PDF下载MODEL: KWYPD
Plug-in Signal Conditioners K-UNIT
[3] OUTPUT 1
A1: Open collector (max. frequency 100 kHz)
A2: Open collector (max. frequency 10 Hz)
M1: 5 V pulse (max. frequency 100 kHz)
M2: 5 V pulse (max. frequency 10 Hz)
N1: 12 V pulse (max. frequency 100 kHz)
N2: 12 V pulse (max. frequency 10 Hz)
H: Relay contact (max. frequency 0.5 Hz)
PULSE ISOLATOR
(two isolated outputs; built-in excitation)
Functions & Features
• Galvanically isolating pulse rate signals
• Input frequency = output frequency
• Various outputs (relay, open collector and voltage pulses)
• Excitation
• Isolation up to 2000 V AC
[4] OUTPUT 2
• High-density mounting
Same range availability as Output 1
(Choose a combination of output 1 and 2 with same max.
frequency limit. Output logic of open collector is reversed
when open collector and others are mixed.)
Typical Applications
• Isolating field pulse signals in order to reduce noises
• Changing e.g. dry contact signal to e.g. 5 V signals
[5] OUTPUT PULSE WIDTH
1: Equal to the input
50
(1.97)
2: One-shot output (≤ 30 ms; std. pulse width 5 ms)
(Specify when optional pulse width is required.)
(10 ms for relay contact pulse)
80
(3.15)
3: One-shot output (≥ 30 ms; std. pulse width 50 ms)
(Specify when optional pulse width is required.)
132
(5.20)
[6] OUTPUT LOGIC
N: The same as the input
R: Inverted
mm (inch)
MODEL: KWYPD–[1][2][3][4][5][6]–[7][8]
[7] POWER INPUT
AC Power
ORDERING INFORMATION
B: 100 V AC
C: 110 V AC
D: 115 V AC
F: 120 V AC
G: 200 V AC
H: 220 V AC
J: 240 V AC
• Code number: KWYPD-[1][2][3][4][5][6]-[7][8]
Specify a code from below for each of [1] through [8].
(e.g. KWYPD-D4A2M23N-B/Q)
• Frequency range (e.g. 0 – 5 Hz)
• Use Ordering Information Sheet (No. ESU-2276) for pulse
width settings of DC voltage pulse input or one-shot output.
• Specify the specification for option code /Q
(e.g. /C01/S01)
DC Power
S: 12 V DC
R: 24 V DC
[1] INPUT
A: Dry contact
[8] OPTIONS
blank: none
B: DC voltage pulse (Specify sensitivity)
C: 5 V pulse (sensitivity 2 V)
D: 12 V/24 V pulse (sensitivity 5 V)
H: Two-wire current pulse
/Q: With options (specify the specification)
[2] EXCITATION
1: 5 V DC / 80 mA
4: 12 V DC / 40 mA
KWYPD SPECIFICATIONS
ES-3577 Rev.14 Page 1/6
http://www.m-system.co.jp/
MODEL: KWYPD
for output code A2, M2, N2, H)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Input resistance: Receiving resistor 220 Ω
Maximum current: ± 50 mA
Hi/Lo level: ≤ 5 mA for Lo, ≥ 15 mA for Hi
■ Voltage pulse waveform
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
Volts
50V max.
Amplitude
Vinp-p
GENERAL SPECIFICATIONS
Construction: Plug-in
DC Offset
Connection: M3.5 screw terminals
t
Screw terminal: Chromated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output 1 to output 2 to power
Excitation adjustment: 5 – 12 V DC
Detecting level adjustments (DC voltage pulse): 2 – 10 V
Input pulse sensing: DC coupled
OUTPUT SPECIFICATIONS
■ Open Collector: 50 V DC @ 50 mA (resistive load)
Maximum frequency:
Output code A1: 100 kHz with load resistance ≤ 1 kΩ
OUtput code A2: 10 Hz with load resistance ≤ 1 kΩ
Saturation voltage: 0.5 V DC
Input filter: Provided with output code A2, M2, N2, H
(time constant approx. 1 msec.)
