HJPA-3A-R/Q [MSYSTEM]
Space-saving Plug-in Signal Conditioners H-UNIT;型号: | HJPA-3A-R/Q |
厂家: | M-SYSTEM |
描述: | Space-saving Plug-in Signal Conditioners H-UNIT |
文件: | 总3页 (文件大小:108K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: HJPA
Space-saving Plug-in Signal Conditioners H-UNIT
[2] OUTPUT
Current
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
FREQUENCY TRANSMITTER
(field-programmable)
6: 1 – 5 V DC (Load resistance 500 Ω min.)
Functions & Features
• Converting the output from a pulse-type transducer into a
standard process signal
POWER INPUT
• Micro-processor based
DC Power
• Field-programmable frequency range
• Linearization available for flow compensation
• Averaging non-uniform pulses
• Excitation
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank: none
• Loop testing via hand-held programmer PU-2x
• Highdensity mounting
/Q: With options (specify the specification)
Typical Applications
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Positive displacement flowmeters, turbine flowmeters and
vortex flowmeters
• Proximity switches
/C02: Polyurethane coating
• Oval flowmeters
/C03: Rubber coating
26 (1.02)
TERMINAL SCREW MATERIAL
/S01: Stainless steel
93
(3.66)
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
137
(5.39)
mm (inch)
MODEL: HJPA–[1][2]–R[3]
ORDERING INFORMATION
• Code number: HJPA-[1][2]-R[3]
GENERAL SPECIFICATIONS
Construction: Plug-in
Specify a code from below for each of [1] through [3].
(e.g. HJPA-3A-R/Q)
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
• Frequency range (e.g. 0 – 152.3 Hz)
• Linearization data (max. 16 points)
Use Ordering Information Sheet (No. ESU-1673) to specify
linearization data when the I/O signals are non-linear.
• Specify the specification for option code /Q
(e.g. /C01/S01)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: -10 – +120 % at 1 – 5 V
(0 – 120 % when 0 % input equals to 0 Hz.)
Linearization: 16 points max. represented as percentage of
full-scale
Note: Consult factory on applications with a sensor handling
periodically (& quickly) changing frequency (e.g. oval
flowmeter).
Adjustments: Programming Unit (model: PU-2x); input
range, low-end cutout, zero and span, simulating output,
averaging nonuniform pulses, linearization data, etc.
(Refer to the users manual of JXCON for the adjustments
configurable with JXCON.)
[1] INPUT
1: Open collector (Excitation: 12 V @ 30 mA)
2: Voltage pulse (Excitation: 12 V @ 30 mA)
3: Mechanical contact (Excitation: 12 V @ 30 mA)
Low-end cutout: 0 – 100 % adjustable (factory set to 0 %);
hysteresis fixed to 1 %
HJPA SPECIFICATIONS
ES-3473 Rev.13 Page 1/3
http://www.m-system.co.jp/
MODEL: HJPA
INPUT SPECIFICATIONS
Excitation: 12 V DC @30 mA; shortcircuit protection
Pulse width (time) requirement: 10 msec. min. at
< 20 Hz; duty ratio 20 – 80 % at ≥ 20 Hz
Offset: Max. 3 times span
■ Open Collector
Frequency range: 0 – 0.01 Hz through 25 kHz
(0 – 1 kHz will be used if not otherwise specified)
Sensing: Approx. 12 V DC @ 3 mA
ON/OFF level: ≤ 800 Ω / 2 V for ON,
≥ 1.2 kΩ / 3.6 V for OFF
■ Mechanical Contact
Frequency range: 0 – 0.01 Hz through 5 Hz
(0 – 5 Hz will be used if not otherwise specified)
Sensing: Approx. 12 V DC @ 3 mA
ON/OFF level: ≤ 800 Ω / 2 V for ON,
≥ 1.2 kΩ / 3.6 V for OFF
■ Voltage Pulse: Square or sine waveforms
Frequency range: 0 – 0.01 Hz through 25 kHz
(0 - 1 kHz will be used if not otherwise specified.)
Input amplitude: 2 – 50 Vp-p
Input impedance: 10 kΩ min.
INSTALLATION
Current consumption: Approx. 90 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail; Standard Rack Mounting
Frame BX-16H available
Weight: 220 g (0.49 lb)
PERFORMANCE in percentage of span
Accuracy: ±0.1 % with segment gain ≤ 1 [±0.1 % × gain]
with segment gain > 1
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: 0.5 sec. + 1 pulse cycle (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(input to output to power)
1500 V AC @ 1 minute (input or output or power to ground)
HJPA SPECIFICATIONS
ES-3473 Rev.13 Page 2/3
http://www.m-system.co.jp/
MODEL: HJPA
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
7.8 (.31)
CLAMP
(top & bottom)
1
2
15
(.59)
DIN RAIL
35mm wide
3
4
2–4.5 (.18)
HOLE
15 (.59) deep
5
6
8–M3.5
SCREW
7
8
107 (4.21)
137 (5.39)
26 (1.02)
26 (1.02)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Isolation
Waveform
Shaper
Digital
Computation
Output
Driver
+
–
1
2
3
4
5
6
7
8
+
–
+
–
INPUT
OUTPUT
POWER
SENSOR EXCITATION
+
12V Supply
MODULAR JACK
PU-2x
SERIAL TRANSMISSION LINE
Base Socket
Input Connection Examples
■ Open Collector or Mechanical Contact ■ Voltage Pulse
+
–
–
+
1
2
3
+
–
–
+
1
2
3
+12V
+12V
PWR
PWR
4kΩ
Specifications are subject to change without notice.
HJPA SPECIFICATIONS
ES-3473 Rev.13 Page 3/3