HPA-13-R/Q [MSYSTEM]
Space-saving Plug-in Signal Conditioners H-UNIT;型号: | HPA-13-R/Q |
厂家: | M-SYSTEM |
描述: | Space-saving Plug-in Signal Conditioners H-UNIT |
文件: | 总3页 (文件大小:101K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: HPA
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Space-saving Plug-in Signal Conditioners H-UNIT
Z: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
PT TRANSMITTER
(Average sensing, RMS calibrated)
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3: 0 – 1 V DC (Load resistance 1000 Ω min.)
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
5: 0 – 5 V DC (Load resistance 5000 Ω min.)
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
0: Specify voltage (See OUTPUT SPECIFICATIONS)
Functions & Features
• Converting an alternating voltage from a potential
(voltage) transformer into a standard process signal
• Minimum ripple
• Average sensing
• High-density mounting
POWER INPUT
Typical Applications
DC Power
• Centralized monitoring and control of power line and
power supply voltage measured at switch boards
• Monitoring abnormal voltage drops for detecting overload
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
26 (1.02)
blank: none
/Q: With options (specify the specification)
93
(3.66)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
137
(5.39)
/C02: Polyurethane coating
mm (inch)
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
MODEL: HPA–[1][2]–R[3]
GENERAL SPECIFICATIONS
Construction: Plug-in
ORDERING INFORMATION
• Code number: HPA-[1][2]-R[3]
Specify a code from below for each of [1] through [3].
(e.g. HPA-1A-R/Q)
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Input waveform: Sine wave
Overrange output: 0 to 120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
[1] INPUT (sine wave)
Voltage
1: 0 – 110 V AC
5: 0 – 150 V AC
INPUT SPECIFICATIONS
Frequency: 50 or 60 Hz
[2] OUTPUT
Current
Input burden: 0.5 VA max.
Overload capacity: 200 % of rating for 1 minute, 120 %
continuous
A: 4 – 20 mA DC (Load resistance 750 Ω max.)
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D: 0 – 20 mA DC (Load resistance 750 Ω max.)
E: 0 – 16 mA DC (Load resistance 900 Ω max.)
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)
Operational range: 0 – 120 % of rating
HPA SPECIFICATIONS
ES-3438 Rev.7 Page 1/3
http://www.m-system.co.jp/
MODEL: HPA
OUTPUT SPECIFICATIONS
■ DC Current: 0 – 20 mA DC
Minimum span: 1 mA
Offset: Max. 1.5 times span
Load resistance: Output drive 15 V max.
■ DC Voltage: 0 – 12 V DC
Minimum span: 5 mV
Offset: Max. 1.5 times span
Load resistance: Output drive 1 mA max.; at ≥ 0.5 V
INSTALLATION
Current consumption: Approx. 55 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail; Standard Rack Mounting
Frame BX-16H available
Weight: 200 g (0.44 lb)
PERFORMANCE in percentage of span
Accuracy: ±0.4 %
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Ripple: 0.5 %p-p max. (100/120 Hz)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute
(input to output or power)
500 V AC @ 1 minute (output to power)
1500 V AC @ 1 minute
(input or output or power to ground)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
7.8 (.31)
CLAMP
(top & bottom)
1
2
15
(.59)
DIN RAIL
35mm wide
3
4
2–4.5 (.18)
HOLE
15 (.59) deep
5
6
8–M3.5
SCREW
7
8
107 (4.21)
137 (5.39)
26 (1.02)
26 (1.02)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
HPA SPECIFICATIONS
ES-3438 Rev.7 Page 2/3
http://www.m-system.co.jp/
MODEL: HPA
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
SOURCE
Z
S
INPUT
TRANSFORMER
VT
FUSE
U
V
u
v
Average
Operation
Output
Driver
1
2
3
4
5
6
7
8
+
–
+
–
OUTPUT
LOAD
POWER
Base Socket
Specifications are subject to change without notice.
HPA SPECIFICATIONS
ES-3438 Rev.7 Page 3/3
http://www.m-system.co.jp/