M2BC-041-K [MSYSTEM]
Super-mini Signal Conditioners Mini-M Series;型号: | M2BC-041-K |
厂家: | M-SYSTEM |
描述: | Super-mini Signal Conditioners Mini-M Series |
文件: | 总8页 (文件大小:231K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M2BC
Super-mini Signal Conditioners Mini-M Series
GENERAL SPECIFICATIONS
Capacity: 4, 8 or 16 positions
Connection
COMMUNICATION CONTROLLER
(CC-Link)
CC-Link: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm , stripped length 7 mm)
2
Functions & Features
I/O: M3 screw terminals (torque 0.8 N·m)
Power input: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
• Receiving up to 16 Mini-M modules
• Enabling interfacing analog I/Os to CC-Link
• Power supplied through printed wiring on the base
Isolation: I/O to CC-Link to power to FG1
Power indicator: Green LED turns on with power supplied.
Model
Model
Model
Model
Model
Model
Model
Model
Model
Model
Model
Model
Model
Model
Model
Model
CC-Link COMMUNICATION
CC-Link: Conforms to Version 1.10
Station type: Remote device station
Station No. setting: Rotary switch; 1 – 64
(factory set to:00)
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
SPAN
ZERO
ZERO
MODEL: M2BC–[1][2]-[3]
Number of occupied stations:
M2BC-04: 1 station
M2BC-08: 2 stations
ORDERING INFORMATION
• Code number: M2BC-[1][2]-[3]
M2BC-16: 4 stations
Remote I/O (RX, RY) is fixed to 32 points.
Baud rate setting: Rotary switch
Specify a code from below for [1] through [3].
(e.g. M2BC-161-K)
(156kbps(factory setting), 625kbps, 2.5Mbps, 5Mbps,
10Mbps)
Power input specification for each I/O modules must be the
same as that of the base.
Transmission cable: Approved for CC-Link
L RUN indicator: Red LED turns on in an normal condition.
L ERR. indicator: Red LED turns on or flashes in an
abnormality; off with wire breakdown.
SD indicator: Red LED turns on when transmitting.
RD indicator: Red LED turns on when receiving.
[1] CAPACITY
04: 4 positions
08: 8 positions
16: 16 positions
[2] I/O TYPE
1: Input
INPUT SPECIFICATIONS
Input modules: Mini-M series; output 1 – 5 V DC;
(Each input must be isolated by signal conditioners. Non-
isolated modules such as M2BW is not usable.)
■ Analog Input
2: Output
[3] POWER INPUT
AC Power
Input range: See each I/O module spec.
Isolation: Transformer (by Mini-M module)
A/D conversion output: Signed binary
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
Signal range 0 – 100 % is converted into hexadecimal 0000
– 2710 (0 – 10000). -15 to 0 % is a negative range
represented by 2's complements.
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
M2BC SPECIFICATIONS
ES-5010 Rev.6 Page 1/8
http://www.m-system.co.jp/
MODEL: M2BC
■ A/D CONVERSION DATA
■ D/A CONVERSION DATA
15
14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
15
14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
SIGN
BIT
SIGN
BIT
RWr n+0
RWr n+1
RWr n+2
RWr n+3
INPUT 1 A/D CONVERSION DATA
INPUT 2 A/D CONVERSION DATA
INPUT 3 A/D CONVERSION DATA
INPUT 4 A/D CONVERSION DATA
RWw n+0
RWw n+1
RWw n+2
RWw n+3
OUTPUT 1 D/A CONVERSION DATA
OUTPUT 2 D/A CONVERSION DATA
OUTPUT 3 D/A CONVERSION DATA
OUTPUT 4 D/A CONVERSION DATA
SIGN
BIT
SIGN
BIT
SIGN
BIT
SIGN
BIT
SIGN
BIT
SIGN
BIT
SIGN
BIT
SIGN
BIT
RWr n+7
RWr n+11
RWr n+15
INPUT 8 A/D CONVERSION DATA
INPUT 12 A/D CONVERSION DATA
INPUT 16 A/D CONVERSION DATA
RWw n+7
RWw n+11
RWw n+15
OUTPUT 8 D/A CONVERSION DATA
OUTPUT 12 D/A CONVERSION DATA
OUTPUT 16 D/A CONVERSION DATA
SIGN
BIT
SIGN
BIT
SIGN
BIT
SIGN
BIT
RWr n+0 through RWr n+3 for 4 inputs.
