JAPD2-5N-P 概述
Plug-in Signal Conditioners M-UNIT
JAPD2-5N-P 数据手册
通过下载JAPD2-5N-P数据手册来全面了解它。这个PDF文档包含了所有必要的细节,如产品概述、功能特性、引脚定义、引脚排列图等信息。
PDF下载MODEL: JAPD2
Plug-in Signal Conditioners M-UNIT
[1] INPUT
Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
A1: 4 – 20 mA DC (Input resistance 50 Ω)
B: 2 – 10 mA DC (Input resistance 500 Ω)
C: 1 – 5 mA DC (Input resistance 1000 Ω)
D: 0 – 20 mA DC (Input resistance 50 Ω)
E: 0 – 16 mA DC (Input resistance 62.5 Ω)
F: 0 – 10 mA DC (Input resistance 100 Ω)
G: 0 – 1 mA DC (Input resistance 1000 Ω)
H: 10 – 50 mA DC (Input resistance 100 Ω)
Z: Specify current (See INPUT SPECIFICATIONS)
Voltage
DC/FREQUENCY CONVERTER
(field-programmable)
Functions & Features
• Providing a pulse rate output in proportion to DC input
signal
• Parameters are field-programmable via hand-held
programmer PU-2x
• Isolation up to 2000 V AC
• High-density mounting
Typical Applications
1: 0 – 10 mV DC (Input resistance 10 kΩ min.)
2: 0 – 100 mV DC (Input resistance 100 kΩ min.)
3: 0 – 1 V DC (Input resistance 1 MΩ min.)
4: 0 – 10 V DC (Input resistance 1 MΩ min.)
5: 0 – 5 V DC (Input resistance 1 MΩ min.)
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
4W: -10 – +10 V DC (Input resistance 1 MΩ min.)
0: Specify voltage (See INPUT SPECIFICATIONS)
• Monitoring & control of power supply system
• Quick countermeasure applicable even in failure or in
sudden voltage change
50
(1.97)
80
(3.15)
[2] OUTPUT
A: Open collector
M: 5 V pulse
127
(5)
mm (inch)
N: 12 V pulse
P: 24 V pulse
J: RS-422 line driver pulse
R: AC/DC switch
MODEL: JAPD2–[1][2]–[3][4]
ORDERING INFORMATION
• Code number: JAPD2–[1][2]–[3][4]
Specify a code from below for each of[1] through [4].
(e.g. JAPD2-6A-S/Q)
[3] POWER INPUT
AC Power
M2: 100 – 240 V AC
DC Power
• Special input range (For codes Z & 0)
• Use Ordering Information Sheet (No. ESU-1571).
Default setting (table below) will be used if not otherwise
specified.
S: 12 V DC
R: 24 V DC
P: 110 V DC
• Specify the specification for option code /Q
(e.g. /C01/S01)
[4] OPTIONS
blank: none
ITEM
DEFAULT
/Q: With options (specify the specification)
Output zero frequency
Output span frequency
0 kHz
1 kHz
(10 Hz for output code R)
100.00%
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Alarm setpoint
Alarm hysteresis
Alarm mode
1.00%
No alarm
/C02: Polyurethane coating
Power ON-delay time
3.0 sec.
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
JAPD2 SPECIFICATIONS
ES-1571 Rev.6 Page 1/4
http://www.m-system.co.jp/
MODEL: JAPD2
RNG4 10 Hz: 0 – 20 Hz
RNG5 1 Hz: 0 – 2 Hz
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
RNG6 100 mHz: 0 – 200 mHz
Min. span: 10 % of available frequency range
Duty ratio: 50 %
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
■ Open Collector: 50 V DC @50 mA (resistive load)
Saturation voltage: 0.6 V DC
■ Voltage Pulse
H level: Rating 5, 12 or 24 V ±10 %
L level: ≤ 0.5 V
GENERAL SPECIFICATIONS
Construction: Plug-in
Load resistance: ≥ 1 kΩ (5 V), ≥ 2.4 kΩ (12 V), ≥ 4.8 kΩ (24
V)
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
■ Noncontact AC/DC Switch: 120 V AC or 120 V DC @200
mA (resistive load)
ON resistance: 3 Ω max.
Housing material: Flame-resistant resin (black)
Isolation: Input to alarm output to output to power
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
Alarm output: Turns on when the input goes above (high) or
below (low) setpoint
Rise time: 5 msec.
Sink time: 3 msec.
■ RS-422 Line Driver Pulse
Transmitter: Conforms to RS-422
■ Relay Contact:
100 V AC @ 1 A (cos ø = 1)
Alarm setpoint: -5 – +105 %
120 V AC @ 1 A (cos ø = 1)
Alarm deadband (hysteresis): 0 – 20 %
Output monitor LED: Red LED turns on when the output is
ON or high.
