MODEL: JTY2  
Factory Setting  
Plug-in Signal Conditioners M-UNIT  
Input type  
Pulse amplitude range  
Pulse amplitude  
Voltage pulse  
1 – 5V p-p  
5V p-p (DC offset 2.5V)  
PULSE DURATION RECEIVER  
(field-programmable; built-in excitation)  
Functions & Features  
Pulse logic  
Detecting level  
Input zero duty ratio  
Non-inverted*1  
Matching the amplitude  
0% *3  
2
*
• Converts the pulse duty ratio into a standard process  
signal  
Input span duty ratio  
No input detecting time  
Moving average  
100% *3  
1 second  
4 cycles  
• Built-in excitation  
Moving average Hi/Lo discarded  
Alarm mode  
Alarm setpoint  
Alarm deadband  
Alarm delay time at start up  
Linearization  
1 each  
• Field-selectable input type and range: Dry contact,  
voltage pulse or two-wire current pulse  
• Isolation up to 2000 V AC  
High alarm  
100%  
1%  
3 seconds  
Without  
• High-density mounting  
*1. Valid duty ratio  
Non-inverted: Hi level for voltage/current pulse  
OFF for open collector  
Typical Applications  
• Transmission or telemetering  
Inverted:  
Lo level for voltage/current pulse  
ON for open collector  
• Converting the pulse duty ratio into an analog momentary  
values  
*2. Detecting voltage in the internal circuit  
*3. Applied to the duty ratio of the selected pulse logic  
50  
(1.97)  
INPUT – Field-selectable  
Open collector  
Voltage pulse  
80  
(3.15)  
Two-wire current pulse  
Described accuracy may not be assured when the input  
waveform is not clear.  
136  
(5.35)  
mm (inch)  
[1] EXCITATION  
1: 5 V DC @ 120 mA  
4: 12 V DC @ 60 mA  
7: 24 V DC @ 25 mA  
MODEL: JTY2–[1][2]–[3][4]  
ORDERING INFORMATION  
• Code number: JTY2-[1][2]-[3][4]  
[2] OUTPUT  
Current  
Specify a code from below for each of [1] through [4].  
(e.g. JTY2-76-K/Q)  
A: 4 – 20 mA DC (Load resistance 750 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)  
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)  
D: 0 – 20 mA DC (Load resistance 750 Ω max.)  
E: 0 – 16 mA DC (Load resistance 900 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)  
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
• Special output range (For codes Z & 0)  
• Use Ordering Information Sheet (No. ESU-1573). Factory  
setting (table below) will be used if not otherwise specified.  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 100 Ω min.)  
4: 0 – 10 V DC (Load resistance 1000 Ω min.)  
5: 0 – 5 V DC (Load resistance 500 Ω min.)  
6: 1 – 5 V DC (Load resistance 500 Ω min.)  
4W: -10 – +10 V DC (Load resistance 2000 Ω min.)  
5W: -5 – +5 V DC (Load resistance 1000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
JTY2 SPECIFICATIONS  
ES-1573 Rev.8 Page 1/5  
http://www.m-system.co.jp/  
MODEL: JTY2  
• No input detecting time  
• Moving average  
• Alarm setpoint  
• Output fine adjustment  
• Linearization  
[3] POWER INPUT  
AC Power  
K: 85 – 132 V AC  
DC Power  
S: 12 V DC  
• Others  
R: 24 V DC  
Adjustments: With DIP and Rotary switches.  
• Pulse amplitude  
V: 48 V DC  
P: 110 V DC  
• Input type  
(Refer to the instruction manual for details)  
Modular jack: Connecting the PU-2x  
Input pulse sensing: DC coupled  
[4] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
No input detecting: The output forced to 0 % or 100 % when  
no input is provided for a preset time period.  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
INPUT SPECIFICATIONS  
Excitation: Shortcircuit protection; approx. 440 mA (max.) at  
shortcircuit  
/C02: Polyurethane coating  
/C03: Rubber coating  
Frequency: 0.1 – 1000 Hz  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
(max. 500 Hz for open collector input)  
Duty ratio range: 1 – 99 % (including 0 and 100 %)  
Minimum span: 20 % (span duty ratio – zero duty ratio)  
Open Collector  
RELATED PRODUCTS  
• Programming Unit (model: PU-2x)  
Input requirements:  
(Excitation: Sensing)  
• PC configurator software (model: JXCON)  
Downloadable at M-System’s web site.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
5 V: Approx. 4 V / 1.0 mA  
12 V: Approx. 9 V / 2.3 mA  
24 V: Approx. 16 V / 4.7 mA  
ON resistance: ≤ 200 Ω  
OFF resistance: ≥ 200 kΩ  
Detecting level: 0 – 5 V  
(Readjustment is required to match the duty ratio after the  
sensor excitation, the pulse amplitude have been changed.)  
Detecting pulse edge: OFF (input monitor LED ON) to ON  
(LED OFF) and ON to OFF  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
Voltage Pulse  
Waveform: Square  
Housing material: Flame-resistant resin (black)  
Isolation: Input to DC output to alarm output to power  
Overrange output: Approx. -15 to +115 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
Alarm mode: High or Low  
Input impedance: 10 kΩ min.  
Pulse amplitude: 0.1 – 100 Vp-p  
Max. voltage between input terminals: 50 V  
Detecting level: 0 – 5  
(Readjustment is required to match the duty ratio after the  
pulse amplitude have been changed.)  
Detecting pulse state: A pulse rise detected when the input  
voltage goes above the detecting level (input monitor LED  
ON); a pulse sink detected when it goes below the level  
