MODEL: LC2  
Plug-in Signal Conditioners M-UNIT  
[2] OUTPUT  
Current  
A: 4 – 20 mA DC (Load resistance 750 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1500 Ω max.)  
C: 1 – 5 mA DC (Load resistance 3000 Ω max.)  
D: 0 – 20 mA DC (Load resistance 750 Ω max.)  
E: 0 – 16 mA DC (Load resistance 900 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1500 Ω max.)  
G: 0 – 1 mA DC (Load resistance 15 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
STRAIN GAUGE TRANSMITTER  
(remote sensing; non-isolated)  
Functions & Features  
• Provides a DC output signal compatible with a bridge type  
strain gauge utilized in load cells, pressure transducers  
• Six-wire remote sensing compensates for lead resistance  
variations  
• Excitation adjustable from 2 V to 5 V  
• Wide-range adjustment: 0 – 80 % for zero, 100 – 20 % for  
span  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 100 Ω min.)  
4: 0 – 10 V DC (Load resistance 1000 Ω min.)  
5: 0 – 5 V DC (Load resistance 500 Ω min.)  
6: 1 – 5 V DC (Load resistance 500 Ω min.)  
4W: -10 – +10 V DC (Load resistance 2000 Ω min.)  
5W: -5 – +5 V DC (Load resistance 1000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
• High-density mounting  
Typical Applications  
• Weighing system for tanks, hoppers, silos  
• Weighing system using cranes  
• Float level meter utilizing strain gauges  
50  
(1.97)  
[3] POWER INPUT  
AC Power  
80  
(3.15)  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
136  
(5.35)  
mm (inch)  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
MODEL: LC2–[1][2]–[3][4]  
DC Power  
R: 24 V DC  
ORDERING INFORMATION  
• Code number: LC2-[1][2]-[3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. LC2-2A-B/E/K/Q)  
[4] OPTIONS (multiple selections)  
Input Signal Indicator  
blank: Without  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
/E: With (0.0 - 100.0 % display)  
Response Time (0 – 90 %)  
blank: Standard (≤ 0.5 sec.)  
/K: Fast Response (Approx. 25 msec.)  
Other Options  
[1] INPUT STRAIN GAUGE  
1: 1 mV/V  
blank: none  
/Q: Option other than the above (specify the specification)  
12: 1.25 mV/V  
15: 1.5 mV/V  
2: 2 mV/V  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
3: 3 mV/V  
4: 4 mV/V  
5: 5 mV/V  
/C02: Polyurethane coating  
6: 10 mV/V  
/C03: Rubber coating  
7: 20 mV/V  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
0: Specify (strain gauge and excitation)  
LC2 SPECIFICATIONS  
ES-1357 Rev.4 Page 1/3  
http://www.m-system.co.jp/  
MODEL: LC2  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
PERFORMANCE in percentage of span  
Accuracy: ±0.1 % (input ≥ 3 mV)  
Connection: M3.5 screw terminals  
Screw terminal: Chromated steel (standard) or stainless  
steel  
Display accuracy: ± (0.1 % of FS + 1 digit)  
(input ≥ 3 mV)  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) (input ≥ 3  
mV)  
Housing material: Flame-resistant resin (black)  
Isolation: Input or output to power  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Excitation adjustment: 2 – 5 V (front) limited to ≤ 10 V when  
the remote sensing terminals are open.  
Zero adjustments (tare): 0 – 80 % (front)  
(Excitation voltage: factory default)  
Span adjustment: 100 – 20 % (front)  
(Excitation voltage: factory default)  
■ DISPLAY (Input indicator)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute for AC power  
1000 V AC @1 minute for DC power  
(input or output to power)  
2000 V AC @1 minute  
(input or output or power to ground)  
LCD digital display: 0.0 - 100.0 % (min. digit 0.1 %)  
(No scaling)  
INPUT SPECIFICATIONS  
Input: Bridge voltage from load cells  
Allowable leadwire resistance: ≤ Total Strain Gauge  
Resistance × 0.25  
Strain Gauge  
Rated output from strain gauge: 1 – 20 mV/V; Input to the  
transmitter must be over 3 mV.  
Excitation: 2 – 5 V adjustable (5 V standard)  
Maximum current: 65 mA  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 15 V max.  
DC Voltage: -10 – +12 V DC  
Minimum span: 5 mV  
Offset: Max. 1.5 times span  
Load resistance: Output drive 10 mA max.; 5 mA for  
negative voltage output; at ≥ 0.5 V  
INSTALLATION  
Power input  
AC: Operational voltage range: rating ±10 %,  
50/60 ± 2 Hz, approx. 5 VA  
DC: Operational voltage range: 24 V ±10 %,  
approx. 150 mA, ripple 10 %p-p max.  
Operating temperature: -5 to +60°C (23 to 140°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 430 g (0.95 lb)  
LC2 SPECIFICATIONS  
ES-1357 Rev.4 Page 2/3  
http://www.m-system.co.jp/  
MODEL: LC2  
EXTERNAL VIEW  
LCD Meter  
Excitation Adj.  
Zero Adj.  
Span Adj.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
8
7
6
5
4
2–  
4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
9
3
2
10 11  
1
11  
M3.5  
SCREW  
50 (1.97)  
107 (4.21)  
136 (5.35)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
*
STRAIN  
GAUGE  
Z
S
Output  
Driver  
+
+
10  
11  
3
1
2
Low Drift  
Amplifier  
OUTPUT  
+
Low Drift  
DC Volt.  
Stabilizer  
EXC.  
9
S +  
S –  
U(+)  
V(–)  
4
7
8
Remote  
Sensing  
POWER  
5
6
Base Socket  
Close across the terminal 3 – 4 and 5 – 9 when the remote sensing is not used.  
* Option /E  
Specifications are subject to change without notice.  
LC2 SPECIFICATIONS  
ES-1357 Rev.4 Page 3/3  
http://www.m-system.co.jp/  

LC2-42-D/K 相关器件

型号 制造商 描述 价格 文档
LC2-42-D/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
LC2-42-F MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
LC2-42-F/E MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
LC2-42-F/K MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
LC2-42-F/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
LC2-42-R MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
LC2-42-R/E MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
LC2-42-R/K MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
LC2-42-R/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
LC2-43-B MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格

LC2-42-D/K 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8