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 380 V AC or 125 V DC
Maximum switching power: 120 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Power ON delay time: 2.0 to 1000.0 sec.
Software programming: Programming Unit (model: PU-2x);
(Refer to the users manual of JXCON for the adjustments
configurable with JXCON)
Mechanical life: 5 x 10 cycles (300 cycle/minute)
7
• Output frequency (zero and span)
• Alarm
INSTALLATION
Power input
• Power ON delay time
•AC: Operational voltage range 85 – 264 V, 47 - 66 Hz;
Approx. 3.2 VA at 100 V
• Others
Approx. 5.1 VA at 200 V
INPUT SPECIFICATIONS
■ DC Current:
Approx. 6.9 VA at 264 V
•DC: Operational voltage range: rating ±10 %, or 85 – 150 V
for 110 V rating (ripple 10 % p-p max.)
Approx. 2.5 W (100 mA at 24 V)
Shunt resistor attached to the input terminals (0.5 W)
Specify input resistance value for code Z.
■ DC Voltage: -300 – +300 V DC
Minimum span: 10 mV
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Offset: Max. 1.5 times span
Input resistance
Weight: 280 g (0.62 lb)
Span 10 – 100 mV : ≥ 10 kΩ
Span 0.1 – 1 V : ≥ 100 kΩ
Span ≥ 1 V : ≥ 1 MΩ
OUTPUT SPECIFICATIONS
Frequency range: 100 mHz to 10 kHz (RNG1 to RNG6)
[ Range name : Available frequency ]
RNG1 10 kHz: 0 – 20 kHz
RNG2 1 kHz: 0 – 2 kHz
RNG3 100 Hz: 0 – 200 Hz
JAPD2 SPECIFICATIONS
ES-1571 Rev.6 Page 2/4
http://www.m-system.co.jp/
MODEL: JAPD2
PERFORMANCE in percentage of span
Accuracy
Output 10 kHz range: ±0.3 %
Output ≤ 1 kHz range: ±0.1 %
Alarm setpoint accuracy: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: 0.3 sec. + (one cycle at 100 % output)
Time required from a step input (0 – 100 %) to the first
pulse output.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input to alarm
output to output to power to ground)
EXTERNAL VIEW
DO NOT change the Output Voltage Adjuster.
Modular Jack
Span Adj.
Zero Adj.
Monitor LED (no function)
Output Monitor LED
Output Voltage Adj.*
*only for voltage pulse output
EXTERNAL DIMENSIONS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
6
5
4
3
2–4.5 (.18) dia.
MTG HOLE
15 (.59) deep
7
8
1
2
8–M3.5
SCREW
50 (1.97)
107 (4.21)
127 (5)
40 (1.57)
50 (1.97)
[3.3 (.13)]
• When mounting, no extra space is needed between units.
JAPD2 SPECIFICATIONS
ES-1571 Rev.6 Page 3/4
http://www.m-system.co.jp/
MODEL: JAPD2
TERMINAL ASSIGNMENTS unit: mm (inch)
INPUT RESISTOR
(model: REM)
6
5
4
3
7
8
1
2
Input shunt resistor attached
for current input.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
OUT.
MON.
Z
S
Isolation
Volt. / Freq.
Converter
Output
Driver
+
–
3
4
5
6
1
2
7
8
+
Computation
*
INPUT
R
OUTPUT
–
+
–
U(+)
POWER
V(–)
Ry
ALARM OUTPUT
PU-2x
MODULAR JACK
SERIAL TRANSMISSION LINE
Base Socket
* Input shunt resistor attached for current input.
Output Connection Examples
■ Open Collector
■ RS-422 Line Driver Pulse
■ AC/DC Switch
• AC Powered
Relay or
Counter Coil
1
+
–
+
–
+
–
+
–
+
–
1
2
1
2
Varistor or Spark
Quenching Circuit
LOAD
2
U
• DC Powered
■ Voltage Pulse
Relay or
Counter Coil
1
+
–
+
–
1
2
Spark Quenching
Diode
LOAD
2
Specifications are subject to change without notice.
JAPD2 SPECIFICATIONS
ES-1571 Rev.6 Page 4/4
http://www.m-system.co.jp/
JAPD2-5N-P 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
JAPD2-5N-P/Q | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
JAPD2-5N-R | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
JAPD2-5N-R/Q | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
JAPD2-5N-S | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
JAPD2-5N-S/Q | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
JAPD2-5P-M2 | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
JAPD2-5P-M2/Q | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
JAPD2-5P-P | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
JAPD2-5P-P/Q | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 | |
JAPD2-5P-R | MSYSTEM | Plug-in Signal Conditioners M-UNIT | 获取价格 |
JAPD2-5N-P 相关文章
- 2024-09-20
- 5
- 2024-09-20
- 8
- 2024-09-20
- 8
- 2024-09-20
- 6