■ Voltage Pulse: Rating (5 or 12 V) ± 10 %
Maximum frequency: 100 kHz
Load resistance: 1.5 kΩ min. for 5 V, 3 kΩ min. for 12 V
L level: ≤ 0.5 V
INPUT SPECIFICATIONS
Excitation: Shortcircuit protection; approx. 150 mA at
shortcircuit
■ Relay Contact: 120 V AC or 30 V DC @ 200 mA
(resistive load)
■ Dry Contact
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 50 VA or 6 W
Minimum load: 5 V DC @ 10 mA
Max. frequency: 100 kHz
Pulse width time requirement: 5 μsec. min. (10 ms
for output code A2, M2, N2, H)
Sensing: 10 V DC @ 2.5 mA
Maximum frequency: 0.5 Hz
Relay life:
ON/OFF level:
2 × 10
7
cycles (mechanical)
cycles (electrical)
≥ 5.5 kΩ /5.5 V for OFF
7 × 10
6
≤ 1.8 kΩ /4.5 V for ON
■ Voltage Pulse: Specify DC offset and amplitude.
Max. frequency: 100 kHz
OUTPUT PULSE WIDTH
Pulse width time requirement: 5 μsec. min. (10 ms
for output code A2, M2, N2, H)
Waveform: Square or sine
•Equal to the Input: No pulse width conversion
(difference between input and output within ±10 μsec.)
• One-shot Output: Constant pulse width
Output Frequency (Hz) = 500 / (Output Pulse Width (msec.))
Adjustable pulse width
Input impedance: 10 kΩ min.
Input amplitude: 2 – 50 Vp-p
Sensitivity adjustment (threshold level): 2 – 10 V
Max. voltage between input terminals: 50 V
• 5V, 12V, 24V Pulse
Pulse width max. 30 msec. (code 2):
1 – 30 msec. adjustable (standard 5 msec. ±20 %) for
'Output' code other than 'H'
Waveform: Square or sine
10 – 30 msec. adjustable (standard 10 msec. ±20 %) for
'Output' code 'H'
Input impedance: 10 kΩ min.
Detecting level
Pulse width min. 30 msec. (code 3): 30 msec. – 1 sec.
adjustable (standard 50 msec. ±20 %)
INPUT 5 V PULSE 12 V / 24 V PULSE
V
H
≥ 2.25 V
≤ 1.75 V
≥ 5.25 V
≤ 4.75 V
VL
■ Two-wire Current Pulse
Max. frequency: 100 kHz
Pulse width time requirement: 5 μsec. min. (10 ms
KWYPD SPECIFICATIONS
ES-3577 Rev.14 Page 2/6
http://www.m-system.co.jp/
MODEL: KWYPD
INSTALLATION
Power input
•AC: Operational voltage range: rating ±10 %,
50/60 ± 2 Hz, approx. 2.5 VA
•DC: Operational voltage range: rating ±10 %,
ripple 10 %p-p max., approx. 2 W (80 mA at 24 V)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lb)
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
2000 V AC @1 minute (input to output 1 or output 2 to
power to ground)
1000 V AC @1 minute (output 1 to output 2)
EXTERNAL VIEW
Excitation Adj.
Sensitivity Adj.
Pulse Width Adj.
KWYPD SPECIFICATIONS
ES-3577 Rev.14 Page 3/6
http://www.m-system.co.jp/
MODEL: KWYPD
OUTPUT LOGIC
VOLTAGE PULSE or
INPUT WAVEFORM
DRY CONTACT
OFF
2-WIRE CURRENT PULSE
H
OUTPUT WAVEFORM
L
ON
H
H
Voltage pulse
L
L
No pulse width conversion
OFF
OFF
Open collector
or relay contact
ON
H
ON
H
One-shot, detecting
input pulse rise
Voltage pulse
L
L
NON INVERTED
OFF
OFF
Open collector
or relay contact
ON
H
ON
H
One-shot, detecting
input pulse sink
Voltage pulse
L
L
OFF
OFF
Open collector
or relay contact
ON
H
ON
H
Voltage pulse
L
L
No pulse width conversion
OFF
OFF
Open collector
or relay contact
ON
H
ON
H
One-shot, detecting
input pulse rise
Voltage pulse
L
L
INVERTED
OFF
OFF
Open collector
or relay contact
ON
H
ON
H
One-shot, detecting
input pulse sink
Voltage pulse
L
L
OFF
OFF
Open collector
or relay contact
ON
ON
The pulse width in one-shot means the bold lined section of a pulse waveform.
