M2EAXT-2R [MSYSTEM]

Super-mini Signal Conditioners with Display Mini-M M2E Series;
M2EAXT-2R
型号: M2EAXT-2R
厂家: M-SYSTEM    M-SYSTEM
描述:

Super-mini Signal Conditioners with Display Mini-M M2E Series

文件: 总8页 (文件大小:195K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: M2EAXT  
Super-mini Signal Conditioners with  
Display Mini-M M2E Series  
INPUT – Field-selectable  
Thermocouple  
(PR), K (CA), E (CRC), J (IC), T (CC), B (RH), R, S, C (WRe 5-26),  
N, U, L, P (Platinel II)  
THERMOCOUPLE ALARM  
(PC programmable, dual or quad alarm trip)  
Functions & Features  
[1] OUTPUT  
2: 4 points; N.O. or make contact  
3: 4 points; N.C. or break contact  
5: 2 points; SPDT or transfer contact  
• Accepts direct input from a thermocouple and provides a  
linearized process signal  
• Wide selection of thermocouples  
• OEL display with good visibility  
• Provides relay outputs at preset temperature input  
• Quad or dual trip  
[2] POWER INPUT  
AC Power  
• Front LCD display indicating values in scaled engineering  
unit range is used to program the module  
• Adjustable deadband (hysteresis)  
• ON delay time selectable  
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
DC Power  
R: 24 V DC  
• Hi/Lo trip and energized/de-energized coil independently  
selectable for each setpoint  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
P: 110 V DC  
• Settable with front button  
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)  
• Enclosed relays  
• Relays can be powered by 200 V AC and 100 V DC  
• High-density mounting on DIN rail  
[3] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
Typical Applications  
• Annunciator  
• Various alarm applications  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
29.5  
(1.16)  
/C02: Polyurethane coating  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
83  
(3.27)  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-5152)  
Up  
Mo  
de  
Default setting will be used if not otherwise specified.  
124  
Down  
Se  
t
(4.88)  
mm (inch)  
RELATED PRODUCTS  
• M2EA configurator software (model: M2EACFG)  
Downloadable at M-System’s web site.  
MODEL: M2EAXT–[1]-[2][3]  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual (EM-5151) for the M2EA configurator for  
applicable cable types.  
ORDERING INFORMATION  
• Code number: M2EAXT-[1]-[2][3]  
Specify a code from below for each [1] through [3].  
(e.g. M2EAXT-2-M2/Q)  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
• Specify the specification for option code /Q  
(e.g. /C01/S01/SET)  
Connection: M3 screw terminals (torque 0.8 N·m)  
Screw terminal: Chromated steel (standard) or stainless  
steel  
M2EAXT SPECIFICATIONS  
ES-5152 Rev.2 Page 1/8  
http://www.m-system.co.jp/  
MODEL: M2EAXT  
Housing material: Flame-resistant resin (gray)  
Isolation: input to L1 or L4 alarm output to L2 or L3 alarm  
output to power  
Relay rating: 100 V AC @ 4 A (cos ø = 1)  
120 V AC @ 4 A (cos ø = 1)  
240 V AC @ 2 A (cos ø = 1)  
(for output code 5, L3 alarm output and L4 alarm output is  
not available)  
30 V DC @ 4 A (resistive load)  
Maximum switching voltage: 250 V AC or 125 V DC  
Maximum switching power: 480 VA or 150 W  
Minimum load: 5 V DC @ 10 mA  
Burnout protection: Upscale standard; downscale or no  
burnout optional by programming  
(Set to "None" at item [74] Burnout, when the unit is  
