DLC-7C4-S [MSYSTEM]
REMOTE I/O INTERFACE UNIT;型号: | DLC-7C4-S |
厂家: | M-SYSTEM |
描述: | REMOTE I/O INTERFACE UNIT |
文件: | 总9页 (文件大小:287K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: DLC
R1xx: Ai 16 + Ao 16 points
Remote I/O
S1xx: Ai 8 + Ao 8 + Di 8 + Do 8 points
U1x : Po 16 + Ao 16 points
REMOTE I/O INTERFACE UNIT
Functions & Features
See data sheet for Standard Multi-Transmission Unit (model:
DLA1) for specifications of I/O sections.
• Interfacing between the host computer and remote I/O
devices
[3] POWER INPUT
• RS-232-C (non-procedure)
AC Power
• Buffer memory common for DLC commands enables quick
I/O without waiting time
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
L: 170 – 264 V AC
• Process I/O
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
53 (2.09)
S: 12 V DC
(Operational voltage range 12 V ±10 %, ripple 10 %p-p max.)
R: 24 V DC
POW
RUN
SA1
SA2
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
300
(11.81)
FIB
ER
LIN
K
RELATED PRODUCTS
RT
RU
• Standard multi-transmission unit (model: DLA1)
200
(2.87)
mm (inch)
GENERAL SPECIFICATIONS
Construction: Surface mounting; terminal access on the
MODEL: DLC–[1][2]–[3]
front
Connection
Transmission line terminal: Euro type connector terminal;
ORDERING INFORMATION
• Code number: DLC-[1][2]-[3]
wire size 1.25 mm
Power supply terminal: Euro type connector terminal; wire
size 1.25 mm max.
RUN contact: Euro type connector terminal; wire size 1.25
mm max.
2
max.
Specify a code from below for each [1] through [3].
(e.g. DLC-1S1A4B4-K)
2
2
[1] TRANSMISSION MEDIA
1: Twisted-pair cable
I/O section:
•32-point I/O (or less): 40-pin connector terminal; M3 × 6
screws (torque 0.7 N·m)
2: Fiber optics cable
7: Twisted-pair – fiber optics (repeater incorporated)
•64-point I/O: FCN 40-pin connector (two);
(FUJITSU FCN-365P040-AU)
[2] I/O SECTION
Housing material: Flame-resistant resin (beige)
Isolation: I/O to transmission section to power
Station No. adjustment: 2 rotary switches; 00 – FF (256)
■ Controller & Transmission Sections
[Computer Interface without Process I/O]
00: RS-232-C (non-procedure)
[RS-232-C with Process I/O]
A1: Di 32 points
Power indicator: Red LED turns ON in normal conditions;
OFF when the voltage level becomes low.
RUN indicator: Red LED turns OFF in error.
■ I/O Section
A2: Di 64 points
C1: Do 32 points (relay)
C2: Do 32 points (open collector)
C3: Do 64 points (relay)
Contact I/O indicator LED: Red lights turn on when the
respective I/O channels are ON.
C4: Do 64 points (open collector)
E1: Di 16 + Do 16 points (relay)
E2 : Di 16 + Do 16 points (open collector)
G1x: Ai 32 points
Analog I/O CPU RUN indicator LED: Red LED turns ON when
the CPU function proves normal, OFF in error.
■ RUN Output: Contact opens in error.
Rated load: 100 V AC or 30 V DC @ 1 A (resistive load)
Maximum switching voltage: 120 V AC or 30 V DC
M1x: Ao 32 points
P1x : Pi 16 + Ai 16 points
http://www.m-system.co.jp/
DLC SPECIFICATIONS
ES-6512 Rev.11 Page 1/9
MODEL: DLC
Maximum switching power: 100 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Error detection
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface; Rack Mounting Frame (model: BX-1DL)
available
•Communication: The receiver units detect loss of
communication and wire break.
•CPU: Watch-dog timer
Weight: 2 kg (4.4 lb)
•Power voltage: Detects when the voltage supply to the
CPU drops by 10 %.
