PDF下载MODEL: FRTD
G: 0 – 1 mA DC (Input resistance 1000 Ω)
Space-saving Plug-in Signal Conditioners F-UNIT
H: 10 – 50 mA DC (Input resistance 100 Ω)
J: 0 – 10 μA DC (Input resistance 1000 Ω)
K: 0 – 100 μA DC (Input resistance 1000 Ω)
GW: -1 – +1 mA DC (Input resistance 1000 Ω)
FW: -10 – +10 mA DC (Input resistance 100 Ω)
Z: Specify current (See INPUT SPECIFICATIONS)
Voltage
RATIO TRANSMITTER
(output bias; thumbwheel switch adjustments)
Functions & Features
• Providing precise matching of DC control signals to final
control elements in open- or closed-loop systems
• Easy thumbwheel switch adjustments
• Ratio adjustable from 0.1 to 3.99
• Bias adjustable within ±99 %
1: 0 – 10 mV DC (Input resistance 10 kΩ min.)
15: 0 – 50 mV DC (Input resistance 10 kΩ min.)
16: 0 – 60 mV DC (Input resistance 10 kΩ min.)
2: 0 – 100 mV DC (Input resistance 100 kΩ min.)
3: 0 – 1 V DC (Input resistance 1 MΩ min.)
4: 0 – 10 V DC (Input resistance 1 MΩ min.)
5: 0 – 5 V DC (Input resistance 1 MΩ min.)
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
4W: -10 – +10 V DC (Input resistance 1 MΩ min.)
5W: -5 – +5 V DC (Input resistance 1 MΩ min.)
0: Specify voltage (See INPUT SPECIFICATIONS)
• High-density mounting
Typical Applications
• Ratio control for air/fuel flows or for two flows
• Gain calculation for manipulated variable from a controller
• Large scale signal span adjustment
26 (1.02)
[3] OUTPUT
Current
100
(3.94)
A: 4 – 20 mA DC (Load resistance 750 Ω max.)
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D: 0 – 20 mA DC (Load resistance 750 Ω max.)
E: 0 – 16 mA DC (Load resistance 900 Ω max.)
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
137
(5.39)
mm (inch)
MODEL: FRTD–[1]–[2][3]–[4][5]
ORDERING INFORMATION
• Code number: FRTD-[1]-[2][3]-[4][5]
Specify a code from below for each of [1] through [5].
(e.g. FRTD-S-AA-L/Q)
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3: 0 – 1 V DC (Load resistance 1000 Ω min.)
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
5: 0 – 5 V DC (Load resistance 5000 Ω min.)
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
4W: -10 – +10 V DC (Load resistance 10 kΩ min.)
5W: -5 – +5 V DC (Load resistance 5000 Ω min.)
0: Specify voltage (See OUTPUT SPECIFICATIONS)
• Special input and output ranges (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] OUTPUT CHARACTERISTICS
S: Positive
R: Negative
[4] POWER INPUT
AC Power
[2] INPUT
K: 85 – 132 V AC
Current
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
A: 4 – 20 mA DC (Input resistance 250 Ω)
A1: 4 – 20 mA DC (Input resistance 50 Ω)
B: 2 – 10 mA DC (Input resistance 500 Ω)
C: 1 – 5 mA DC (Input resistance 1000 Ω)
D: 0 – 20 mA DC (Input resistance 50 Ω)
E: 0 – 16 mA DC (Input resistance 62.5 Ω)
F: 0 – 10 mA DC (Input resistance 100 Ω)
L: 170 – 264 V AC
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
FRTD SPECIFICATIONS
ES-1485 Rev.6 Page 1/4
http://www.m-system.co.jp/
MODEL: FRTD
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
INPUT SPECIFICATIONS
■ DC Current:
Shunt resistor attached to the input terminals (0.5 W)
Specify input resistance value for code Z.
■ DC Voltage: -300 – +300 V DC
Minimum span: 3 mV
[5] OPTIONS
blank: none
/Q: With options (specify the specification)
Offset: Max. 1.5 times span
Input resistance
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Span 3 – 10 mV : ≥ 10 kΩ
Span 10 – 100 mV : ≥ 10 kΩ
Span 0.1 – 1 V : ≥ 100 kΩ
Span ≥ 1 V : ≥ 1 MΩ
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
OUTPUT SPECIFICATIONS
■ DC Current: 0 – 20 mA DC
GENERAL SPECIFICATIONS
Construction: Plug-in
Minimum span: 1 mA
Offset: Max. 1.5 times span
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
Load resistance: Output drive 15 V max.
