M2FV-R2/Q [MSYSTEM]

Super-mini Signal Conditioners Mini-M Series;
M2FV-R2/Q
型号: M2FV-R2/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Super-mini Signal Conditioners Mini-M Series

文件: 总4页 (文件大小:113K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: M2FV  
Super-mini Signal Conditioners Mini-M Series  
OUTPUT – Field-selectable  
Current  
4 – 20 mA DC (Load resistance 750 Ω max.)  
0 – 20 mA DC (Load resistance 750 Ω max.)  
Voltage  
SIGNAL TRANSMITTER  
(field-configurable)  
Functions & Features  
0 – 10 V DC (Load resistance 10 kΩ min.)  
2 – 10 V DC (Load resistance 10 kΩ min.)  
0 – 5 V DC (Load resistance 5000 Ω min.)  
1 – 5 V DC (Load resistance 5000 Ω min.)  
• Converts DC input from a sensor into a standard process  
signal  
• DIP switch configurable input & output range and  
response time  
• High-density mounting  
• Power indicator LED  
[1] POWER INPUT  
AC Power  
Typical Applications  
M: 85 – 264 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
• Isolation between control room and field instrumentation  
(Select ‘/N’ for ‘Standards & Approvals’ code.)  
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
23 (.91)  
DC Power  
R: 24 V DC  
Model  
76  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
R2: 11 – 27 V DC  
(2.99)  
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)  
(Select ‘/N’ for ‘Standards & Approvals’ code.)  
P: 110 V DC  
ZERO  
SPAN  
124  
(4.88)  
mm (inch)  
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)  
[2] OPTIONS (multiple selections)  
Standards & Approvals (must be specified)  
/N: Without CE  
MODEL: M2FV-[1][2]  
/CE: CE marking  
ORDERING INFORMATION  
• Code number: M2FV-[1][2]  
Other Options  
blank: none  
Specify a code from below for each of [1] and [2].  
(e.g. M2FV-M2/CE/Q)  
/Q: Option other than the above (specify the specification)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Orders will be shipped at default factory settings for Input (4  
– 20mA ) and Output (4 – 20mA ) and Response time  
(Standard responce ).  
/C02: Polyurethane coating  
/C03: Rubber coating  
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
INPUT – Field-selectable  
Current  
4 – 20 mA DC (Input resistance 50 Ω)  
0 – 20 mA DC (Input resistance 50 Ω)  
Voltage  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
0 – 10 V DC (Input resistance 100 kΩ min.)  
2 – 10 V DC (Input resistance 100 kΩ min.)  
0 – 5 V DC (Input resistance 100 kΩ min.)  
1 – 5 V DC (Input resistance 100 kΩ min.)  
Connection: M3 screw terminals (torque 0.8 N·m)  
Screw terminal: Chromated steel (standard) or stainless  
steel  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
Overrange output: Approx. -10 to +120 %  
M2FV SPECIFICATIONS  
ES-5106 Rev.7 Page 1/4  
http://www.m-system.co.jp/  
MODEL: M2FV  
Zero adjustment: -2 to +2 % (front)  
Span adjustment: 98 to 102 % (front)  
Power LED: Green LED turns on when the power is supplied.  
INPUT SPECIFICATIONS  
DC Current: Input resistor incorporated  
INSTALLATION  
Power Consumption  
AC:  
Approx. 3 VA at 100 V  
Approx. 4 VA at 200 V  
Approx. 5 VA at 264 V  
DC: Approx. 3 W  
Operating temperature: -30 to +60°C (-22 to +140°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 150 g (0.33 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.1 %  
I/O setting accuracy: ±0.2 %  
Temp. coefficient: ±0.015%/°C (±0.008%/°F)  
Response time:  
Standard response ≤ 0.5 sec. (0 – 90 %)  
Fast response ≤ 30 msec. (0 – 90 %)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
to power to ground)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Low Voltage Directive  
EN 61010-1  
Measurement Category II  
Pollution Degree 2  
Input or output to power: Reinforced insulation (300 V)  
Input to output: Basic insulation (300 V)  
RoHS Directive  
EN 50581  
M2FV SPECIFICATIONS  
ES-5106 Rev.7 Page 2/4  
http://www.m-system.co.jp/  
MODEL: M2FV  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
Input Range  
and Response Time  
Setting  
SW1  
Power LED  
1 2 3 4  
ON  
OFF  
Output Range  
Setting  
SW2  
Zero Adj.  
Span Adj.  
1 2 3 4 5 6  
ON  
OFF  
Refer to the instruction manual for detailed procedures.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
6 (.23)  
DIN RAIL  
35mm wide  
4
1
5
8
2–4.2x5  
(.17x.20)  
MTG HOLE  
6 (.24) deep  
12  
9
8–M3  
SCREW  
14 13  
21.5 (.85) 10 (.39)  
84 (3.31)  
114 (4.49)  
15 (.59)  
[4 (.16)]  
23 (.91)  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
INPUT RANGE  
& RESPONSE TIME  
SELECTOR DIP SW  
OUTPUT RANGE  
SELECTOR DIP SW  
Z
S
Isolation  
*
Output  
Driver  
Low Drift  
Amplifier  
+
1
4
5
8
9
+
INPUT  
OUTPUT  
POWER  
12  
POWER LED  
13 U(+)  
14 V(–)  
Base Socket  
* Input shunt resistor incorporated for current input.  
M2FV SPECIFICATIONS  
ES-5106 Rev.7 Page 3/4  
http://www.m-system.co.jp/  
MODEL: M2FV  
Specifications are subject to change without notice.  
M2FV SPECIFICATIONS  
ES-5106 Rev.7 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

M2G

Double-Balanced Mixer
TE

M2G

SURFACE MOUNT GENERAL RECTIFIER
SEMTECH

M2G

SMAF surface mount glass passivated rectifier
JDSU

M2G1

MEDIUM CURRENT SILICON RECTIFIERS
ETC

M2G5

MEDIUM CURRENT SILICON RECTIFIERS
ETC

M2G9

MEDIUM CURRENT SILICON RECTIFIERS
ETC

M2GA-7001-1

Lighted and non-lighted/convex versions
OMRON

M2GA-7001-3

Lighted and non-lighted/convex versions
OMRON

M2GA-99A1-H1ND

Lighted and non-lighted/convex versions
OMRON

M2GA-99A1-H1NG

Lighted and non-lighted/convex versions
OMRON

M2GA-99A1-H1NW

Lighted and non-lighted/convex versions
OMRON

M2GB120DA-3

HIGH BRIGHTNESS GREEN LED LAMP
MICRO-ELECTRO