PERFORMANCE
Permissible power failure duration: ≤ 20 ms
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(I/O to transmission to power)
MULTIPLEX COMMUNICATION
Communication: Half-duplex, synchronous
Transmission: Conform to RS-422, EIA
Transmission speed: 125 kbps
Protocol: SIN-NET (M-System's; data format conforms to
SDLC)
Error check: CRC
■ Twisted-pair Cable
Cable: CPEV-0.9 dia.
Connection: Euro Type connector terminal; wire size 1.25
mm max.
2
Transmission Distance: 1 kilometer max. with 16 units
connected; 3 kilometers max. between 2 stations each of
which consists of 3 units
Terminator: Incorporated (Remove the attached jumper pin
when the unit is not located at the end of transmission line.)
■ Fiber Optics Cable
Link: JIS F07 connector (Consult factory for details)
Transmission distance: 1 kilometer max. with PCF
Transmission loss: 7 dB max.
■ Twisted-pair – Fiber Optics: Converting signals between
two media and waveform shaping
INTERFACE
Transmission: Conform to EIA RS-232-C
Communication: Asynchronous, half-duplex, non-procedure
DIP switch: Setting RS-232-C specifications
Transmission speed: 300 – 9600 bps
Data bit: 7 or 8 bits
Stop bit: 1, 1.5 or 2 bits
Parity: Even or odd
RS-232-C connector: 25-pin D-sub connector (female) (M2.6
× 0.45 screw connector)
RS-232-C cable: Cross (provided by the user)
INSTALLATION
Power consumption
•AC: Approx. 17.5 VA max.
•DC: Approx. 17 W max. (1.1 A with 24 V)
Grounding: Not required in normal environments; 100 Ω or
less grounding resistance in noisy environments
Operating temperature: -5 to + 50°C (23 to 122°F)
http://www.m-system.co.jp/
DLC SPECIFICATIONS
ES-6512 Rev.11 Page 2/9
MODEL: DLC
DESCRIPTIONS
•RUN Contact (LED) Behaviors
Input units (00, A1, A2, G1 and P1): The LED turns ON with the network configured; OFF in an abnormality; the network is
reconfigured after an abnormality.
Output units (C1, C2, C3, C4, M1 and U1): The LED turns ON when data from the paired input unit is received normally, with the
network configured; OFF when the data is lost; turns also OFF in an abnormality in the network.
I/O-mixed units (E1, E2, R1 and S1): Functions of both input and output units are used.
[CAUTION]
When the network is reconfigured e.g. by noise interference, the RUN LED and output for all units on the network turn briefly
OFF until they are turned ON after the reconfiguration is complete.
EXTERNAL VIEW
Power LED Indicator
■ DIP SWITCH
ON
OFF
RUN LED Indicator
1
Transmission
Speed
Station Address Setting
Rotary Switches
2
3
4
5
6
7
8
SA1
SA2
Data Bit
Stop Bit
DIP Switches
Parity
With/Without
Parity Check
RS-232-C Connector
• RS-232-C Connection Example
(cross type cable)
■D-SUB CONNECTOR
PIN ASSIGNMENT
Connector
Unit Side
Connector
Computer Side
13
25
FG
1
2
3
4
5
6
7
8
20
1
2
3
4
5
6
7
8
20
FG
SD
RD
RS
CS
DR
SG
CD
ER
SD
RD
RS
CS
DR
SG
CD
ER
14
1
■ MULTI-TRANSMISSION SECTION, PROCESS I/O SECTION & INDICATOR LED SECTION
(Process I/O and indicator LED sections are provided only for process I/O type)
Power LED Indicator
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
RUN LED Indicator
Station No. Setting
Rotary Switches
SA1
SA2
■
STANDARD TYPE
(40-terminal connector)
■
DLC-A2, C3, C4
(FCN 40-pin connectors)
I/O Indicator LEDs
(Varies according to I/O types.