connected with another instrument in parallel.)  
Cold junction compensation: CJC sensor attached to the  
input terminals  
Mechanical life: 5 × 10 cycles  
7
Alarm Trip Operation Terminal No. in parentheses  
• Example Quad N.O. contacts (LL, L, H, HH)  
Configuration: Program with front buttons or Via PC.  
Programmable features include: Refer to the parameter list.  
Configurator connection: 2.5 dia. miniature jack;  
RS-232-C level  
ON OFF  
ON OFF  
L1 (3–6)  
L2 (5–7)  
L3 (5–8)  
L4 (3–9)  
OFF ON  
OFF ON  
DISPLAY  
Input  
%
0
50  
100  
Display functions: Displays and sets measured range,  
LL  
L
H
HH  
engineering unit  
Trip operation in power failure  
Display size: Approx. 15.6 × 20.8 mm (0.61” × 0.82”)  
Number of pixels: 68 × 95 (horizontal × vertical)  
Character color: Yellow (reversing display of the current  
value and the alarm setting value when alarm is tripped)  
Display life: Approx. 60000 hours  
Output code 2 : All relays turn OFF.  
Output code 3 : All relays turn ON.  
Output code 5 : Terminals 3 – 9, 5 – 8 turn ON.  
(Expected time for the Display brightness to be reduced to  
50 % when the Display is used continuously with brightness  
setting 2 in 25 ℃)  
INSTALLATION  
Power Consumption  
AC:  
Display type: OEL display  
Max. 6 VA at 100 V  
Max. 7 VA at 200 V  
Max. 8 VA at 264 V  
DC: ≤ 2.5 W  
Display digit: Negative 5 digits, positive 6 digits (-99999 to  
999999)  
Decimal point position: None, number of decimal places 1 or  
2
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 10 to 85 %RH (non-condensing)  
Mounting: Surface or DIN rail  
INPUT SPECIFICATIONS  
Input resistance: 1 MΩ min.  
Weight: 200 g (0.44 lb)  
Burnout sensing: ≤ 0.2 μA  
Measurement rang: -5 to +105% of input setting value  
Refer to the operating manual (EM-5152-B) for changing  
input range, setting value.  
PERFORMANCE in percentage of FS input  
Accuracy: [Table 1 Accuracy value or ±0.1 % of span,  
whichever is greater + Cold Junction Compensation Error  
0.5°C (0.9°F)] ±1 digit.  
See CALCULATION EXAMPLES OF OVERALL ACCURACY.  
Cold junction compensation error:  
OUTPUT SPECIFICATIONS  
Quad Alarm  
±0.5°C at 25 ±10°C  
Relay rating: 100 V AC @ 1 A (cos ø = 1)  
120 V AC @ 1 A (cos ø = 1)  
±0.9°F at 77 ±18°F  
(The described accuracy may be partially not  
satisfied when the input temperature is below 0°C. Consult  
factory.)  
240 V AC @ 0.5 A (cos ø = 1)  
30 V DC @ 1 A (resistive load)  
Maximum switching voltage: 250 V AC or 125 V DC  
Maximum switching power: 120 VA or 30 W  
Minimum load: 5 V DC @ 10 mA  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Response time (Filter time constant: 0 sec.): ≤ 0.5 sec.  
(0 – 100 % at 90 % setpoint)  
Mechanical life: 5 × 10  
7
cycles  
Burnout response: ≤ 10 sec.  
DUAL ALARM  
M2EAXT SPECIFICATIONS  
ES-5152 Rev.2 Page 2/8  
http://www.m-system.co.jp/  
MODEL: M2EAXT  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute (input to L1 or L4  
alarm output to L2 or L3 alarm output to power to ground)  
(for output code 5, L3 alarm output and L4 alarm output is  
not available)  
CALCULATION EXAMPLES OF OVERALL ACCURACY  
[Example]  
Input Range (PR) thermocouple, 0 – 1600°C  
1) Absolute value accuracy (Table 1): 2.00°C  
2) Convert to %, 2.00°C ÷ 1600°C = 0.125 % of span  
3) 0.125 % > 0.1 % of span. ➠ 0.125 % is selected.  