Shades indicate default setting.
Input pulse rise/sink detected with voltage level
KWYPD SPECIFICATIONS
ES-3577 Rev.14 Page 4/6
http://www.m-system.co.jp/
MODEL: KWYPD
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom)
7.8 (.31)
DIN RAIL
35mm wide
8
7
6
5
4
2
–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
9
3
2
10 11
1
11
–M3.5
SCREW
50 (1.97)
103 (4.06)
132 (5.20)
40 (1.57)
50 (1.97)
[3.3 (.13)]
• When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
SENSITIVITY
PULTH WIDTH
Isolation
Waveform
Shaper
Output
Driver
One-Shot *
+
–
+
5
6
4
3
9
1
2
+
–
OUTPUT 1
INPUT
SENSOR EXCITATION
Excitation
Supply
Output
Driver
10
11
7
+
OUTPUT 2
POWER
EXCITATION
–
U(+)
V(–)
8
Base Socket
*Disregard one-shot circuit for output pulse width code “1”.
Input Connection Examples
Output Connection Examples
■ Open Collector
■
Dry Contact
■ 2-Wire Current Pulse
• Built-in Excitation
■ Voltage Pulse
+10V
4kΩ
220Ω
+
–
5
6
4
–
+
5
6
4
1
2
+
–
+
–
1
2
+
–
+
–
2-WIRE
PICK-UP
–
PWR
+
Vsns
Vsns
■ Relay Contact
• AC Powered
• External DC Supply
■
Voltage Pulse
Relay or
Counter Coil
1
2
10kΩ
220Ω
Varistor or Spark
Quenching Circuit
+
–
–
+
5
–
+
5
6
4
LOAD
2-WIRE
PICK-UP
6
4
U
DC SUPPLY
Vsns
Vsns
• DC Powered
+
–
PWR
Relay or
Counter Coil
1
2
Spark Quenching
Diode
LOAD
KWYPD SPECIFICATIONS
ES-3577 Rev.14 Page 5/6
http://www.m-system.co.jp/
MODEL: KWYPD
Specifications are subject to change without notice.
KWYPD SPECIFICATIONS
ES-3577 Rev.14 Page 6/6
http://www.m-system.co.jp/
KWYPD-H1N113R-R 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
KWYPD-H1N113R-R/Q | MSYSTEM | Plug-in Signal Conditioners K-UNIT | 获取价格 | |
KWYPD-H1N113R-S | MSYSTEM | Plug-in Signal Conditioners K-UNIT | 获取价格 | |
KWYPD-H1N113R-S/Q | MSYSTEM | Plug-in Signal Conditioners K-UNIT | 获取价格 | |
KWYPD-H1N211N-B | MSYSTEM | Plug-in Signal Conditioners K-UNIT | 获取价格 | |
KWYPD-H1N211N-B/Q | MSYSTEM | Plug-in Signal Conditioners K-UNIT | 获取价格 | |
KWYPD-H1N211N-C | MSYSTEM | Plug-in Signal Conditioners K-UNIT | 获取价格 | |
KWYPD-H1N211N-C/Q | MSYSTEM | Plug-in Signal Conditioners K-UNIT | 获取价格 | |
KWYPD-H1N211N-D | MSYSTEM | Plug-in Signal Conditioners K-UNIT | 获取价格 | |
KWYPD-H1N211N-D/Q | MSYSTEM | Plug-in Signal Conditioners K-UNIT | 获取价格 | |
KWYPD-H1N211N-R | MSYSTEM | Plug-in Signal Conditioners K-UNIT | 获取价格 |
KWYPD-H1N113R-R 相关文章
- 2024-10-31
- 6
- 2024-10-31
- 6
- 2024-10-31
- 7
- 2024-10-31
- 8