RWr n+0 through RWr n+7 for 8 inputs.
RWr n+0 through RWr n+15 for 16 inputs.
RWw n+0 through RWw n+3 for 4 outputs.
RWw n+0 through RWw n+7 for 8 outputs.
RWw n+0 through RWw n+15 for 16 outputs.
OUTPUT SPECIFICATIONS
Output modules: Model M2VS; input 1 – 5 V DC
■ Analog Output
INSTALLATION
Power Consumption:
•AC:
Output range: See model M2VS spec.
Isolation: Transformer
approx. 6 VA without I/O module
approx. 30 VA with 4 modules (M2DY)
approx. 50 VA with 8 modules (M2DY)
approx. 90 VA with 16 modules (M2DY)
Current consumption:
D/A conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000
– 2710 (0 – 10000). -15 to 0 % is a negative range
represented by 2's complements.
•DC
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
approx. 0.25 A without I/O module
approx. 1 A with 4 modules (M2DY)
approx. 1.5 A with 8 modules (M2DY)
approx. 2.5 A with 16 modules (M2DY)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface
Weight: Without I/O module
M2BC-04 1.2 kg (2.6 lb)
M2BC-08 1.5 kg (3.3 lb)
M2BC-16 2 kg (4.4 lb)
M2BC SPECIFICATIONS
ES-5010 Rev.6 Page 2/8
http://www.m-system.co.jp/
MODEL: M2BC
PERFORMANCE in percentage of span
A/D conversion: Accuracy of input module ±0.1%
D/A conversion: Accuracy of M2VS ±0.1 %
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1000 V AC @1 minute (power to I/O
module to CC-Link module to FG1)
COMM. MODULE FRONT PANEL
PU-2
A
L
L
RUN
ERR.
E
F
SD
RD
PWR
B
C
D
STATION NO.
X
10
X1
B
RATE
A: Modular jack for factory calibration
B: Power LED
C: Station No. Setting
D: Baud rate Setting
E: Status indicator LED
F: Euro type connector terminal for CC-Link
COMMUNICATION CABLE CONNECTIONS
MASTER UNIT
M2BC
I/O UNIT
TERMINATOR
blue
DA
DB
DA
DB
DA
DB
white
yellow
DG
SLD
FG
DG
SLD
FG
DG
SLD
FG
M2BC SPECIFICATIONS
ES-5010 Rev.6 Page 3/8
http://www.m-system.co.jp/
MODEL: M2BC
EXTERNAL DIMENSIONS unit: mm (inch)
■ M2BC-041 (INPUT BASE)
210 (8.27)
190 (7.48)
170 (6.69)
1
2
3
4
5 8 5 8 5 8 5 8
1 4 1 4 1 4 1 4
FG1
13 14
CH1
CH4
2–M3 POWER
TERMINALS
**
CT PROTECTOR (CTM2)
6 (.24)
16–M3 INPUT TERMINALS
* 165 (6.50) required for pneumatic tubing for M2PV.
** Attached to M2CA and M2CE.
■ M2BC-042 (OUTPUT BASE)
210 (8.27)
190 (7.48)
170 (6.69)
6 (.24)
8–M3 OUTPUT
TERMINALS
CH1 CH2 CH3 CH4
9
12
9
12
9
12
9 12
1
2
3
4
FG1
13 14
2–M3 POWER
TERMINALS
M2BC SPECIFICATIONS
ES-5010 Rev.6 Page 4/8
http://www.m-system.co.jp/
MODEL: M2BC
■ M2BC-081 (INPUT BASE)
300 (11.81)
280 (11.02)
260 (10.24)
1
2
3
4
5
6
7
8
5 8 5 8 5 8 5 8 5 8 5 8 5 8 5 8
FG1
1 4 1 4 1 4 1 4 1 4 1 4 1 4 1 4 13 14
CH1 CH7 CH8
2–M3 POWER
TERMINALS
6 (.24)
**
CT PROTECTOR (CTM2)
32–M3 INPUT TERMINALS
* 165 (6.50) required for pneumatic tubing for M2PV.