4) CJC error (0.5°C) added: 0.175 % of span  
Accuracy = ±(0.175% of span + 1 digit)  
[Table 1]  
°C  
INPUT RANGE  
MINIMUM SPAN  
SETTING RANGE  
to 1760  
ACCURACY CONFORMANCE RANGE  
(PR)  
K (CA)  
E (CRC)  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
0
2ꢀ00  
100  
100  
100  
100  
2ꢀ00  
2ꢀ00  
2ꢀ00  
2ꢀ00  
100  
100  
100  
100  
0 to 1760  
-150 to +1370  
-170 to +1000  
-180 to +1200  
-170 to +400  
400 to 1760  
200 to 1760  
0 to 1760  
-270 to +1370  
-270 to +1000  
-210 to +1200  
-270 to +400  
J
(IC)  
T
(CC)  
B (RH)  
0 to 1820  
R
-50 to +1760  
-50 to +1760  
S
C (WRe 5-26)  
0
to 2315  
0 to 2315  
N
-270 to +1300  
-200 to +600  
-200 to +900  
-130 to +1300  
-200 to +600  
-200 to +900  
0 to 1395  
U
L
P (Platinel II)  
0 to 1395  
°F  
INPUT RANGE  
MINIMUM SPAN  
SETTING RANGE  
32 to 3200  
ACCURACY CONFORMANCE RANGE  
(PR)  
K (CA)  
E (CRC)  
36  
36  
36  
36  
36  
36  
36  
36  
36  
36  
36  
36  
36  
3ꢀ60  
180  
180  
180  
180  
3ꢀ60  
3ꢀ60  
3ꢀ60  
3ꢀ60  
180  
180  
180  
180  
32 to 3200  
-238 to +2498  
-274 to +1832  
-292 to +2192  
-274 to +752  
752 to 3200  
392 to 3200  
32 to 3200  
-454 to +2498  
-454 to +1832  
-346 to +2192  
-454 to +752  
32 to 3308  
J
(IC)  
T
(CC)  
B (RH)  
R
-58 to +3200  
-58 to +3200  
32 to 4199  
S
C (WRe 5-26)  
32 to 4199  
N
-454 to +2372  
-328 to +1112  
-328 to +1652  
32 to 2543  
-202 to +2372  
-328 to +1112  
-328 to +1652  
32 to 2543  
U
L
P (Platinel II)  
K
INPUT RANGE  
MINIMUM SPAN  
SETTING RANGE  
273ꢀ15 to 2033ꢀ15  
3ꢀ15 to 1643ꢀ15  
3ꢀ15 to 1273ꢀ15  
63ꢀ15 to 1473ꢀ15  
3ꢀ15 to 673ꢀ15  
273ꢀ15 to 2093ꢀ15  
223ꢀ15 to 2033ꢀ15  
223ꢀ15 to 2033ꢀ15  
273ꢀ15 to 2588ꢀ15  
3ꢀ15 to 1573ꢀ15  
73ꢀ15 to 873ꢀ15  
73ꢀ15 to 1173ꢀ15  
273ꢀ15 to 1668ꢀ15  
ACCURACY CONFORMANCE RANGE  
(PR)  
K (CA)  
E (CRC)  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
20  
2ꢀ00  
100  
100  
100  
100  
2ꢀ00  
2ꢀ00  
2ꢀ00  
2ꢀ00  
100  
100  
100  
100  
273ꢀ15 to 2033ꢀ15  
123ꢀ15 to 1643ꢀ15  
103ꢀ15 to 1273ꢀ15  
93ꢀ15 to 1473ꢀ15  
103ꢀ15 to 673ꢀ15  
673ꢀ15 to 2033ꢀ15  
473ꢀ15 to 2033ꢀ15  
273ꢀ15 to 2033ꢀ15  
273ꢀ15 to 2588ꢀ15  
143ꢀ15 to 1573ꢀ15  
73ꢀ15 to 873ꢀ15  
73ꢀ15 to 1173ꢀ15  
273ꢀ15 to 1668ꢀ15  
J
(IC)  
T
(CC)  
B (RH)  
R
S
C (WRe 5-26)  
N
U
L
P (Platinel II)  
M2EAXT SPECIFICATIONS  
ES-5152 Rev.2 Page 3/8  
http://www.m-system.co.jp/  
MODEL: M2EAXT  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1  
Measurement Category II (output)  
Installation Category II (power)  
Pollution Degree 2  
Input or output to power: Reinforced insulation (300 V)  
Input to output: Basic insulation (300 V)  
L1 or L4 alarm output to L2 or L3 alarm output:  
Basic insulation (300 V)  
RoHS Directive  
EN 50581  
EXTERNAL VIEW  
Display  
PERCENT  
50.00  
%
L4  
L3  
L2  
L1  
80.00  
70.00  
30.00  
20.00  
Up Button  
Mode Button  
Set Button  
Down Button  
Up  
Mode  
Configurator Jack  
Down  
Set  
COMPONENT  
FUNCTION  
Display  
Indicates present values, setting values and abnormal information. Two types of present values at upper  
and lower are displayed by setting.  
Mode button  
Used to shift from measuring mode to each setting mode. Destination to shift is changed by the time press-  
ing and holding the button. Used to return from each setting mode to measuring mode. (press and hold for  
