MODEL: KEPF  
Plug-in Signal Conditioners K-UNIT  
[3] OUTPUT SIGNAL POLARITY  
P: Negative in lag, positive in lead  
M: Negative in lead, positive in lag  
POWER FACTOR TRANSDUCER  
Functions & Features  
• Providing a DC output signal in proportion to power factor  
• DC output containing little ripple is ideal for computer  
input  
[4] OUTPUT  
Current  
A: 4 – 20 mA DC (Load resistance 600 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1200 Ω max.)  
C: 1 – 5 mA DC (Load resistance 2400 Ω max.)  
D: 0 – 20 mA DC (Load resistance 600 Ω max.)  
E: 0 – 16 mA DC (Load resistance 750 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1200 Ω max.)  
G: 0 – 1 mA DC (Load resistance 12 kΩ max.)  
GW: -1 – +1 mA DC (Load resistance 10 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
• Isolation up to 2000 V AC  
• High-density mounting  
Typical Applications  
• Centralized monitoring and control of power management  
system in a manufacturing facility or building  
• Measuring power factor for a motor  
50  
(1.97)  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 1000 Ω min.)  
4: 0 – 10 V DC (Load resistance 10 kΩ min.)  
5: 0 – 5 V DC (Load resistance 5000 Ω min.)  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
1W: -10 – +10 mV DC (Load resistance 10 kΩ min.)  
2W: -100 – +100 mV DC (Load resistance 100 kΩ min.)  
3W: -1 – +1 V DC (Load resistance 1000 Ω min.)  
4W: -10 – +10 V DC (Load resistance 10 kΩ min.)  
5W: -5 – +5 V DC (Load resistance 5000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
80  
(3.15)  
132  
(5.20)  
mm (inch)  
MODEL: KEPF–[1][2][3][4]–[5][6]  
ORDERING INFORMATION  
• Code number: KEPF-[1][2][3][4]-[5][6]  
Specify a code from below for each of [1] through [6].  
(e.g. KEPF-11PA-C/Q)  
[5] AUXILIARY POWER SUPPLY  
AC Power  
B: 100 V AC  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
[1] CONFIGURATION  
1: 3-phase / 3-wire  
H: 220 V AC  
J: 240 V AC  
4: 3-phase / 4-wire  
DC Power  
R: 24 V DC  
[2] INPUT (balanced load)  
1: 110 V / 5 A AC  
V: 48 V DC  
P: 110 V DC  
2: 110 V / 1 A AC  
3: 220 V / 1 A AC  
[6] OPTIONS  
blank: none  
4: 220 V / 5 A AC  
5: 220 V / 380 V / 1 A AC (3-phase / 4-wire)  
6: 220 V / 380 V / 5 A AC (3-phase / 4-wire)  
7: 110 V / 190 V / 1 A AC (3-phase / 4-wire)  
8: 110 V / 190 V / 5 A AC (3-phase / 4-wire)  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
KEPF SPECIFICATIONS  
ES-3668 Rev.5 Page 1/4  
http://www.m-system.co.jp/  
MODEL: KEPF  
OPERATION DIAGRAM (example)  
/C02: Polyurethane coating  
/C03: Rubber coating  
• Negative in lag, positive in lead  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
OUT  
20mA  
OUT  
+10V  
12  
4
0
GENERAL SPECIFICATIONS  
Construction: Plug-in  
-10V  
0.5  
(Lag)  
1
0.5  
(Lead)  
0.5  
(Lag)  
1
0.5  
(Lead)  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
• Negative in lead, positive in lag  
OUT  
20mA  
OUT  
+10V  
Housing material: Flame-resistant resin (black)  
Isolation: Voltage input to current input to output to  
auxiliary power  
12  
4
0
Computation: Phase angle detection  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
-10V  
0.5  
(Lag)  
0.5  
(Lag)  
1
0.5  
(Lead)  
1
0.5  
(Lead)  
Note: When there is no input voltage or 5% or less of rated  
input current , the output may become unstable (hunting).  
INPUT SPECIFICATIONS  
A device which employs different measuring methods may  
show different outputs from that of M-System's.  
Frequency: 50 or 60 Hz  
INSTALLATION  
Auxiliary power supply  
