MODEL: HAS
Space-saving Plug-in Signal Conditioners H-UNIT
[2] OUTPUT
1: Single (SPDT); Hi in power failure
2: Single (SPDT); Lo in power failure
5: Hi/Lo (N.O.); OFF in power failure
6: Hi/Lo (N.C.); OFF in power failure
0: Specify
DC ALARM
Functions & Features
• Providing relay contact closures at preset DC input levels
• Single or dual (Hi/Lo) trip
• Multi-turn screwdriver setpoint adjustments
• Enclosed relays
POWER INPUT
• Relays can be powered 110 V DC
• High-density mounting
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Typical Applications
• Annunciator
[3] OPTIONS
blank: none
• Various alarm applications
/Q: With options (specify the specification)
26 (1.02)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
93
(3.66)
/C02: Polyurethane coating
/C03: Rubber coating
137
(5.39)
TERMINAL SCREW MATERIAL
/S01: Stainless steel
mm (inch)
MODEL: HAS–[1][2]–R[3]
GENERAL SPECIFICATIONS
Construction: Plug-in
ORDERING INFORMATION
• Code number: HAS-[1][2]-R[3]
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
Specify a code from below for each of [1] through [3].
(e.g. HAS-62-R/Q)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
• Special input range (For code 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
Setpoint adjustments: Multi-turn screwdriver adjustments
(front); -5 – +105 % independently
Use Ordering Information Sheet (No. ESU-1033) to specify
output code 0 specifications.
Hysteresis (deadband): Approx. 1 %
Front LEDs: Red LED turns on when the coil is energized.
Power ON timer: Relays de-energized for approx. 2 seconds
after power is turned on.
[1] INPUT
Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
D: 0 – 20 mA DC (Input resistance 50 Ω)
G: 0 – 1 mA DC (Input resistance 1000 Ω)
H: 10 – 50 mA DC (Input resistance 100 Ω)
Voltage
INPUT SPECIFICATIONS
■ DC Current:
Shunt resistor attached to the input terminals (0.5 W)
■ DC Voltage: 0 – 300 V DC
Minimum span: 1 V
3: 0 – 1 V DC (Input resistance 1 MΩ min.)
4: 0 – 10 V DC (Input resistance 1 MΩ min.)
5: 0 – 5 V DC (Input resistance 1 MΩ min.)
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
0: Specify voltage (See INPUT SPECIFICATIONS)
Offset: Max. 1.5 times span
Input resistance: ≥ 1 MΩ
HAS SPECIFICATIONS
ES-3481 Rev.11 Page 1/4
http://www.m-system.co.jp/
MODEL: HAS
Insulation resistance: ≥ 100 MΩ with 500 V DC
OUTPUT SPECIFICATIONS
■ Relay Contact: 100 V AC @ 1 A (cos ø = 1)
120 V AC @ 1 A (cos ø = 1)
Dielectric strength: 500 V AC @ 1 minute
(input to output to power)
1500 V AC @ 1 minute (input or output or power to ground)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 380 V AC or 125 V DC
Maximum switching power: 120 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Mechanical life: 5 x 10 cycles
7
For maximum relay life with inductive loads, external
protection is recommended.
Alarm Trip Operation Terminal No. in parentheses
•Output Code : 1, 2
(3–5)ON
Output
(3–6)ON
Input
(%)
0
50
50
50
▲
100
100
100
Setpoint
•Output Code : 5
(3–5)ON
Hi Output
(3–6)ON
Lo Output
Input
(%)
0
▲
▲
Lo Setpoint
Hi Setpoint
•Output Code : 6
(3–5)ON
Hi Output
(3–6)ON
Lo Output
Input
(%)
0
▲
▲
Lo Setpoint
Hi Setpoint
Trip Operation in Power Failure
• Output Code 1: Terminals 3 – 5 turn ON
• Output Code 2: Terminals 3 – 6 turn ON
• Output Code 5, 6: both relays turn OFF
INSTALLATION
Current consumption: Approx. 40 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail; Standard Rack Mounting
Frame BX-16H available
Weight: 180 g (0.40 lb)
PERFORMANCE in percentage of span
Trip point repeatability: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: Approx. 0.5 sec. (0 – 100 % at 90 %
setpoint)
Line voltage effect: ±0.1 % over voltage range
HAS SPECIFICATIONS
ES-3481 Rev.11 Page 2/4
http://www.m-system.co.jp/
MODEL: HAS
EXTERNAL VIEW
Single or Dual High LED
Single Alarm or
Dual High Setpoint Adj.
Dual Low Setpoint Adj.*
Dual Low LED*
*Not provided for Single Alarm.
EXTERNAL DIMENSIONS unit: mm (inch)
7.8 (.31)
CLAMP
(top & bottom)
1
2
15
(.59)
DIN RAIL
35mm wide
3
4
2–4.5 (.18)
HOLE
15 (.59) deep
5
6
8–M3.5
SCREW
7
8
107 (4.21)
137 (5.39)
26 (1.02)
26 (1.02)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
TERMINAL ASSIGNMENTS unit: mm (inch)
INPUT RESISTOR
(model: REM)
1
2
3
4
5
6
7
8
Input shunt resistor attached
for current input.
HAS SPECIFICATIONS
ES-3481 Rev.11 Page 3/4
http://www.m-system.co.jp/
MODEL: HAS
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■ SINGLE ALARM
■ Relay Protection
•AC Powered
ADJ.
Inductive
Load (Coil)
**
5
Varistor or Spark
Quenching Circuit
Low Drift
Amplifier
LOAD
+
–
1
2
4
Comparator
Ry
*
6
3
7
8
OUTPUT
POWER
INPUT
R
U
•DC Powered
Inductive
Load (Coil)
+
–
Diode, Varistor or
CR Circuit
LOAD
Base Socket
* Input shunt resistor attached for current input.
**Relay status is determined by output codes.
■ DUAL ALARM
HI ADJ. LO ADJ.
**
**
5
6
3
7
8
HI
Low Drift
Amplifier
Ry
+
–
1
2
4
Comparator
*
OUTPUT
POWER
INPUT
R
LO
Ry
+
–
Base Socket
* Input shunt resistor attached for current input.
**Relay status is determined by output codes.
Specifications are subject to change without notice.
HAS SPECIFICATIONS
ES-3481 Rev.11 Page 4/4