See each I/O section of
model DLA1 data sheet.)
1
3
5
7
LED Indicator
Selector
U
L
2
4
6
8
9
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
■ TWISTED-PAIR
■ FIBER OPTICS
■
TWISTED-PAIR & FIBER
CN1
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
Fiber Link
Connector
Fiber Link
Connector
Fiber Link
Connector
9
8
7
6
5
4
9
8
Jumper
Jumper
CN2
7
6
5
5
4
4
Euro
Connector
Terminal
Euro
Connector
Terminal
Euro
Connector
Terminal
3
2
1
3
2
1
3
2
1
http://www.m-system.co.jp/
DLC SPECIFICATIONS
ES-6512 Rev.11 Page 3/9
MODEL: DLC
CONNECTION DIAGRAM
■ TWISTED-PAIR CABLE
(transmission media code: 1)
■FIBER OPTICS CABLE
(transmission media code: 2)
■TWISTED-PAIR & FIBER OPTICS
(transmission media code: 7)
D-SUB
RS-232-C
D-SUB
RS-232-C
D-SUB
RS-232-C
CONNECTOR
CONNECTOR
CONNECTOR
FIBER - OPTIC
CONNECTOR
FIBER - OPTIC
CONNECTOR
Fiber Optics
FIBER - OPTIC
CONNECTOR
Fiber Optics
Shielded
Twisted-pair Cable
Shielded
Twisted-pair Cable
+
–
9
8
7
6
5
4
3
2
1
+
–
9
8
7
6
5
4
3
2
1
JUMPER PIN*
JUMPER PIN*
5
RUN CONTACT
RUN CONTACT
4
RUN CONTACT
3
2
1
EARTH (FG)
V(–)
EARTH (FG)
EARTH (FG)
V(–)
V(–)
POWER
POWER
POWER
U(+)
U(+)
U(+)
*When the unit is located at the end of transmission line via twisted-pair cable (= no cross-wiring),
short across the terminals 6 – 7 with the jumper pin (or wire) provided with the unit.
Remove the jumper pin for all the unit not located at the end.
DIMENSIONS unit: mm (inch)
■ STANDARD TYPE
SIDE MOUNTING 4 – 4 (.16) dia.
[53 (2.09) deep]
SURFACE MOUNTING M4 SCREW
[7 (.28) deep]
• 40-pin Connector Terminal Block
1
2
3
5
7
9
4
6
8
10
11
12
13
14
15
16
17
18
19
20
21
22
23
40–M3 SCREW
TERMINAL
24
26
28
30
32
34
36
38
40
25
27
29
31
33
35
37
39
3.5 (.14)
170 (6.69)
200 (7.87)
53 (2.09)
28 (1.10)
Observe appropriate space for the front RS-232-C cable
(provided by user).
(Fig.A-1)
(Fig. A-2)
http://www.m-system.co.jp/
DLC SPECIFICATIONS
ES-6512 Rev.11 Page 4/9
MODEL: DLC
■ WITH I/O CONNECTORS
SIDE MOUNTING 4 – 4 (.16) dia.
[53 (2.09) deep]
SURFACE MOUNTING M4 SCREW
[7 (.28) deep]
• Connector Pin Assignment
LED INDICATOR
SELECTOR
U
L
A1
B1
CN1
CN2
A20
A1
B20
B1
A20
B20
3.5 (.14)
170 (6.69)
200 (7.87)
53 (2.09)
80 (3.15) min.
Observe appropriate space for the front RS-232-C cable
(provided by user).
(Fig. B-1)
(Fig. B-2)
•Terminal Assignment, Euro Type Connector Terminals
•Wiring Procedure of Connector Terminals
PIN TERMINAL
PHOENIX CONTACT AI 1.5-8BK RECOMMENDED
MULTI-STRAND CABLE: 1.25 mm2 (.02 in2)
SCREWDRIVER (–)
9
*
8
7
6
5
4
SOLID CABLE
1.4 mm (.06) dia.