2 sec. or more)  
Set button  
Used to change setting value of setting parameter. When at setting changeable state, used to enter (save)  
the setting value. Used to move on through digits of setting value for alarm setpoint value at setting change-  
able state.  
Used to release latching alarm in measuring mode (hold down more than 2 seconds).  
Up button  
Used to shift through setting parameter, and to increase or select setting value.  
Used to shift through setting parameter, and to decrease or select setting value.  
Down button  
Con!gurator Jack  
Used to con!gure with M2EA con!gurator software (model: M2EACFG). At the same time, set the lockout  
setting of the unit to ‘lock.  
Refer to the operating manual (EM-5152-B) for detailed procedures.  
M2EAXT SPECIFICATIONS  
ES-5152 Rev.2 Page 4/8  
http://www.m-system.co.jp/  
MODEL: M2EAXT  
PARAMETER LIST  
MODE  
ITEM SETTING PARAMETER  
RANGE  
UNIT  
INITIAL VALUE  
Basic setting  
01  
09  
10  
Lockout setting  
Temperature unit  
Input range  
Lock / Unlock  
°C / °F / K  
Lock  
°C  
(PR)  
K (CA)  
K (CA)  
E (CRC)  
J (IC)  
T (CC)  
B (RH)  
R
S
C (WRe 5-26)  
N
U
L
P (Platinel II)  
12  
13  
16  
0 % input setting  
100 % input setting  
Input decimal point  
(PR): 0.0 – 1740.0  
°C  
°C  
0.0  
K (CA): -270.0 – 1350.0  
E (CRC): -270.0 – 980.0  
J (IC): -210.0 – 1180.0  
T (CC): -270.0 – 380.0  
B (RH): 0.0 – 1800.0  
R: -50.0 – 1740.0  
S: -50.0 – 1740.0  
C (WRe 5-26): 0.0 – 2295.0  
N: -270.0 – 1280.0  
U: -200.0 – 580.0  
L: -200.0 – 880.0  
P (Platinel II): 0.0 – 1375.0  
(PR): 20.0 – 1760.0  
1000.0  
K (CA): -250.0 – 1370.0  
E (CRC): -250.0 – 1000.0  
J (IC): -190.0 – 1200.0  
T (CC): -250.0 – 400.0  
B (RH): 20.0 – 1820.0  
R: -30.0 – 1760.0  
S: -30.0 – 1760.0  
C (WRe 5-26): 20.0 – 2315.0  
N: -250.0 – 1300.0  
U: -180.0 – 600.0  
L: -180.0 – 900.0  
P (Platinel II): 20.0 – 1395.0  
No decimal point  
The number of decimal places : 1 or 2  
1 place of decimals  
30  
31  
32  
33  
34  
40  
41  
L1 alarm enable  
L1 alarm setpoint  
L1 trip action  
Disable / Enable  
Enable  
200.0  
Low  
-99999 – 999999  
High / Low  
*
L1 deadband  
0 – 999999  
*
1.0  
L1 coil at alarm  
L2 alarm enable  
L2 alarm setpoint  
Energized / De-energized  
Disable / Enable  
Energized  
Enable  
-99999 – 999999  
*
800.0 (2 points alarm)  
300.0 (4 points alarm)  
42  
L2 trip action  
High / Low  
High (2 points alarm)  
Low (4 points alarm)  
43  
44  
50  
51  
52  
53  
54  
L2 deadband  
0 – 999999  
*
1.0  
L2 coil at alarm  
L3 alarm enable  
L3 alarm setpoint  
L3 trip action  
Energized / De-energized  
Disable / Enable  
Energized  
Enable  
700.0  
High  
-99999 – 999999  
High / Low  
*
L3 deadband  
0 – 999999  
*
1.0  
L3 coil at alarm  
Energized / De-energized  
Energized  
M2EAXT SPECIFICATIONS  
ES-5152 Rev.2 Page 5/8  
http://www.m-system.co.jp/  
MODEL: M2EAXT  
MODE  
ITEM SETTING PARAMETER  
RANGE  
UNIT  
INITIAL VALUE  
Enable  
800.0  
High  
Basic setting  
60  
61  
62  
63  
64  
70  
71  
72  
89  
74  
77  
78  
L4 alarm enable  
L4 alarm setpoint  
L4 trip action  
Disable / Enable  
-99999 – 999999  
High / Low  
*
L4 deadband  
0 – 999999  
*
1.0  
L4 coil at alarm  
Alarm ON-delay time  
Power ON-delay time  
Latching alarm  
Alarm test  
Energized / De-energized  
0 – 999  
Energized  
