JC-CU-3-11-R5 [MSYSTEM]
HUB MODULE;型号: | JC-CU-3-11-R5 |
厂家: | M-SYSTEM |
描述: | HUB MODULE |
文件: | 总9页 (文件大小:343K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: JC-CU
Remote I/O JC Series
[4] OPTIONS
Other Options
blank: none
HUB MODULE
(CUnet use)
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
EX-FACTORY SETTING
53
(2.09)
/SET: Preset according to the Ordering Information Sheet
(No. ESU-9042)
FUNCTIONS & FEATURES
115
(4.52)
The HUB Module for CUnet (model: JC-CU) extends total
length of network cable and branch cable of CUnet. Total
max. length is 900 m when transfer rate is 3 Mbps. In order
to connect the JC-CU, the unit configuring CUnet must
support HUB module.
73
(2.87)
mm (inch)
GENERAL SPECIFICATIONS
Number of port:
MODEL: JC–CU-[1]-1[2]-[3][4]
JC-CU-3: Trunk 1 port, feeder 2 port
JC-CU-7: Trunk 1 port, feeder 6 port
Max. number of inserted HUBs: 2
(Depending on specification of CUnet I/O unit)
Connectable devices: The products conforming to CUnet
Connection
ORDERING INFORMATION
• Code number: JC-CU-[1]-1[2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. JC-CU-7-12-R/Q)
• Specify the specification for option code /Q
(e.g. /SET)
Network: RJ-45 Modular Jack
Power input: Separable tension clamp terminal
Power on LED: PWR (green) turns on while the power is
supplied.
[1] I/O TYPE
3: 3 port (trunk 1 port, feeder 2 port)
7: 7 port (trunk 1 port, feeder 6 port)
CUnet COMMUNICATION
Communication mode: half-duplex
Network cable
TERMINAL BLOCK
1: Tension clamp terminal block for power supply
• Shield cable
ZHY262PS (Shinko Seisen Industry Co., Ltd.)
ZHT262PS (Shinko Seisen Industry Co., Ltd.)
• Dual-shield cable
RJ-45 Modular jack for communication
[2] COMMUNICATION CONNECTOR PIN ASSIGNMENT
1: 3, 4 pair wiring
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transmission distance / Transfer rate:
Refer to the table below (Selectable with
DIP switch. Factory default: 12 Mbps)
Terminating resistor:
2: 4, 5 pair wiring
(Ethernet LAN cable pin assignment)
Trunk built-in (Selectable with DIP switch. Factory default:
disable)
[3] POWER INPUT
DC Power
Feeder built-in
R: 24 V DC
Status indicator LEDs: ERR, LNK
(Refer to the instruction manual for details)
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R5: 16 - 32 V DC
(Operational voltage range 15 - 33 V DC, ripple 10 %p-p max.)
JC-CU SPECIFICATIONS
ES-9042 Rev.2 Page 1/9
https://www.m-system.co.jp/
MODEL: JC-CU
Number of inserted HUBs
Transfer rate
12Mbps
6Mbps
0
1
2
100m
200m
300m
200m
400m
600m
300m
800m
900m
3Mbps
INSTALLATION
Rated current for power supply connector: 8A
Power consumtpion:
JC-CU-3: Approx. 0.9 W
JC-CU-7: Approx. 1.2 W
Operating temperature: -10 to +55°C
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight
JC-CU-3: 150 g (0.33 lb)
JC-CU-7: 160 g (0.35 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
JC-CU-3 (CU0A or CU0B to CU1 or CU2 or FE to power)
JC-CU-7 (CU0A or CU0B to CU1 or CU2 or CU3 or CU4 or CU5
or CU6 or FE to power)
Dielectric strength: 1500 V AC @ 1 minute
JC-CU-3 (CU0A or CU0B to CU1 or CU2 or FE to power)
JC-CU-7 (CU0A or CU0B to CU1 or CU2 or CU3 or CU4 or CU5
or CU6 or FE to power)
STANDARDS & APPROVALS
Refer to the manuals to comply with the standards.