Remove cover.
8 mm (.32)
3
2
1
*
Not provided for fiber optics (code 2)
Note : There is no specific order for connecting fiber optics.
http://www.m-system.co.jp/
DLC SPECIFICATIONS
ES-6512 Rev.11 Page 5/9
MODEL: DLC
■ WITHOUT PROCESS I/O
• DLC-00
SIDE MOUNTING 4 – 4 (.16) dia.
[53 (2.09) deep]
SURFACE MOUNTING M4 SCREW
[7 (.28) deep]
3.5 (.14)
53 (2.09)
170 (6.69)
200 (7.87)
Observe appropriate space for the front RS-232-C cable
(provided by the user).
(Fig. C)
MOUNTING REQUIREMENTS unit: mm (inch)
■ SURFACE MOUNTING
■ SIDE MOUNTING (terminal block at the right side)
55
55
2–M4 SCREW
4–M4 SCREW
(2.17) (2.17)
3.5 (.14)
170 (6.69)
WIRING SPACE
95 (3.74) MIN.
http://www.m-system.co.jp/
DLC SPECIFICATIONS
ES-6512 Rev.11 Page 6/9
MODEL: DLC
FUNCTION BLOCK DIAGRAM
POWER TERMINALS
MULTI-XMISSION TERMINALS
1
2
6
7
8
9
4 5
RUN Relay
Contact
Multi-Xmission
Interface
Isolation
Circuit
RUN
LED
RUN
Controller
Network
CPU
Watch-dog
POWER LED
Station No.
Set SW
RAM
EP ROM
UART
Common RAM
or Latching Circuit
I/O
Controller
***
*
Isolation
Circuit
Contact I/O
Indicator LEDs
****
I/O CPU
RUN LED
I/O
Driver
**
**
I/O TERMINALS
MODULAR JACK
*
Not included with codes G1, P1, R1 or S1.
** Not included with codes A1, A2, C1, C2, C3, C4, E1 or E2.
*** Not included when there is no process I/O.
**** Not included with codes G1, M1 or R1.
SYSTEM CONFIGURATION EXAMPLES
1. Minimum System Configuration
This module
(with process I/O)
RS-232-C
process I/O
http://www.m-system.co.jp/
DLC SPECIFICATIONS
ES-6512 Rev.11 Page 7/9
MODEL: DLC
2. Remote I/O: 1 Computer
This module
(with process I/O)
RS-232-C
twisted-pair cable
or fiber optics
Control Room
Field
multi-transmission line
DLA1
DLA1
DLA1
DLA1
.
.
.
.
process I/O
process I/O
process I/O
process I/O
3. Remote I/O: 1 Computer and Multi-Transmission Unit for Back-Up
DLA1
direct I/O transmission
with the field
This module
RS-232-C
twisted-pair cable
or fiber optics
indicator (lamp, meter)
operation terminal (switch)
Control Room
Field
multi-transmission line
DLA1
DLA1
DLA1
DLA1
.
.
.
.
process I/O
process I/O
process I/O
process I/O
4. Remote I/O: Several Computers
This module
This module
RS-232-C
RS-232-C
twisted-pair cable
or fiber optics
twisted-pair cable
or fiber optics
Control Room A
Field
Control Room B
multi-transmission line
DLA1
DLA1
DLA1
DLA1
.
.
.
.
process I/O
process I/O
process I/O
process I/O
http://www.m-system.co.jp/
DLC SPECIFICATIONS
ES-6512 Rev.11 Page 8/9
MODEL: DLC
5. Remote I/O: Via Modem
modem cable
(straight)
Station A
leased circuit
Station B
This module
modem cable
(straight)
multi-transmission line
DLA1
DLA1
DLA1
DLA1
.
.
.
.
process I/O
process I/O
process I/O
process I/O
Specifications are subject to change without notice.
http://www.m-system.co.jp/
DLC SPECIFICATIONS
ES-6512 Rev.11 Page 9/9
相关型号: