HSN-2H6/Q [MSYSTEM]

Space-saving Plug-in Signal Conditioners H-UNIT;
HSN-2H6/Q
型号: HSN-2H6/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Space-saving Plug-in Signal Conditioners H-UNIT

文件: 总3页 (文件大小:110K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: HSN  
Space-saving Plug-in Signal Conditioners H-UNIT  
[2] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
INPUT LOOP POWERED ISOLATOR  
Functions & Features  
• Loop-powered design eliminates output loop power supply  
• 500 V DC input-to-output isolation  
• 2 isolators housed in one enclosure  
• 350 Ω output drive with 4 – 20 mA  
• High-density mounting  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
Typical Applications  
• Isolation between control room and field instrumentation,  
between telemetering system and input device  
• Eliminates ground problems in existing systems  
thanks to easiness of application without requiring  
additional power wiring  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel (standard) or stainless  
steel  
26 (1.02)  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output; between channels  
Zero adjustment (front)  
93  
(3.66)  
Voltage output: -5 to +5 %  
Current output: -0.5 to +0.5 %  
Span adjustment (front)  
137  
(5.39)  
Voltage output: 95 to 105 %  
mm (inch)  
Current output: 98.5 to 101.5 %  
MODEL: HSN–[1][2]  
INPUT & OUTPUT  
■ Input 4 – 20 mA DC / Output 1 – 5 V DC  
Equivalent input impedance: Approx. 250 Ω with 20 mA  
input  
ORDERING INFORMATION  
• Code number: HSN-[1][2]  
Operational range: 3 – 22 mA DC  
(Accuracy is assured within 4 – 22 mA)  
Load resistance: ≥ 50 kΩ  
Specify a code from below for each of [1] and [2].  
(e.g. HSN-2/Q)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
■ Input 10 – 50 mA DC / Output 1 – 5 V DC  
Equivalent input impedance: Approx. 100 Ω with 50 mA  
input  
[1] INPUT / OUTPUT  
Single-channel  
Operational range: 7 – 55 mA DC  
(Accuracy is assured within 8 – 55 mA)  
Load resistance: ≥ 50 kΩ  
1: 4 – 20 mA DC / 1 – 5 V DC  
1H6: 10 – 50 mA DC / 1 – 5 V DC  
1AA: 4 – 20 mA DC / 4 – 20 mA DC  
1HA: 10 – 50 mA DC / 4 – 20 mA DC  
Dual-channel  
■ Input 4 – 20 mA DC / Output 4 – 20 mA DC  
Equivalent input impedance: 230 Ω plus load resistance with  
20 mA input  
2: 4 – 20 mA DC / 1 – 5 V DC  
2H6: 10 – 50 mA DC / 1 – 5 V DC  
2AA: 4 – 20 mA DC / 4 – 20 mA DC  
2HA: 10 – 50 mA DC / 4 – 20 mA DC  
Operational range: 3 – 22 mA DC  
(Accuracy is assured within 4 – 22 mA)  
Load resistance: 50 – 350 Ω (min. 50 Ω required for  
adequate operation)  
■ Input 10 – 50 mA DC / Output 4 – 20 mA DC  
Equivalent input impedance: 90 Ω + [load resistance×0.16]  
HSN SPECIFICATIONS  
ES-3419 Rev.8 Page 1/3  
http://www.m-system.co.jp/  
MODEL: HSN  
with 50 mA input  
Voltage output: ±0.015 %/°C (±0.008 %/°F)  
Operational range: 7 – 55 mA DC  
(Accuracy is assured within 8 – 55 mA)  
Load resistance: 50 – 600 Ω (min. 50 Ω required for  
adequate operation)  
Current output: ±0.02 %/°C (±0.01 %/°F)  
