HPV-5-R/P7 [MSYSTEM]
Space-saving Plug-in Signal Conditioners H-UNIT;型号: | HPV-5-R/P7 |
厂家: | M-SYSTEM |
描述: | Space-saving Plug-in Signal Conditioners H-UNIT |
文件: | 总3页 (文件大小:100K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: HPV
Space-saving Plug-in Signal Conditioners H-UNIT
POWER INPUT
DC Power
R: 24 V DC
P/I TRANSDUCER
Functions & Features
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Converting a standard pneumatic signal into a
proportional DC output
[2] OPTIONS (multiple selections)
• High-density mounting
Input
blank: 0.2 – 1.0 kgf/cm
/A1S: 19.6 – 98.1 kPa
/A2S: 20 – 100 kPa
/A3S: 20.7 – 103.4 kPa
/A2: 0.2 – 1.0 bar
2
Typical Applications
• Converting a pneumatic system into a 4 – 20 mA for
indicating and controlling in DCS system
25 (.98)
/A3: 3 – 15 psig
H•UNIT
HPV
Pneumatic Connection
blank: Rc 1/4"
123
(4.84)
/P7: 1/4" NPT fitting
GENERAL SPECIFICATIONS
Construction: Plug-in
120
(4.72)
Connection
mm (inch)
Output & power input: M3.5 screw terminals;
torque 0.8 N·m
MODEL: HPV–[1]–R[2]
Pneumatic: Rc 1/4" or 1/4" NPT female; torque ≤ 12 N·m
Material
Housing: Flame-resistant resin (black)
Base socket: Die cast aluminium
Screw terminals: Nickel-plated steel
Isolation: Output to power
ORDERING INFORMATION
• Code number: HPV–[1]–R[2]
Specify a code from below for each of [1] and [2].
(e.g. HPV-A-R/A2S/P7)
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
• Special output range (For codes Z & 0)
[1] OUTPUT
Current
INPUT SPECIFICATIONS
■ Input
A: 4 – 20 mA DC (Load resistance 750 Ω max.)
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D: 0 – 20 mA DC (Load resistance 750 Ω max.)
E: 0 – 16 mA DC (Load resistance 900 Ω max.)
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
19.6 – 98.1 kPa, 0.2 – 1.0 kgf/cm
2
20 – 100 kPa, 0.2 – 1.0 bar
20.7 – 103.4 kPa, 3 – 15 psig
OUTPUT SPECIFICATIONS
■ DC Current: 0 – 20 mA DC
Minimum span: 1 mA
Offset: Max. 1.5 times span
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3: 0 – 1 V DC (Load resistance 1000 Ω min.)
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
5: 0 – 5 V DC (Load resistance 5000 Ω min.)
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
0: Specify voltage (See OUTPUT SPECIFICATIONS)
Load resistance: Output drive 15 V max.
■ DC Voltage: 0 – 12 V DC
Minimum span: 5 mV
Offset: Max. 1.5 times span
Load resistance: Output drive 1 mA max.; at ≥ 1 V
INSTALLATION
Current consumption: Approx. 60 mA
Operating temperature: -5 to +55°C (23 to 131°F)
HPV SPECIFICATIONS
ES-3420 Rev.9 Page 1/3
http://www.m-system.co.jp/
MODEL: HPV
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface; Standard Rack Mounting Frame (BX-
16H) available
Weight: 400 g (0.88 lb)
PERFORMANCE in percentage of span
Accuracy: ±0.2 %
Temp. coefficient: ±0.03 %/°C (±0.02 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Permissible overrange: 196 kPa (2.0 kgf/cm2, 1.96 bar, 28
psig)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500V AC @ 1 minute
(output to power to housing)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
8.3
(.32)
1
2
4
4–M3.5
SCREW
3
15 (.59)
PNEUMATIC
CONNECTION
Rc 1/4” or 1/4” NPT
2–4.3 (.17) dia.
MTG HOLE
*
NPT FITTING
25 (.98)
103 (4.06)
123 (4.84)
25 (.98)
•When mounting, no extra space is needed between units.
*Fitting provided for 1/4” NPT connection.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Z
S
Semiconductor
Pressure Sensor
Low Drift
Amplifier
Output
Driver
3
4
1
2
+
–
+
–
INPUT
OUTPUT
POWER
CONSTANT
CURRENT
Base Socket
HPV SPECIFICATIONS
ES-3420 Rev.9 Page 2/3
http://www.m-system.co.jp/
MODEL: HPV
Specifications are subject to change without notice.
HPV SPECIFICATIONS
ES-3420 Rev.9 Page 3/3
http://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明