** Attached to M2CA and M2CE.
■ M2BC-082 (OUTPUT BASE)
300 (11.81)
280 (11.02)
260 (10.24)
6 (.24)
16–M3 OUTPUT
TERMINALS
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
9
12
9
12
9
12
9
12
9
12
9
12
9
12
9
12
1
2
3
4
5
6
7
8
FG1
13 14
2–M3 POWER
TERMINALS
M2BC SPECIFICATIONS
ES-5010 Rev.6 Page 5/8
http://www.m-system.co.jp/
MODEL: M2BC
■ M2BC-161 (INPUT BASE)
480 (18.90)
460 (18.11)
440 (17.32)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
5 8 5 8 5 8 5 8 5 8 5 8
FG1
5 8 5 8 5 8 5 8 5 8
1 4 1 4 1 4 1 4 1 4
5 8 5 8 5 8 5 8 5 8
1 4 1 4 1 4 1 4 1 4
1 4 1 4 1 4 1 4 1 4 1 4 13 14
CH11 CH16
CH1
CH5
CH6
CH10
2–M3 POWER
TERMINALS
**
CT PROTECTOR (CTM2)
6 (.24)
64–M3 INPUT TERMINALS
* 165 (6.50) required for pneumatic tubing for M2PV.
** Attached to M2CA and M2CE.
■ M2BC-162 (OUTPUT BASE)
480 (18.90)
460 (18.11)
440 (17.32)
6 (.24)
32–M3 OUTPUT TERMINALS
CH1 CH2 CH3 CH4 CH5
12 12 12 12 12
CH6 CH7 CH8 CH9 CH10
12 12 12 12 12
CH11 CH12 CH13 CH14 CH15 CH16
9
9
9
9
9
9
9
9
9
9
9
12
9
12
9
12
9
12
9
12
9
12
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
FG1
13 14
2–M3 POWER
TERMINALS
M2BC SPECIFICATIONS
ES-5010 Rev.6 Page 6/8
http://www.m-system.co.jp/
MODEL: M2BC
MOUNTING REQUIREMENTS unit: mm (inch)
■ M2BC-04
190 (7.48)
4–M5 SCREW
■ M2BC-08
280 (11.02)
4–M5 SCREW
■ M2BC-16
460 (18.11)
4–M5 SCREW
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■ INPUT BASE
■ OUTPUT BASE
COMMUNICATION MODULE
INDICATOR ROTARY
I/O MODULES
1
ISOLATION
4
9
Ch.1
INPUT
5
Ch.1
OUTPUT
LED
SW
DA
DB
12
8
To Other
CC-Link
Devices
Communication
CPU
DG
SLD
FG
1
ISOLATION
4
9
Ch.2
INPUT
Ch.2
OUTPUT
A / D
or
D / A
Conv.
I / O
CPU
5
8
12
Modular Jack
for Factory
Calibration
MODULAR JACK
SERIAL
TRANSMISSION
LINE
1
4
5
8
ISOLATION
9
Ch.16*
INPUT
Ch.16*
OUTPUT
12
13
14
U(+)
V(–)
POWER
FG1
* Up to Ch.4 for M2BC-04, Ch.8 for M2BC-08.
M2BC SPECIFICATIONS
ES-5010 Rev.6 Page 7/8
http://www.m-system.co.jp/
MODEL: M2BC
Specifications are subject to change without notice.
M2BC SPECIFICATIONS
ES-5010 Rev.6 Page 8/8
http://www.m-system.co.jp/
相关型号: