MODEL: LPA  
(220 V in code 5 and 6, and 110 V in code 7 and 8  
Power Transducer Series L-UNIT  
are phase voltage)  
PHASE ANGLE TRANSDUCER  
Functions & Features  
[3] OUTPUT SIGNAL POLARITY  
P: Negative in lag, positive in lead  
• Providing a DC output signal in proportion to phase angle  
• DC output containing little ripple is ideal for computer  
input  
M: Negative in lead, positive in lag  
• Isolation up to 2000 V AC  
[4] OUTPUT  
Current  
• High-density mounting  
A: 4 – 20 mA DC (Load resistance 600 Ω max.)  
FW: -10 – +10 mA DC (Load resistance 1000 Ω max.)  
GW: -1 – +1 mA DC (Load resistance 10 kΩ max.)  
JW: -5 – +5 mA DC (Load resistance 2000 Ω max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
Typical Applications  
• Centralized monitoring and control of power management  
system in a manufacturing facility or building  
• Measuring phase angle for a motor  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
1W: -10 – +10 mV DC (Load resistance 10 kΩ min.)  
2W: -100 – +100 mV DC (Load resistance 100 kΩ min.)  
3W: -1 – +1 V DC (Load resistance 1000 Ω min.)  
4W: -10 – +10 V DC (Load resistance 10 kΩ min.)  
5W: -5 – +5 V DC (Load resistance 5000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
75  
(2.95)  
75  
(2.95)  
112  
(4.41)  
mm (inch)  
[5] AUXILIARY POWER SUPPLY  
AC Power  
B: 100 V AC  
C: 110 V AC  
MODEL: LPA–[1][2][3][4]–[5][6]  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
ORDERING INFORMATION  
• Code number: LPA–[1][2][3][4]-[5][6]  
Specify a code from below for each [1] through [6].  
(e.g. LPA-11PA-C/Q)  
H: 220 V AC  
J: 240 V AC  
DC Power  
R: 24 V DC  
• Special DC output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
V: 48 V DC  
P: 110 V DC  
[6] OPTIONS  
blank: none  
[1] CONFIGURATION  
1: 3-phase / 3-wire  
/Q: With options (specify the specification)  
4: 3-phase / 4-wire  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
[2] INPUT (balanced load)  
1: 110 V / 5 A AC  
2: 110 V / 1 A AC  
/C02: Polyurethane coating  
3: 220 V / 1 A AC  
/C03: Rubber coating  
4: 220 V / 5 A AC  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
5: 220 V / 380 V / 1 A AC (3-phase / 4-wire)  
6: 220 V / 380 V / 5 A AC (3-phase / 4-wire)  
7: 110 V / 190 V / 1 A AC (3-phase / 4-wire)  
8: 110 V / 190 V / 5 A AC (3-phase / 4-wire)  
http://www.m-system.co.jp/  
LPA SPECIFICATIONS  
ES-1981 Rev.13 Page 1/3  
MODEL: LPA  
OPERATION DIAGRAM (example)  
GENERAL SPECIFICATIONS  
Construction: Stand-alone; terminal access at the front  
Connection: M3.5 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel (standard) or stainless  
steel  
• Negative in lag, positive in lead  
OUT  
20mA  
OUT  
+10V  
12  
4
0
Housing material: Flame-resistant resin (black)  
Isolation: Voltage input to current input to output to  
auxiliary power  
-10V  
60°  
(Lag)  
0
60°  
(Lead)  
60°  
(Lag)  
0
60°  
(Lead)  
Computation: Phase angle detection  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
• Negative in lead, positive in lag  
OUT  
20mA  
OUT  
+10V  
Span adjustment: 95 to 105 % (front)  
12  
4
0
INPUT SPECIFICATIONS  
■INPUT  
-10V  
60°  
(Lag)  
0
60°  
(Lead)  
60°  
(Lag)  
0
60°  
(Lead)  
Frequency: 50 or 60 Hz  
Voltage Input  
Input burden: 0.5 VA  
Remark: When there is no input voltage or 5% or less of the rated  