(LED OFF).  
Alarm setpoint: -15 – +115 %  
Alarm deadband: 0 – 20 %  
Linearization: Max. 16 points  
Input monitor LED: Red LED blinks according to the input.  
Excitation adjustment: 5 – 24 V DC  
Software programming: Programming Unit (model: PU-2x);  
(Refer to the users manual of JXCON for the adjustments  
configurable with JXCON)  
Two-wire Current Pulse  
Waveform: Square  
Input resistance: Receiving resistor 100 Ω  
Input range: 0 – 25 mA  
• Input zero and span duty ratio  
Minimum pulse amplitude: 10 mA  
JTY2 SPECIFICATIONS  
ES-1573 Rev.8 Page 2/5  
http://www.m-system.co.jp/  
MODEL: JTY2  
Detecting level: 0 – 5 V  
Operating temperature: -5 to +60°C (23 to 140°F)  
(Readjustment is required to match the duty ratio after the  
pulse amplitude have been changed.)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Detecting pulse state: The input resistor (100 Ω) converts  
the current signal into 0 – 2.5 V. A pulse rise detected when  
the voltage goes above the detecting level (input monitor  
LED ON); a pulse sink detected when it goes below the level  
(LED OFF).  
Weight: 350 g (0.77 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.25 %  
Alarm setpoint accuracy: ±0.1 %  
Voltage pulse waveform  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: 0.5 sec. + 1 pulse cycle (0 – 90 %)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength:  
Volts  
50V  
max.  
Amplitude  
DC Offset  
Vin p-p  
2000 V AC @ 1 minute (input to output to power)  
1500 V AC @ 1 minute (input or output or power to alarm  
output)  
t
Two-wire current pulse waveform  
2000 V AC @ 1 minute (circuit to ground)  
25mA  
Amps.  
max.  
Amplitude  
DC Offset  
mA p-p  
t
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 15 V max.  
DC Voltage: -10 – +12 V DC  
Minimum span: 5 mV  
Offset: Max. 1.5 times span  
Load resistance: Output drive 10 mA max.; 5 mA for  
negative voltage output; at ≥ 0.5 V  
Alarm Output: Relay contact  
Rated load: 125 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 0.5 A (resistive load)  
Maximum switching voltage: 250 V AC or 125 V DC  
Maximum switching power: 62.5 VA or 60 W  
Minimum load: 10 mV DC @ 1 mA  
Mechanical life: 5 × 10 cycles (300 cycles/minute)  
7
For maximum relay life with inductive loads, external  
protection is recommended.  
INSTALLATION  
Power input  
AC: Operational voltage range 85 – 132 V,  
47 – 66 Hz, approx. 6 VA  
DC: Operational voltage range: Rating ±10 %, or 85 – 150  
V for 110 V rating; ripple 10 %p-p max.; Approx. 3.3 W (130  
mA at 24 V)  
JTY2 SPECIFICATIONS  
ES-1573 Rev.8 Page 3/5  
http://www.m-system.co.jp/  
MODEL: JTY2  
EXTERNAL VIEW  
Modular Jack  
Input Monitor LED PL1  
Detecting Level Adj.  
ON  
Detecting Level Adj. Pin  
Pulse Amplitude Selector  
1
2
3
4
5
6
Zero Adj.  
Span Adj.  
Input Type Selector  
Sensor Excitation Adj.  
Refer to the instruction manual for detailed procedures.  
INPUT PULSE LOGIC  
INPUT TYPE  
PULSE LOGIC  
WAVEFORM  
H
Voltage pulse  
Two-wire current pulse  
Non-inverted  
L
ON current (H)  
OFF current (L)  
H
Inverted  
Non-inverted  
Inverted  
L
OFF  
ON  
Open collector  
OFF  
ON  
The pulse logic is applied to the bold lined section of the waveform.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
8
7
6
5
4
2–  
4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
9
3
2
10 11  
1
11  
M3.5  
SCREW  
50 (1.97)  
107 (4.21)  
136 (5.35)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
JTY2 SPECIFICATIONS  
ES-1573 Rev.8 Page 4/5  
http://www.m-system.co.jp/  
MODEL: JTY2  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
10  
Ry  
ALARM OUTPUT  
9
DETECT. LEVEL  
INPUT  
MON.  
INPUT TYPE  
11  
1
Z
S
Isolation  
Waveform  
Shaper  
Digital  
Computation  
Output  
Driver  
+
+
5
6
4
3
INPUT  
OUTPUT  
POWER  
2
SENSOR EXCITATION  
+
Excitation  
Supply  
U(+)  
V(–)  
7
VS  
8
PU-2x  
MODULAR JACK  
SERIAL TRANSMISSION LINE  
Base Socket  
Input Connection Examples  
Dry Contact  
2-Wire Current Pulse  
•Built-in Excitation  
100Ω  
+
+
5
6
4
+
5
6
4
2-WIRE  
PICK-UP  
Vsns  
Vsns  
PWR  
5kΩ  
Voltage Pulse  
•External DC Supply  
100Ω  
+
5
6
4
+
5
6
4
2-WIRE  
PICK-UP  
DC SUPPLY  
PWR  
+
Vsns  
Vsns  
+
Specifications are subject to change without notice.  
JTY2 SPECIFICATIONS  
ES-1573 Rev.8 Page 5/5  
http://www.m-system.co.jp/  

JTY2-43-P/Q 相关器件

型号 制造商 描述 价格 文档
JTY2-43-R MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
JTY2-43-R/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
JTY2-43-S MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
JTY2-43-S/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
JTY2-43-V MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
JTY2-43-V/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
JTY2-44-K MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
JTY2-44-K/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
JTY2-44-P MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
JTY2-44-P/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格

JTY2-43-P/Q 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8