Response time  
Voltage output: ≤ 0.5 sec. (0 – 90 %)  
Current output: Approx. 15 msec. (0 – 90 %)  
Load effect (current output)  
•INPUT 4 – 20 mA DC / OUTPUT 1 – 5 V DC  
4 – 20 mA input: 0.015 %/Ω (50 – 150 Ω)  
0.003 %/Ω (150 – 350 Ω)  
5.0  
approx. 5.0  
10 – 50 mA input: 0.015 %/Ω (50 – 100 Ω)  
0.003 %/Ω (100 – 600 Ω)  
4.0  
approx.  
3.7  
(The unit is calibrated with 250 Ω load at the factory.)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength:  
3.0  
4
12  
20  
INPUT CURRENT [mA]  
500 V AC @1 minute (input to output)  
1500 V AC @1 minute (between channels)  
1500 V AC @1 minute (input or output to ground)  
•INPUT 10 – 50 mA DC / OUTPUT 1 – 5 V DC  
5.0  
approx. 5.0  
4.0  
approx.  
3.7  
3.0  
10  
30  
50  
INPUT CURRENT [mA]  
•INPUT 4 – 20mA DC / OUTPUT 4 – 20 mA DC  
12.0  
approx. 11.6  
(load 350)  
10.0  
8.0  
approx. 9.6  
(load 250)  
6.0  
approx. 5.0  
approx. 4.6  
approx. 3.8  
approx. 5.6  
(load 50)  
3.0  
4
12  
20  
INPUT CURRENT [mA]  
•INPUT 10 – 50 mA DC / OUTPUT 4 – 20 mA DC  
10.0  
approx. 9.3  
(load 600)  
8.0  
approx. 6.5  
(load 250)  
6.0  
approx. 4.7  
approx. 4.1  
approx. 3.8  
3.0  
approx. 4.9  
(load 50)  
10  
30  
50  
INPUT CURRENT [mA]  
INSTALLATION  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail; Standard Rack Mounting  
Frame BX-16H available  
Weight: 200 g (0.44 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.1 %  
Temp. coefficient  
HSN SPECIFICATIONS  
ES-3419 Rev.8 Page 2/3  
http://www.m-system.co.jp/  
MODEL: HSN  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
7.8 (.31)  
CLAMP  
(top & bottom)  
1
2
15  
(.59)  
DIN RAIL  
35mm wide  
3
4
2–4.5 (.18)  
HOLE  
15 (.59) deep  
5
6
8–M3.5  
SCREW  
7
8
107 (4.21)  
137 (5.39)  
26 (1.02)  
26 (1.02)  
[3.3 (.13)]  
•When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Note: For the single-channel model, the terminals 3 – 4 and 7 – 8 are used.  
VOLTAGE OUTPUT  
Z
S
Buffer  
Amplifier  
+
+
1
2
3
4
Chopper  
Inverter  
5
6
7
8
+
+
Ch 1. INPUT  
Ch 2. INPUT  
Ch 1. OUTPUT  
Ch 2. OUTPUT  
Rectifier  
Channel 2  
Base Socket  
CURRENT OUTPUT  
S
Isolation  
Inverter  
Load Effect  
Compensation  
+
1
5
6
+
Ch 1. OUTPUT  
Ch 2. OUTPUT  
Z
Ch 1. INPUT  
Ch 2. INPUT  
+
2
3
4
7
8
+
Channel 2  
Base Socket  
Specifications are subject to change without notice.  
HSN SPECIFICATIONS  
ES-3419 Rev.8 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

HSN-2HA

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HSN-2HA/Q

Space-saving Plug-in Signal Conditioners H-UNIT
MSYSTEM

HSN-3000

Nuclear Event Detector
MAXWELL

HSN-3000F

Nuclear Event Detector
MAXWELL

HSN-3000L

Nuclear Event Detector
MAXWELL

HSN-500

Nuclear Event Detector
MAXWELL

HSN-500F

Nuclear Event Detector
MAXWELL

HSN-500L

Nuclear Event Detector
MAXWELL

HSN100

Fixed Resistor, Wire Wound, 1350V, Chassis Mount, ROHS COMPLIANT
OHMITE

HSN1000

Nuclear Event Detector
MAXWELL

HSN1000F

Nuclear Event Detector
MAXWELL

HSN1000L

Nuclear Event Detector
MAXWELL