■ DC Voltage: -10 – +12 V DC
Minimum span: 5 mV
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Offset: Max. 1.5 times span
Load resistance: Output drive 1 mA max. at ≥ 0.5 V
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
INSTALLATION
Power input
Equation: X
= F – K X
where X : output (%)
: input (%)
K: ratio
o
= KX
i
+ B for positive ratio;
•AC: Approx. 4.5 VA
X
o
i
+ B for negative ratio
•DC: 24 V approx. 70 mA
o
110 V approx. 20 mA
Xi
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail; Standard Rack Mounting
Frame BX-16H available
(0.1 – 3.99 conformance range)
B: bias (-99 – +99 %)
F: 100 %
Weight: 200 g (0.44 lb)
(factory setting: K = 1, B = 0 %)
Ratio/bias adjustment: 3-digit thumbwheel switches
100%
PERFORMANCE in percentage of span
Ratio setting accuracy: ±0.2 %
[Examples of Positive Gain]
2
1
1
2
3
4
5
6
K = 1
B
B
B
B
B
B
= 50%
= 50%
= 0
4
K = 0.5
K = 2
(at 0.1 – 3.99 conformance range)
50
Bias setting accuracy: ±1 %
K = 1
= 0
3
5
6
K = 0.5
K = 1
= 0
Accuracy: ±0.3 % (with ratio = 1, bias = 0 %)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength
= –50%
0
0
50
100%
INPUT
100%
[Examples of Negative Gain]
5
1
1
2
3
4
5
6
K = 1
B
B
B
B
B
B
= 50%
= –50%
= 0
3
K = 0.5
K = 2
Power input code R:
50
1000 V AC @ 1 minute (input to output)
2000 V AC @ 1 minute (input or output or power to ground)
500 V AC @ 1 minute (I/O to power)
K = 1
= 0
4
K = 0.5
K = 1
= 0
6
2
= –50%
0
0
50
100%
Power input code K, L, P:
INPUT
1000 V AC @ 1 minute (input to output)
2000 V AC @ 1 minute (input or output or power to ground)
FRTD SPECIFICATIONS
ES-1485 Rev.6 Page 2/4
http://www.m-system.co.jp/
MODEL: FRTD
1500 V AC @ 1 minute (I/O to power)
EXTERNAL VIEW
Zero Adj.
Ratio Adj.
3 9 9
Bias Adj.
+
9 9
Span Adj.
EXTERNAL DIMENSIONS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
1
2
15
(.59)
DIN RAIL
35mm wide
3
4
2–4.5 (.18)
HOLE
15 (.59) deep
5
6
8–M3.5
SCREW
7
8
26 (1.02)
107 (4.21)
137 (5.39)
26 (1.02)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
TERMINAL ASSIGNMENTS unit: mm (inch)
INPUT RESISTOR
(model: REM)
1
2
3
4
5
6
7
8
Input shunt resistor attached
for current input.
FRTD SPECIFICATIONS
ES-1485 Rev.6 Page 3/4
http://www.m-system.co.jp/
MODEL: FRTD
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
RATIO
BIAS
+
THUMBWHEEL
SWITCHES
3 9 9
9 9
Z
S
Isolation
Low Drift
Amplifier
Reverser, Ratio / Bias
Computation
Output
Driver
+
–
1
2
3
4
5
6
7
8
+
*
INPUT
R
OUTPUT
POWER
–
U(+)
V(–)
Base Socket
*Input shunt resistor attached for current input.
Specifications are subject to change without notice.
FRTD SPECIFICATIONS
ES-1485 Rev.6 Page 4/4
http://www.m-system.co.jp/
FRTD-R-GW5W-P 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
FRTD-R-GW5W-R | MSYSTEM | Space-saving Plug-in Signal Conditioners F-UNIT | 获取价格 | |
FRTD-R-GW6-K | MSYSTEM | Space-saving Plug-in Signal Conditioners F-UNIT | 获取价格 | |
FRTD-R-GW6-K/Q | MSYSTEM | Space-saving Plug-in Signal Conditioners F-UNIT | 获取价格 | |
FRTD-R-GW6-L | MSYSTEM | Space-saving Plug-in Signal Conditioners F-UNIT | 获取价格 | |
FRTD-R-GW6-P | MSYSTEM | Space-saving Plug-in Signal Conditioners F-UNIT | 获取价格 | |
FRTD-R-GW6-R | MSYSTEM | Space-saving Plug-in Signal Conditioners F-UNIT | 获取价格 | |
FRTD-R-GWA-K | MSYSTEM | Space-saving Plug-in Signal Conditioners F-UNIT | 获取价格 | |
FRTD-R-GWA-K/Q | MSYSTEM | Space-saving Plug-in Signal Conditioners F-UNIT | 获取价格 | |
FRTD-R-GWA-L | MSYSTEM | Space-saving Plug-in Signal Conditioners F-UNIT | 获取价格 | |
FRTD-R-GWA-L/Q | MSYSTEM | Space-saving Plug-in Signal Conditioners F-UNIT | 获取价格 |
FRTD-R-GW5W-P 相关文章
- 2024-10-31
- 6
- 2024-10-31
- 6
- 2024-10-31
- 7
- 2024-10-31
- 8