MODEL: M2AP  
Super-mini Signal Conditioners Mini-M Series  
[2] OUTPUT  
1: Open collector (max. 1 kHz)  
2: 5 V pulse (max. 1 kHz)  
DC/FREQUENCY CONVERTER  
Functions & Features  
4: Dry contact AC/DC switch (max. frequency 30 Hz)  
(‘/UL’ is not selectable for ‘Standards & Approvals’ code.)  
• Provides a pulse rate output in proportion to DC input  
signal  
[3] POWER INPUT  
Typical Applications  
AC Power  
• Totalizing applications in combination with a counter  
M: 85 – 264 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
(Select ‘/N’ for ‘Standards & Approvals’ code.)  
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
23 (.91)  
(90 – 264 V for UL)  
Model  
76  
(2.99)  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
R2: 11 – 27 V DC  
ZERO  
SPAN  
124  
(4.88)  
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)  
(Select ‘/N’ for ‘Standards & Approvals’ code.)  
P: 110 V DC  
mm (inch)  
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)  
(Select ‘/N’ for ‘Standards & Approvals’ code.)  
MODEL: M2AP-[1][2]-[3][4]  
[4] OPTIONS (multiple selections)  
Standards & Approvals (must be specified)  
/N: Without CE or UL  
ORDERING INFORMATION  
• Code number: M2AP-[1][2]-[3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. M2AP-61-M2/CE/Q)  
/CE: CE marking  
/UL: UL approval, CE marking  
Other Options  
• Output frequency range (e.g. 0 – 500 Hz)  
• Special input range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
blank: none  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
[1] INPUT  
Current  
A: 4 – 20 mA DC (Input resistance 250 Ω)  
D: 0 – 20 mA DC (Input resistance 50 Ω)  
G: 0 – 1 mA DC (Input resistance 1000 Ω)  
H: 10 – 50 mA DC (Input resistance 100 Ω)  
Z: Specify current (See INPUT SPECIFICATIONS)  
( 0 % input must be 0 mA.)  
/C02: Polyurethane coating  
/C03: Rubber coating (UL not available)  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel (UL not available)  
Voltage  
3: 0 – 1 V DC (Input resistance 1 MΩ min.)  
4: 0 – 10 V DC (Input resistance 1 MΩ min.)  
5: 0 – 5 V DC (Input resistance 1 MΩ min.)  
6: 1 – 5 V DC (Input resistance 1 MΩ min.)  
0: Specify voltage (See INPUT SPECIFICATIONS)  
( 0 % input must be 0 V.)  
M2AP SPECIFICATIONS  
ES-5051 Rev.19 Page 1/4  
http://www.m-system.co.jp/  
MODEL: M2AP  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
OUTPUT PULSE WIDTH  
Frequency less than 500 Hz at 100% input  
Duty ratio 20% (See the figure below)  
Connection: M3 screw terminals (torque 0.8 N·m)  
Screw terminal: Chromated steel (standard) or stainless  
steel  
• Open Collector  
• Voltage Pulse  
OFF  
H Level  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
Zero adjustment: 0 – 5 % (front)  
ON  
20  
L Level  
%
20%  
80  
%
80%  
1 / f  
1 / f  
Span adjustment: 95 to 105 % (front)  
Frequency greater than 500 Hz at 100% input  
See the figure and equation below.  
INPUT SPECIFICATIONS  
DC Current:  
• Open Collector  
• Voltage Pulse  
OFF  
H Level  
Shunt resistor attached to the input terminals (0.5 W)  
Specify input resistance value for code Z.  
DC Voltage: 0 – 300V DC  
ON  
L Level  
Pulse Width  
Pulse Width  
Minimum span: 1V  
Input resistance: 1 MΩ min.  
1
Pulse Width [millisec.] =  
2.09 × 100% Frequency [kHz]  
OUTPUT SPECIFICATIONS  
Open Collector: 30 V DC @100 mA (resistive load)  
Frequency range: 0 – 10 pulses/hour through 1 kHz  
Saturation voltage: 0.6 V DC  
Dry Contact AC/DC Switch  
See the figure below. ON pulse width is limited  
within 75 25 msec. when the output frequency  