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
JC-CU SPECIFICATIONS
ES-9042 Rev.2 Page 2/9
https://www.m-system.co.jp/
MODEL: JC-CU
EXTERNAL VIEW
■ I/O TYPE : 3 3port
• SIDE VIEW
• FRONT VIEW
Status Indicator LED
PWR
ERR
LNK0
CU0A
PWR LED
ERR LED
RJ-45 Modular Jack
for Trunk
SW1
ON
➞
CU0B
RJ-45 Modular Jack
for Feeder
CU1
LNK1
Operating Mode Setting
)
Status Indicator LED
(
DIP SW SW1
CU2
LNK2
SW1
1
2
3
4
Transfer Rate
Terminating
Resistor
Power Supply
Connector
ON ➞
PWR+
PWR
-
FE
■ I/O TYPE : 7 7port
• SIDE VIEW
• FRONT VIEW
Status Indicator LED
PWR
ERR
LNK0
CU0A
PWR LED
ERR LED
RJ-45 Modular Jack
for Trunk
SW1
Status Indicator LED
Status Indicator LED
ON
➞
CU0B
CU1
LNK1
Operating Mode Setting
)
LNK5
CU5
RJ-45 Modular Jack
for Feeder
(
DIP SW SW1
RJ-45 Modular Jack
for Feeder
CU2
LNK2
SW1
LNK6
CU6
1
2
3
4
Transfer Rate
CU3
Power Supply
Connector
Terminating
Resistor
LNK3
Status Indicator LED
ON ➞
PWR+
CU4
PWR-
LNK4
FE
JC-CU SPECIFICATIONS
ES-9042 Rev.2 Page 3/9
https://www.m-system.co.jp/
MODEL: JC-CU
CONNECTION DIAGRAMS
■ POWER SUPPLY
Cable connector: TFMC1,5 / 5–STF–3,5
(Phoenix Contact) (included in the package)
Applicable wire size: 0.2 − 1.5 mm2; stripped length 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm2 (Phoenix Contact)
• AI0,34−10TQ 0.34 mm2 (Phoenix Contact)
• AI0,5−10WH 0.5 mm2 (Phoenix Contact)
• AI0,75−10GY 0.75 mm2 (Phoenix Contact)
• A1−10 1.0 mm2 (Phoenix Contact)
• A1,5−10 1.5 mm2 (Phoenix Contact)
1. PWR + Power Supply
2. PWR − Power Supply
1ꢀ
2
3ꢀ
3. FE
Functional earth
■ NETWORK
Reccommended cable connector: TM21P–88P (Hirose Electric)
(not included in the package)
• COMMUNICATION CONNECTOR PIN ASSIGNMENT CODE: 1
1
2
3
4
5
6
7
8
Trunk (CU0A, CU0B)
Feeder (CU1, CU2, CU3, CU4, CU5, CU6)
1. NC
2. NC
3. TR+
4. TR–
5. NC
6. NC
7. NC
8. SLD
Unused
Unused
Network (+)
Network (–)
Unused
1. NC
2. NC
3. TR+
4. TR–
5. NC
6. NC
7. NC
8. SLD
Unused
Unused
Network (+)
Network (–)
Unused
Unused
Unused
Shield
Unused
Unused
Shield
• COMMUNICATION CONNECTOR PIN ASSIGNMENT CODE: 2
1
2
3
4
5
6
7
8
Trunk (CU0A, CU0B)
Feeder (CU1, CU2, CU3, CU4, CU5, CU6)
1. NC
2. NC
3. NC
4. TR–
5. TR+
6. NC
7. NC
8. SLD
Unused
Unused
Unused
Network (–)
Network (+)
Unused
1. NC
2. NC
3. NC
4. TR–
5. TR+
6. NC
7. NC
8. SLD
Unused
Unused
Unused
Network (–)
Network (+)
Unused
Unused
Shield
Unused
Shield
JC-CU SPECIFICATIONS
ES-9042 Rev.2 Page 4/9
https://www.m-system.co.jp/
MODEL: JC-CU
■ CONNECTION WITH OTHERS
CUnet I/O Module
CUnet I/O Module
HUB Module
TR+
TR−
TR+
TR−
TR+
TR−
SLD
Terminating
Resistor
Terminating
Resistor
SHIELD
SLD
Trunk CU0A/CU0B
CUnet I/O Module
TR+
TR−
TR+
TR−
SLD
Terminating
Resistor
Terminating
Resistor
SLD
Feeder CU1 – CU6
Note: Be sure to turn ON the switch of the terminating resistor located at both ends of the modules.
DIMENSIONS unit: mm (inch)
50(1.97)
[3(.12)]
73(2.87)
55(2.17)
[4(.16)]
2–4.3 (.17) dia Mtg Hole
4 (.16) deep
DIN RAIL
(35 mm wide)
JC-CU SPECIFICATIONS
ES-9042 Rev.2 Page 5/9
https://www.m-system.co.jp/
MODEL: JC-CU
MOUNTING REQUIREMENTS unit: mm [inch]
JC-CU SPECIFICATIONS
ES-9042 Rev.2 Page 6/9
https://www.m-system.co.jp/
MODEL: JC-CU
SCHEMATIC CIRCUITRY
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.
