CLSE-20 [MSYSTEM]
CLAMP-ON CURRENT SENSOR;型号: | CLSE-20 |
厂家: | M-SYSTEM |
描述: | CLAMP-ON CURRENT SENSOR |
文件: | 总2页 (文件大小:116K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: CLSE
CLAMP-ON CURRENT SENSOR
Functions & Features
INPUT SPECIFICATIONS
Maximum working voltage: 480 V AC (primary side)
Operational range & overload capacity
• Easy-to-install, spring-loaded, clamp-on type current
sensor
OPERATIONAL RANGE OVERLOAD CAPACITY *
CLSE-R5
CLSE-05
CLSE-10
CLSE-20
CLSE-40
CLSE-60
5 A maximum
50 A maximum
100 A maximum
200 A maximum
400 A maximum
600 A maximum
10 A continuous
60 A continuous
120 A continuous
240 A continuous
480 A continuous
720 A continuous
• Over-voltage clamp element for safety in open circuit
• Wide frequency band
• Screw terminal connection
*4000% of rating for 1 second
Caution 1: The output values may vary depending on the
accuracy of engagement at the clamp connection.
Caution 2: The sensor's mechanical construction may cause
it to generate resonance sound. However, it does not affect
the performance of the sensor.
MODEL: CLSE–[1][2]
INSTALLATION
ORDERING INFORMATION
• Code number: CLSE-[1][2]
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Weight:
Specify a code from below for each of [1] and [2].
(e.g. CLSE-R5/CE)
CLSE-R5: 45 g (1.6 oz)
Confirm the correct sensor type described on the data sheet
of the combined transducer/transmitter module.
CLSE-05: 40 g (1.4 oz)
CLSE-10: 75 g (2.6 oz)
CLSE-20: 180 g (6.3 oz)
CLSE-40: 300 g (10.5 oz)
[1] POWER INPUT
R5: 5 A
CLSE-60: 330 g (11.6 oz)
05: 50 A
10: 100 A
PERFORMANCE in percentage of span
Frequency: 45 – 65 Hz (including the harmonic current up to
20 kHz)
20: 200 A
40: 400 A
60: 600 A
For 65.1 Hz – 1.2 kHz, ratio error is ±2 %/In.
Maximum load: 10 Ω
Insulation resistance: ≥ 100 MΩ with 500 V DC
(sensor core to output terminal)
[2] OPTIONS
Standards & Approvals
blank: Without CE
/CE: CE marking
Dielectric strength: 2000 V AC @ 1 minute
(sensor core to output terminal)
MODEL PRIMARY SECONDARY
RATIO
PHASE DISPLACEMENT
ERROR
RATING
5 A
RATING
1.65 mA
20 mA
20 mA
20 mA
20 mA
20 mA
ERROR
RELATED PRODUCTS
CLSE-R5
CLSE-05
CLSE-10
CLSE-20
CLSE-40
CLSE-60
1%/In, 2%/0.2 In
1%/In, 2%/0.2 In
1%/In, 2%/0.2 In
1%/In, 2%/0.2 In
1%/In, 2%/0.2 In
1%/In, 2%/0.2 In
1.5 1°
50 A
1 1°
• Special cable (model: CLS-CN)
(Used in combination with the CLSA-08C.)
• Special cable (model: CLSA-08C)
100 A
200 A
400 A
600 A
0.5 1°
1°
1°
1°
GENERAL SPECIFICATIONS
Construction: Clamp
STANDARDS & APPROVALS
EU conformity:
Connection: M3 screw terminals (torque 0.3 N·m)
Housing material: Flame-resistant resin (black)
EMC Directive
Applicable wire size: AWG22 or thicker (0.6 dia. or 0.3 mm
2
EN 61326-1
or thicker; Max. 30 meters, twisted)
Low Voltage Directive
EN 61010-1
Detachable number of times: Approx. 100 times
CLSE SPECIFICATIONS
ES-9234 Rev.7 Page 1/2
https://www.m-system.co.jp/
MODEL: CLSE
EN 61010-2-032
Measurement Category III (input)
Pollution Degree 2
RoHS Directive
EXTERNAL DIMENSIONS unit: mm (inch)
■ Sensor model No.: CLSE-R5, CLSE-05
2–M3 SCREW
50 (1.97)
37 (1.46)
4
(.16)
26 (1.02)
4
(.16)
10 dia.
(.39)
L
K
TERMINAL COVER
(detachable)
■ Sensor model No.: CLSE-10
55 (2.17)
4
(.16)
31 (1.22)
4
(.16)
2–M3 SCREW
40.5 (1.59)
16 dia.
(.63)
L
K
TERMINAL COVER
(detachable)
■ Sensor model No.: CLSE-20
74.5 (2.93)
49.5 (1.95)
4
(.16)
34 (1.34)
4
(.16)
2–M3 SCREW
24 dia.
(.94)
TERMINAL COVER
(detachable)
L
K
■ Sensor model No.: CLSE-40, CLSE-60
91 (3.58)
61 (2.40)
4
(.16)
40.5 (1.59)
4
(.16)
2–M3 SCREW
36 dia.
(1.42)
TERMINAL COVER
(detachable)
L
K
Specifications are subject to change without notice.
CLSE SPECIFICATIONS
ES-9234 Rev.7 Page 2/2
https://www.m-system.co.jp/
相关型号: