)
(EN 60079-11)
SAFETY PARAMETERS
Operating temperature
For ATEX / FM:
T4: -40 to +80°C
T5: -40 to +55°C
Ex-data:
• Output circuit
Ui (Vmax): 30 V DC
Ii (Imax): 96 mA DC
Pi (Pmax): 0.72 W
Ci: 1 nF
Li: 0 mH
• Sensor circuit
Uo (Voc): 6.4 V DC
Io (Isc): 30 mA DC
Po: 48 mW
Co (Ca): 20 μF
Lo (La): 10 mH
B3HU SPECIFICATIONS
ES-7502 Rev.14 Page 3/5
http://www.m-system.co.jp/
MODEL: B3HU
INPUT TYPE, RANGE & ACCURACY
■ INPUT TYPE, RANGE & ACCURACY
MIN.
SPAN
INPUT TYPE
DC mV & V
MAXIMUM RANGE
ACCURACY
4 mV
-50 to +1000 mV
±0.1 % or ±±0μV, whichever is greater (F.S. input ≤ 50 mV)
±0.1 % or ±ꢀ0μV, whichever is greater (F.S. input ≤ 200 mV)
±0.1 % or ±ꢁ0μV, whichever is greater (F.S. input ≤ 500 mV)
±0.1 % or ±ꢂ0μV, whichever is greater (F.S. input > 500 mV)
Potentiometer
Resistance
2 % Total resicetance 150 to 4000Ω ±0.1 %
10Ω
0 to 4000Ω
±0.1 % or ±0.1Ω, whichever is greater.*2
°C
°F
THERMOCOUPLE
MIN.
SPAN
MAXIMUM CONFORMANCE ACCURACY MIN.
1
MAXIMUM CONFORMANCE ACCURACY
1
RANGE
RANG
*
SPAN
RANGE
RANG
*
(PR)
K (CA)
E (CRC)
20
0 to 1760
0 to 1760
-150 to +1370
-170 to +1000
1.00
0.25
0.20
36
32 to 3200
32 to 3200
-238 to +2498
-274 to +1832
1.80
0.45
0.36
20 -270 to +1370
20 -270 to +1000
36 -454 to +2498
36 -454 to +1832
J (IC)
T (CC)
B (RH)
20 -210 to +1200
-180 to +1200
-170 to +400
400 to 1760
0.25
0.25
0.75
36 +346 to +2192 -292 to +2192
0.45
0.45
1.35
20
20
-270 to +400
100 to 1820
36
36
-454 to +752
212 to 3308
-274 to +752
752 to 3200
R
20
20
20
-50 to +1760
-50 to +1760
0 to 2315
200 to 1760
0 to 1760
0 to 2315
0.50
0.50
0.25
36
36
36
-58 to +3200
-58 to +3200
32 to 4199
392 to 3200
32 to 3200
32 to 4199
0.90
0.90
0.45
S
C (WRe 5-26)
N
20 -270 to +1300
-130 to +1300
-200 to +600
-200 to +900
0 to 1395
0.30
0.20
0.25
0.25
36 -454 to +2372
36 -328 to +1112
36 -328 to +1652
-202 to +2372
-328 to +1112
-328 to +1652
32 to 2543
0.54
0.36
0.45
0.45
U
20
20
20
-200 to +600
-200 to +900
0 to 1395
L
P (Platinel II)
36
32 to 2543
°C
°F
RTD
MIN.
SPAN
ACCURACY MIN.
2
ACCURACY
2
MAXIMUM RANGE
MAXIMUM RANGE
*
SPAN
*
Pt 100 (JIS ’97, IEC)
Pt 200
Pt 300
20
20
20
-200 to +850
-200 to +850
-200 to +850
0.15
0.15
0.15
36
36
36
-328 to +1562
-328 to +1562
-328 to +1562
0.27
0.27
0.27
Pt 400
Pt 500
Pt 1000
20
20
20
-200 to +850
-200 to +850
-200 to +850
0.15
0.15
0.15
36
36
36
-328 to +1562
-328 to +1562
-328 to +1562
0.27
0.27
0.27
Pt 50 Ω (JIS ’81)
JPt 100 (JIS ’89)
Ni 100
20
20
20
-200 to +649
-200 to +510
-80 to +260
0.15
0.15
0.15
36
36
36
-328 to +1200
-328 to +950
-112 to +500
0.27
0.27
0.27
Ni 120
20
20
20
20
-80 to +260
-50 to +200
-200 to +200
-50 to +250
0.15
0.15
0.15
0.50
36
36
36
36
-112 to +500
-58 to +392
-328 to +392
-58 to +482
0.27
0.27
0.27
0.90
Ni 508.4 Ω
Ni-Fe 604
CU10 @ 25°C
*1. [Accuracy or 0.1% oꢀ sꢁan, whichever is greater] + Cold Junction Comꢁensation Error.
*2. Or 0.1% oꢀ sꢁan, whichever is greater.
(For 2- or 3-wire resistance or RTD, the value is valid by the sensor calibration aꢀter the wiring is done.)
B3HU SPECIFICATIONS
ES-7502 Rev.14 Page 4/5
http://www.m-system.co.jp/
MODEL: B3HU
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
10 11 12
7
8
9
DIN RAIL
35mm wide
1
4
2
5
3
6
CJC SENSOR
(model: CJM)
*
110.5 (4.35)
[5 (.20)]
18 (.71)
*Used only with a thermocouple input
• When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Hazardous Area
Safe Area
HART
Comm.
RTD & Resistance
DC mV
POT
2-wire
A
3-wire
4-wire
T/C
Isolation
24V DC
+
Input
Computation
Output
Computation
Output
Driver
+
–
3
2
A
A
A
B
B
1
2
4
3
5
6
7
8
2
*
Low Drift
Amplifier
1
1
*
OUTPUT LOAD
4 – 20mA DC
*
+
+
–
+
–
9
B
B
3
*
Safety Barrier
1
B
10
11
12
–
–
4
*
CJC
*1. Close across the terminals 1 & 2 for a resistance or RTD input.
*2. Limited to 250 – 1100Ω for HART communication.
*3. A safety barrier must be installed for the intrinsic safety.
The safety barrier must meet the Ex-data of this unit and must be approved for the hazardous location.
*4. Replace the Terminal Block (4 – 5 – 6) with the one connected with the CJC Sensor, included in the package.
Specifications are subject to change without notice.
B3HU SPECIFICATIONS
ES-7502 Rev.14 Page 5/5
http://www.m-system.co.jp/