0
sec.  
sec.  
0 – 999  
5
Disable / Enable  
Disable  
Cancel  
Up  
Option  
Burnout  
None / Down / Up  
Cold junction compensation CJM / FXD TEMP  
CJM  
Preset !xed terminal tem-  
perature  
-50.00 – 100.00  
*
°C  
0.00  
79  
80  
81  
01  
91  
Filter time constant  
Input Zero !ne adjust  
Input Span !ne adjust  
Lockout setting  
0 – 30  
sec.  
°C  
°C  
0
-10.00 – 10.00  
-10.00 – 10.00  
Lock / Unlock  
*
0.00  
*
0.00  
Lock  
Advanced  
Display setting  
Upper: choose from 3 types  
Lower: choose from 5 types  
1 (darkest) – 4 (brightest)  
0 (always on), 1 – 60  
OFF / RESET  
*
*
Upper: INPUT  
Lower: ALARM  
92  
93  
94  
95  
01  
Brightness  
min.  
4
Display timeout  
Reset all settings  
Version indication  
Lockout setting  
10  
OFF  
Lock / Unlock  
Lock  
* For detailed setting, refer to the operating manual (EM-5152-B).  
EXTERNAL DIMENSIONS unit: mm (inch)  
6 (.23)  
3
2
5
1
4
2–4.2x5  
6
(.17x.20)  
MTG HOLE  
6 (.24) deep  
DIN RAIL  
35mm wide  
9
8
7
11–M3  
SCREW  
11 10  
22 (.87)  
29 (1.14)  
94 (3.70)  
124 (4.88)  
29.5 (1.16)  
8
[4 (.16)]  
(.31)  
• When mounting, no extra space is needed between units.  
M2EAXT SPECIFICATIONS  
ES-5152 Rev.2 Page 6/8  
http://www.m-system.co.jp/  
MODEL: M2EAXT  
TERMINAL ASSIGNMENTS  
CJC SENSOR  
(model: CJM)  
3
2
5
4
1
6
9
8
7
11 10  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
OUTPUT CODE 3: N.C. RELAY  
OUTPUT CODE 2: N.O. RELAY  
comp. leadwire  
T/C  
+
+
1
RY  
RY  
9
6
L4 OUTPUT  
L1 OUTPUT  
COM  
9
L4 OUTPUT  
L1 OUTPUT  
Low Drift  
Amplifie  
& Burnout  
6
Digital  
Computation  
Circuit  
2
4
CJC  
SENSOR  
3
3
8
7
5
COM  
RY  
RY  
8
L3 OUTPUT  
L2 OUTPUT  
COM  
L3 OUTPUT  
L2 OUTPUT  
COM  
model: CJM  
CONFIGURATOR  
JACK  
7
5
Display  
Circuit  
10  
11  
U(+)  
POWER  
CONTROL  
SW  
V(–)  
Base Socket  
OUTPUT CODE 5: SPDT RELAY  
comp. leadwire  
N.C.  
N.O.  
COM  
N.C.  
N.O.  
COM  
U(+)  
V(–)  
9
6
T/C  
+
+
1
RY  
RY  
L1 OUTPUT  
Low Drift  
Amplifie  
& Burnout  
3
Digital  
Computation  
Circuit  
2
4
CJC  
SENSOR  
8
L2 OUTPUT  
POWER  
7
model: CJM  
CONFIGURATOR  
JACK  
5
10  
11  
Display  
Circuit  
CONTROL  
SW  
Base Socket  
Relay Protection  
• AC Powered  
• DC Powered  
Inductive  
Load (Coil)  
Inductive  
Load (Coil)  
Varistor or Spark  
Quenching Circuit  
Diode, Varistor or  
CR Circuit  
LOAD  
LOAD  
U
M2EAXT SPECIFICATIONS  
ES-5152 Rev.2 Page 7/8  
http://www.m-system.co.jp/  
MODEL: M2EAXT  
Specifications are subject to change without notice.  
M2EAXT SPECIFICATIONS  
ES-5152 Rev.2 Page 8/8  
http://www.m-system.co.jp/  

相关型号:

M2EAXT-2R/Q

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-3M2

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-3M2/Q

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-3P

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-3P/Q

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-3R

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-3R/Q

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-5M2

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-5M2/Q

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-5P

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-5P/Q

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM

M2EAXT-5R

Super-mini Signal Conditioners with Display Mini-M M2E Series
MSYSTEM