■ JC−CU−3−11
Isolation
Isolation
NC
NC
NC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Comm.
Circuit
Comm.
Circuit
NC
TR+
TR−
NC
TR+
TR−
NC
CU0A
COMMUNICATION
CU1
NC
NC
NC
NC
Control
Circuit
SLD
SLD
Isolation
NC
NC
NC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Comm.
Circuit
NC
TR+
TR−
NC
TR+
TR−
NC
CU0B
COMMUNICATION
CU2
NC
NC
NC
NC
SLD
SLD
+
PWR +
1
2
3
Power
Circuit
POWER (IN)
PWR
FE
−
−
PWR +
1
2
3
POWER (OUT)
PWR
FE
−
■ JC−CU−7−11
Isolation
Isolation
NC
NC
NC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Comm.
Circuit
Comm.
Circuit
NC
TR+
TR−
NC
TR+
TR−
NC
CU0A
COMMUNICATION
CU1
NC
NC
NC
NC
Control
Circuit
SLD
SLD
NC
NC
1
2
3
4
5
6
7
8
Isolation
NC
1
2
3
4
5
6
7
8
Comm.
Circuit
TR+
TR−
NC
NC
TR+
TR−
NC
CU0B
COMMUNICATION
CU6
NC
NC
NC
SLD
NC
SLD
+
−
PWR +
1
2
3
Power
Circuit
POWER (IN)
PWR
FE
−
PWR +
1
2
3
POWER (OUT)
PWR
FE
−
JC-CU SPECIFICATIONS
ES-9042 Rev.2 Page 7/9
https://www.m-system.co.jp/
MODEL: JC-CU
■ JC−CU−3−12
Isolation
Isolation
NC
NC
NC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Comm.
Circuit
Comm.
Circuit
NC
NC
NC
CU0A
TR−
TR+
NC
TR−
TR+
NC
CU1
COMMUNICATION
NC
NC
Control
Circuit
SLD
SLD
Isolation
NC
NC
NC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Comm.
Circuit
NC
NC
NC
CU0B
COMMUNICATION
TR−
TR+
NC
TR−
TR+
NC
CU2
NC
NC
SLD
SLD
+
PWR +
1
2
3
Power
Circuit
POWER (IN)
PWR
FE
−
−
PWR +
1
2
3
POWER (OUT)
PWR
FE
−
■ JC−CU−7−12
Isolation
Isolation
NC
NC
NC
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Comm.
Circuit
Comm.
Circuit
NC
NC
NC
CU0A
COMMUNICATION
TR−
TR+
NC
TR−
TR+
NC
CU1
NC
NC
Control
Circuit
SLD
SLD
NC
NC
1
2
3
4
5
6
7
8
Isolation
NC
1
2
3
4
5
6
7
8
Comm.
Circuit
NC
NC
TR−
TR+
NC
NC
CU0B
COMMUNICATION
TR−
TR+
NC
CU6
NC
SLD
NC
SLD
+
−
PWR+
1
2
3
Power
Circuit
POWER (IN)
PWR−
FE
PWR+
1
2
3
POWER (OUT)
PWR−
FE
JC-CU SPECIFICATIONS
ES-9042 Rev.2 Page 8/9
https://www.m-system.co.jp/
MODEL: JC-CU
SYSTEM CONFIGURATION EXAMPLES
System configurration example of Number of inserted HUBs: 2 is shown below.
The number of inserted HUBs is determined by the route, where max. number of HUB is gone through, out of all route.
When HUB module is used, the frame option must be set in any CUnet I/O module connected to the network. Refer to the
instruction manual of your CUnet I/O module for the detailed settings.
HUB Module
(Model: JC−CU)
CUnet
I/O Module
CUnet
I/O Module
Rt
HUB Module
(Model: JC−CU)
CUnet
I/O Module
Rt
Rt
Rt
Rt
Rt
Rt
Rt : Terminating Resistor
Note 1) Max. transmission distance between CUnet I/O module and HUB module, HUB module and HUB module is as follows.
100 m at 12 Mbps, 200 m at 6 Mbps and 300 m at 3 Mbps.
Note 2) Be sure to connect CU0A/CU0B to the host side.
Note 3) The terminating resistor must be enabled for the modules at both end of the communication line. The terminating resistor is
incorporated in the feeder side port of the HUB module.
Specifications are subject to change without notice.
JC-CU SPECIFICATIONS
ES-9042 Rev.2 Page 9/9