• Voltage Input  
AC: Operational voltage range: rating -15/+10 %,  
50/60 Hz, approx. 2 VA  
Input burden: 0.5 VA  
Operational range: 85 – 120 % of rating  
Overload capacity: 150 % of rating for 10 sec., 120 %  
continuous  
DC: Operational voltage range: rating ±10 %,  
or 85 – 150 V for 110 V rating, ripple 10 %p-p max.,  
approx. 2 W (18 mA at 110 V)  
• Current Input  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 85 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Input burden:  
0.1 VA (input 1 A)  
0.5 VA (input 5 A)  
Weight: 400 g (0.88 lb)  
Operational range: 10 – 120 % of rating  
Overload capacity: 1000 % of rating for 3 sec., 200 % for 10  
sec., 120 % continuous  
PERFORMANCE in percentage of span  
Accuracy: ±2 % with input 1 – 0.866, balanced load  
±4 % with input 0.866 – 0.5, balanced load (at 23°C ±10°C  
or 73.4°F ±18°F, 45 – 65 Hz)  
Input range:  
Lag 0.5 – 1 – lead 0.5  
Lead 0.5 – 1 – lag 0.5  
Response time: ≤ 2 sec. (0 – 100 % ±1 %)  
Ripple: 0.5 %p-p max.  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC and ± 1 mA  
Minimum span: 1 mA  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(voltage input to current input to output to auxiliary power  
to ground)  
Offset: Max. 1.5 times span  
Load resistance: Output drive 12 V max.  
DC Voltage: -10 – +12 V DC  
Minimum span: 5 mV  
Impulse withstand voltage: 1.2 / 50 μsec., ±5 kV  
(input to output or ground)  
Offset: Max. 1.5 times span  
Load resistance: Output drive 1 mA max. at ≥ 0.5 V  
KEPF SPECIFICATIONS  
ES-3668 Rev.5 Page 2/4  
http://www.m-system.co.jp/  
MODEL: KEPF  
CONNECTION DIAGRAM  
3-PHASE/3-WIRE  
3-PHASE/4-WIRE  
SOURCE  
1
SOURCE  
1
2
3
N
2
3
VT  
VT  
FUSE  
FUSE  
V
U
v
P2  
P3  
U
u
P2  
P0  
P3  
9
4
1
2
3
9
4
1
2
+
+
OUTPUT  
OUTPUT  
V
V
v
v
u
U
u
K
L
K
L
k
l
k
l
1S  
1L  
1S  
1L  
5
6
5
6
CT  
CT  
*
*
10  
11  
10  
11  
U(+)  
V(–)  
U(+)  
V(–)  
AUXILIARY POWER**  
AUXILIARY POWER**  
LOAD  
LOAD  
*CT Protector (model: CTM) attached to these terminals.  
**The transducer can be powered from the input voltage when the voltage is sufficiently stable and meets within the range of auxiliary  
power supply of the unit specified in the data sheet/instruction manual.  
EXTERNAL DIMENSIONS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
8
9
7
6
5
4
2
4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
3
2
10 11  
1
11  
M3.5  
SCREW  
50 (1.97)  
103 (4.06)  
132 (5.20)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
TERMINAL ASSIGNMENTS unit: mm (inch)  
CT PROTECTOR  
(model: CTM)  
8
7
6
5
4
9
3
2
10 11  
1
KEPF SPECIFICATIONS  
ES-3668 Rev.5 Page 3/4  
http://www.m-system.co.jp/  
MODEL: KEPF  
Specifications are subject to change without notice.  
KEPF SPECIFICATIONS  
ES-3668 Rev.5 Page 4/4  
http://www.m-system.co.jp/  

KEPF-41MD-R 相关器件

型号 制造商 描述 价格 文档
KEPF-41MD-R/Q MSYSTEM Plug-in Signal Conditioners K-UNIT 获取价格
KEPF-41MD-V MSYSTEM Plug-in Signal Conditioners K-UNIT 获取价格
KEPF-41MD-V/Q MSYSTEM Plug-in Signal Conditioners K-UNIT 获取价格
KEPF-41P1-B MSYSTEM Plug-in Signal Conditioners K-UNIT 获取价格
KEPF-41P1-B/Q MSYSTEM Plug-in Signal Conditioners K-UNIT 获取价格
KEPF-41P1-C MSYSTEM Plug-in Signal Conditioners K-UNIT 获取价格
KEPF-41P1-C/Q MSYSTEM Plug-in Signal Conditioners K-UNIT 获取价格
KEPF-41P1-D MSYSTEM Plug-in Signal Conditioners K-UNIT 获取价格
KEPF-41P1-D/Q MSYSTEM Plug-in Signal Conditioners K-UNIT 获取价格
KEPF-41P1-P MSYSTEM Plug-in Signal Conditioners K-UNIT 获取价格

KEPF-41MD-R 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8