MODEL: HJDL
Space-saving Plug-in Signal Conditioners H-UNIT
LINEARIZATION CODE
1: Segment data
2: Square root extraction
3: Thermocouple
4: RTD
DEFAULT
Linear
–––
CURRENT LOOP SUPPLY
(linearizing; field-programmable)
Functions & Features
K
0 – 1000°C
Pt 100 0 – 100°C
• Powering a 4 – 20 mA DC current loop
• Microprocessor based
• Shortcircuit protection
INPUT
Current
• Applicable to smart transmitters
• Field-programmable linearization data
• Loop testing via hand-held programmer PU-2x
• High-density mounting
A: 4 – 20 mA DC (Input resistance 250 Ω)
[1] LINEARIZATION
0: None
Typical Applications
1: Segment data
2: Square root extraction
3: Thermocouple
4: RTD
• Various 2-wire transmitters
• Providing isolation and linearization for a 2-wire
temperature transmitter
• Linearizing weir flowmeter output to provide a linear-to-
volume signal
• Linearizer application
[2] OUTPUT
Current
(4 – 20 mA input)
• Square root extraction for differential pressure transmitter
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
26 (1.02)
6: 1 – 5 V DC (Load resistance 500 Ω min.)
93
(3.66)
POWER INPUT
DC Power
R: 24 V DC
137
(5.39)
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
mm (inch)
[3] OPTIONS
blank: none
MODEL: HJDL–A[1][2]–R[3]
/Q: With options (specify the specification)
ORDERING INFORMATION
• Code number: HJDL-A[1][2]-R[3]
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Specify a code from below for each of [1] through [3].
(e.g. HJDL-A1A-R/Q)
/C02: Polyurethane coating
Default setting (following table) will be used if not otherwise
specified.
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
No linearization data will be programmed if you don't
specify type of linearization and required data.
• Linearization data
Code 1 segment data: Use Ordering Information Sheet (No.
ESU-1669) to specify linearization data.
Code 3 T/C, Code 4 RTD: Specify input sensor type and
temperature range.
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
• Specify the specification for option code /Q
(e.g. /C01/S01)
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
HJDL SPECIFICATIONS
ES-3474 Rev.9 Page 1/3
http://www.m-system.co.jp/
MODEL: HJDL
cable types.
• Thermocouple linearizable range
USABLE RANGE
°C
T/C
GENERAL SPECIFICATIONS
Construction: Plug-in
°F
(PR)
K (CA)
E (CRC)
0 to 1760
-270 to +1370
-270 to +1000
32 to 3200
-454 to +2498
-454 to +1832
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
J
(IC)
T (CC)
B (RH)
-210 to +1200
-270 to +400
0 to 1820
-346 to +2192
-454 to +752
32 to 3308
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
R
S
-50 to +1760
-50 to +1760
-58 to +3200
-58 to +3200
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Linearization: 16 points max. represented as percentage of
full-scale
Note: For the temperatures that range below 0°C, the
transmitter may partially not satisfy the described accuracy.
Consult factory.
Adjustments: Programming Unit (model: PU-2x);
linearization data, zero and span, simulating output, etc.
(Refer to the users manual of JXCON for the adjustments
configurable with JXCON.)
• RTD linearizable range
USABLE RANGE
RTD
°C
°F
JPt 100 (JIS ’89)
Pt 100 (JIS ’89)
Pt 100 (JIS ’97, IEC)
Pt 50Ω (JIS ’81)
Ni 508.4 Ω
-200 to +500
-200 to +650
-200 to +650
-200 to +500
-50 to +200
-328 to +932
-328 to +1202
-328 to +1202
-328 to +932
-58 to +392
SUPPLY OUTPUT
Output voltage: 24 – 28 V DC with no load
Current rating: ≤ 22 mA DC
• Shortcircuit Protection
Note:Pt100(JIS’89)isdeviatedfromPt100(JIS’97) only
within the described accuracy.
Current limited: 30 mA max.
Protected time duration: No limit
INSTALLATION
INPUT SPECIFICATIONS
Current consumption: Approx. 95 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail; Standard Rack Mounting
Frame BX-16H available
■ DC Current: Input resistor incorporated
LINEARIZATION
• No linearization: The output is proportional to the input.
• Segment data: 16 points (15 segments) max. within the
range of -15.00 to +115.00 % input or output represented
as percentage of fullscale
Weight: 220 g (0.49 lb)
PERFORMANCE in percentage of span
Accuracy: ±0.1 % with segment gain ≤ 1 [±0.1 % × gain]
with segment gain > 1
• Square root extraction
Low-end cutout: 5 % (output); curve characteristics as in the
figure below
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
■ Square root extraction
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(input to output to power)
6%
5%
1500 V AC @ 1 minute (input or output or power to ground)
0
INPUT
HJDL SPECIFICATIONS
ES-3474 Rev.9 Page 2/3
http://www.m-system.co.jp/
MODEL: HJDL
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
7.8 (.31)
CLAMP
(top & bottom)
1
2
15
(.59)
DIN RAIL
35mm wide
3
4
2–4.5 (.18)
HOLE
15 (.59) deep
5
6
8–M3.5
SCREW
7
8
107 (4.21)
137 (5.39)
26 (1.02)
26 (1.02)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
2-WIRE
TRANSMITTER
Current
Limiter
24V DC
Supply
+
+
–
1
2
3
4
Isolation
Digital
Computation
Output
Driver
–
5
6
7
8
+
–
+
–
OUTPUT
POWER
+
MONITOR
V
(1 – 5V DC)
–
250Ω
MODULAR JACK
PU-2x
SERIAL TRANSMISSION LINE
Base Socket
■ When Used as Linearizer
No Connection
1
2
3
+
250Ω
INPUT
–
Specifications are subject to change without notice.
HJDL SPECIFICATIONS
ES-3474 Rev.9 Page 3/3
http://www.m-system.co.jp/