input current, the output may become unstable (hunting).  
Operational range: 85 – 120 % of rating  
Overload capacity: 150 % of rating for 10 sec., 120 %  
continuous  
INSTALLATION  
Auxiliary power supply  
Current Input  
Input burden: 0.1 VA (input 1 A)  
0.5 VA (input 5 A)  
AC: Operational voltage range: rating -15/+10 %,  
50/60 Hz, approx. 2 VA  
Operational range: 10 – 120 % of rating  
Overload capacity: 1000 % of rating for 3 sec., 200 % for 10  
sec., 120 % continuous  
DC: Operational voltage range: rating ±10 %,  
or 85 – 150 V for 110 V rating, ripple 10 %p-p max.,  
approx. 2 W (18 mA at 110 V)  
■ Input range:  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 85 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Lag 60° – 0 – lead 60°  
Lead 60° – 0 – lag 60°  
Weight: 450 g (0.99 lb)  
OUTPUT SPECIFICATIONS  
■ DC Current: -10 – + 20 mA DC  
Span: Min. 1 mA, max. 20 mA  
Offset: Max. 1.5 times span  
PERFORMANCE in percentage of span  
Accuracy: ±2 % with balanced load  
(at 23°C ±10°C or 73.4°F ±18°F, 45 – 65 Hz)  
Response time: ≤ 2 sec. (0 – 100 % ±1 %)  
Ripple: 0.5 %p-p max.  
Load resistance: Output drive 12 V maximum; 10 V for [±]  
output  
DC Voltage: -10 – +12 V DC  
Minimum span: 5 mV  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(voltage input to current input to output to auxiliary power  
to ground)  
Offset: Max. 1.5 times span  
Load resistance: Output drive 1 mA max. at ≥ 0.5 V  
Impulse withstand voltage: 1.2 / 50 μsec., ±5 kV  
(input to output or ground)  
http://www.m-system.co.jp/  
LPA SPECIFICATIONS  
ES-1981 Rev.13 Page 2/3  
MODEL: LPA  
CONNECTION DIAGRAM  
3-PHASE/3-WIRE  
3-PHASE/4-WIRE  
SOURCE  
3
SOURCE  
2
1
2
N
1
3
VT  
VT  
FUSE  
FUSE  
V
U
v
P2  
P3  
U
u
P2  
P0  
P3  
15  
16  
11  
12  
9
15  
13  
16  
11  
12  
9
+
+
OUTPUT  
OUTPUT  
u
V
V
v
v
U(+)  
U(+)  
U
u
*
*
AUXILIARY POWER  
AUXILIARY POWER  
V(–)  
K
L
K
L
10  
10  
V(–)  
k
l
1S  
1L  
k
l
1S  
1L  
1
2
1
2
CT  
CT  
LOAD  
LOAD  
*The transducer can be powered from the input voltage when the voltage is sufficiently stable and meets other supply voltage requirements.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
8 (.31)  
M3.5 SCREW  
(Only on the used terminals)  
2–5.8 (.23) dia. or  
2–4.8 (.18) dia.  
MTG HOLE  
8 (.31) deep  
DIN RAIL  
35mm wide  
1
9
2
3
4
5
6
7 8  
TERMINAL  
COVER  
10 11 12 13 14 15 16  
112 (4.41)  
[3.3 (.13)]  
75 (2.95)  
•When mounting, no extra space is needed between units.  
MOUNTING REQUIREMENTS unit: mm (inch)  
M5 SCREWS  
M4 SCREWS  
60 (2.36)  
60 (2.36)  
2–M5  
2–M4  
Specifications are subject to change without notice.  
http://www.m-system.co.jp/  
LPA SPECIFICATIONS  
ES-1981 Rev.13 Page 3/3  

LPA-42MA-B/Q 相关器件

型号 制造商 描述 价格 文档
LPA-42MA-C MSYSTEM Power Transducer Series L-UNIT 获取价格
LPA-42MA-C/Q MSYSTEM Power Transducer Series L-UNIT 获取价格
LPA-42MA-D MSYSTEM Power Transducer Series L-UNIT 获取价格
LPA-42MA-D/Q MSYSTEM Power Transducer Series L-UNIT 获取价格
LPA-42MA-F MSYSTEM Power Transducer Series L-UNIT 获取价格
LPA-42MA-F/Q MSYSTEM Power Transducer Series L-UNIT 获取价格
LPA-42MA-P MSYSTEM Power Transducer Series L-UNIT 获取价格
LPA-42MA-P/Q MSYSTEM Power Transducer Series L-UNIT 获取价格
LPA-42MA-R MSYSTEM Power Transducer Series L-UNIT 获取价格
LPA-42MA-R/Q MSYSTEM Power Transducer Series L-UNIT 获取价格

LPA-42MA-B/Q 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8