gets low (below 2 to 4 Hz).  
• Dry Contact AC/DC Switch  
5 V Pulse  
OFF  
Frequency range: 0 – 10 pulses/hour through 1 kHz  
Hi level: 3.0 – 5.5 V  
ON  
20  
%
80  
%
Lo level: ≤ 0.5 V  
1 / f  
Load resistance: 250 Ω min.  
Dry Contact AC/DC Switch  
Frequency range: 0 – 10 pulses/hour through 30 Hz  
Timer: Limits within 75 ±25 msec.  
for wider than 75 msec. pulses  
INSTALLATION  
Power Consumption  
AC:  
Rated load: 132 V AC @200 mA (cos ø = 1)  
30 V DC @200 mA (resistive load)  
Saturation voltage: 3 V DC  
Approx. 3 VA at 100 V  
Approx. 4 VA at 200 V  
Approx. 5 VA at 264 V  
DC: Approx. 3 W  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 150 g (0.33 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.1 %  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time: Approx. 3 sec. (0 – 90 %)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
to power to ground)  
M2AP SPECIFICATIONS  
ES-5051 Rev.19 Page 2/4  
http://www.m-system.co.jp/  
MODEL: M2AP  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1  
Measurement Category II (input, output)  
Installation Category II (power)  
Pollution Degree 2  
Input or output to power: Reinforced insulation (300 V)  
Input to output: Basic insulation (300 V)  
RoHS Directive  
EN 50581  
Approval:  
UL/C-UL nonincendive Class I, Division 2,  
Groups A, B, C, and D  
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)  
UL/C-UL general safety requirements  
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)  
EXTERNAL DIMENSIONS unit: mm (inch)  
6 (.23)  
DIN RAIL  
35mm wide  
4
1
5
8
2–4.2x5  
(.17x.20)  
MTG HOLE  
6 (.24) deep  
12  
9
8–M3  
SCREW  
14 13  
21.5 (.85) 10 (.39)  
84 (3.31)  
114 (4.49)  
15 (.59)  
[4 (.16)]  
23 (.91)  
• When mounting, no extra space is needed between units.  
M2AP SPECIFICATIONS  
ES-5051 Rev.19 Page 3/4  
http://www.m-system.co.jp/  
MODEL: M2AP  
TERMINAL ASSIGNMENTS unit: mm (inch)  
INPUT RESISTOR  
(model: REM2)  
4
1
5
8
12  
9
14 13  
Input shunt resistor attached  
for current input.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Z
S
Isolation  
**  
Timer  
Low Drift  
Amplifier  
Volt. / Freq.  
Converter  
Output  
Driver  
+
+
1
4
5
8
Divider  
9
*
INPUT  
R
OUTPUT  
POWER  
12  
13 U(+)  
14 V(–)  
Base Socket  
*
Input shunt resistor attached for current input.  
** Dry contact AC/DC switch only.  
Output Connection Examples  
Open Collector  
Dry Contact AC/DC Switch  
• AC Powered  
Relay or  
Counter Coil  
+
+
9
9
Varistor or Spark  
Quenching Circuit  
12  
LOAD  
12  
U
Voltage Pulse  
• DC Powered  
Relay or  
Counter Coil  
9
+
+
9
Spark Quenching Diode  
LOAD  
12  
12  
Specifications are subject to change without notice.  
M2AP SPECIFICATIONS  
ES-5051 Rev.19 Page 4/4  
http://www.m-system.co.jp/  

M2AP-51-R2/Q 相关器件

型号 制造商 描述 价格 文档
M2AP-51-R2/UL MSYSTEM Super-mini Signal Conditioners Mini-M Series 获取价格
M2AP-52-M MSYSTEM Super-mini Signal Conditioners Mini-M Series 获取价格
M2AP-52-M/CE MSYSTEM Super-mini Signal Conditioners Mini-M Series 获取价格
M2AP-52-M/N MSYSTEM Super-mini Signal Conditioners Mini-M Series 获取价格
M2AP-52-M/Q MSYSTEM Super-mini Signal Conditioners Mini-M Series 获取价格
M2AP-52-M/UL MSYSTEM Super-mini Signal Conditioners Mini-M Series 获取价格
M2AP-52-M2 MSYSTEM Super-mini Signal Conditioners Mini-M Series 获取价格
M2AP-52-M2/CE MSYSTEM Super-mini Signal Conditioners Mini-M Series 获取价格
M2AP-52-M2/N MSYSTEM Super-mini Signal Conditioners Mini-M Series 获取价格
M2AP-52-M2/Q MSYSTEM Super-mini Signal Conditioners Mini-M Series 获取价格

M2AP-51-R2/Q 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8