KSED-41-L3 [MSYSTEM]
Plug-in Signal Conditioners K-UNIT;型号: | KSED-41-L3 |
厂家: | M-SYSTEM |
描述: | Plug-in Signal Conditioners K-UNIT |
文件: | 总4页 (文件大小:130K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: KSED
Plug-in Signal Conditioners K-UNIT
[2] POWER INPUT
AC Power
K3: 100 – 120 V AC
DC ALARM
(Operational voltage range 90 – 132 V, 47 – 66 Hz)
L3: 200 – 240 V AC (Operational voltage range 180 – 264 V,
47 – 66 Hz) (UL not available)
(thumbwheel switch adjustment)
Functions & Features
• Providing SPDT relay outputs at preset DC input
levels
• Dual (Hi/Lo) trip
[3] OPTIONS (multiple selections)
Standards & Approvals
• Thumbwheel switch setpoint adjustments
• Enclosed relays
blank: CE marking
• High-density mounting
/UL: UL approval, CE marking
Other Options
Typical Applications
• Annunciator
blank: none
/Q: Option other than the above (specify the specification)
• Various alarm applications
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
50
(1.97)
/C02: Polyurethane coating
80
(3.15)
/C03: Rubber coating (UL not available)
TERMINAL SCREW MATERIAL
4
3
4
1
/S01: Stainless steel (UL not available)
132
(5.20)
mm (inch)
GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless
steel
MODEL: KSED–[1]1–[2][3]
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Setpoint adjustments: Thumbwheel switches (front); 0 – 99
% independently; 1 % increments
Hysteresis (deadband): Approx. 1 %
Front LEDs: Red light turns on when the coil for Hi output is
energized.
ORDERING INFORMATION
• Code number: KSED-[1]1-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. KSED-61-K3/UL/Q)
• Specify the specification for option code /Q
(e.g. /C01)
Green light turns on when the coil for Lo output is
energized.
[1] INPUT
Current
Power ON timer: Relays de-energized for approx. 2 seconds
after power is turned on.
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
4: 0 – 10 V DC (Input resistance 1 MΩ min.)
5: 0 – 5 V DC (Input resistance 1 MΩ min.)
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
INPUT SPECIFICATIONS
■ DC Current:
Shunt resistor attached to the input terminals (0.5 W)
OUTPUT
Relay; SPDT or transfer contact
OUTPUT SPECIFICATIONS
■ Relay Contact:
100 V AC @5 A (cos ø = 1)
120 V AC @5 A (cos ø = 1)
240 V AC @2.5 A (cos ø = 1)
30 V DC @5 A (resistive load)
SETPOINT ADJUSTMENTS
1: Thumbwheel switch
KSED SPECIFICATIONS
ES-3610 Rev.9 Page 1/4
http://www.m-system.co.jp/
MODEL: KSED
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 600 VA or 150 W
Minimum load: 5 V DC @10 mA
Mechanical life: 1 × 10 cycles
7
Alarm Trip Operation Terminal No. in parentheses
(1–2)ON
Hi Output
Lo Output
(1–3)ON
(9–10)ON
(9–11)ON
Input
(%)
0
▲
50
▲
100
Lo Setpoint
Hi Setpoint
Trip Operation in Power Failure
: Terminals 1 – 3, 9 – 11 turn ON.
INSTALLATION
Power Consumption
•AC: Approx. 2 VA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 85 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 300 g (0.66 lb)
PERFORMANCE in percentage of span
Setpoint accuracy: ±0.5 %
Trip point repeatability: ±0.05 %
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.7 sec. (0 – 100 % at 90 % setpoint)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute
(input or output to power to ground)
1500 V AC @1 minute (input to output)
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (output)
Installation Category II (power)
Pollution Degree 2
Input to output to power: Basic insulation (300 V)
RoHS Directive
EN 50581
Approval:
UL/C-UL general safety requirements
(UL 3111-1, CAN/CSA-C22.2 No.1010-1)
KSED SPECIFICATIONS
ES-3610 Rev.9 Page 2/4
http://www.m-system.co.jp/
MODEL: KSED
EXTERNAL VIEW
Hi Monitor LED
Hi Setpoint Adj.
9
9
9
9
Lo Setpoint Adj.
Lo Monitor LED
EXTERNAL DIMENSIONS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
8
9
7
6
5
4
2
–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
3
2
10 11
1
11
–M3.5
SCREW
50 (1.97)
103 (4.06)
132 (5.20)
40 (1.57)
50 (1.97)
[3.3 (.13)]
• When mounting, no extra space is needed between units.
TERMINAL ASSIGNMENTS unit: mm (inch)
INPUT RESISTOR
(model: REM)
8
7
6
5
4
9
3
2
10 11
1
Input shunt resistor attached
for current input.
KSED SPECIFICATIONS
ES-3610 Rev.9 Page 3/4
http://www.m-system.co.jp/
MODEL: KSED
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
D / A
Converter
THUMBWHEEL
SWITCHES
9 9
3
2
1
N.C.
N.O.
COM
Low Drift
Amplifier
Comparator
Comparator
+
–
5
6
4
Ry
Ry
*
HI OUTPUT
LO OUTPUT
INPUT
R
11 N.C.
10 N.O.
D / A
Converter
THUMBWHEEL
SWITCHES
9 9
9
7
8
COM
U
POWER
V
Base Socket
*Input shunt resistor attached for current input.
■Relay Protection
•AC Powered
•DC Powered
Inductive
Load (Coil)
Inductive
Load (Coil)
Varistor or Spark
Quenching Circuit
Diode, Varistor or
CR Circuit
LOAD
LOAD
U
Specifications are subject to change without notice.
KSED SPECIFICATIONS
ES-3610 Rev.9 Page 4/4
http://www.m-system.co.jp/
相关型号: