M2XM2-1Z1-R/CE [MSYSTEM]
Super-mini Signal Conditioners Mini-M Series;型号: | M2XM2-1Z1-R/CE |
厂家: | M-SYSTEM |
描述: | Super-mini Signal Conditioners Mini-M Series |
文件: | 总4页 (文件大小:109K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M2XM2
Super-mini Signal Conditioners Mini-M Series
[1] OUTPUT
Current
Z1: Range 0 – 20 mA DC
Voltage
POTENTIOMETER TRANSMITTER
(PC programmable)
V1: Range -2.5 – +2.5 V DC
Functions & Features
V2: Range -10 – +10 V DC
• Provides a DC output proportional to a potentiometer or
slidewire position input
(Configurator software is used to change output over the
described range of the selected suffix code. For changing
out of this range, set the Output Range Selectors inside the
unit before software adjustment.)
• PC programmable
• Potentiometer’s zero/span points can be captured by on-
site calibrations
Typical Applications
[2] POWER INPUT
• Tank levels
AC Power
• Positions: Compensating non-linear signal from the linking
mechanism of a position detector
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
(90 – 264 V for UL)
DC Power
23 (.91)
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
M
od
el
76
(2.99)
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
(110 V ±10 % for UL)
124
(4.88)
[3] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N: Without CE or UL
mm (inch)
/CE: CE marking
/UL: UL approval, CE marking
Other Options
MODEL: M2XM2–1[1]–[2][3]
blank: none
/Q: Option other than the above (specify the specification)
ORDERING INFORMATION
• Code number: M2XM2-1[1]-[2][3]
Specify a code from below for each [1] through [3].
(e.g. M2XM2-1Z1-R/CE/Q)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Input range (e.g. 0 – 500 Ω)
• Output range (e.g. 4 – 20 mA DC)
• Specify the specification for option code /Q
(e.g. /C01/S01/SET)
/C02: Polyurethane coating
/C03: Rubber coating (UL not available)
TERMINAL SCREW MATERIAL
/S01: Stainless steel (UL not available)
EX-FACTORY SETTING
INPUT POTENTIOMETER
1: Total resistance 100 Ω – 10 kΩ
(Configurator software is used to change input range
(total resistance).)
/SET: Preset according to the Ordering Information Sheet
(No. ESU-5093)
RELATED PRODUCTS
• PC configurator software (model: JXCON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
M2XM2 SPECIFICATIONS
ES-5093 Rev.10 Page 1/4
http://www.m-system.co.jp/
MODEL: M2XM2
Output range: -10 – +10 V DC
GENERAL SPECIFICATIONS
Construction: Plug-in
Minimum span: 1 V
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless
steel
Load resistance: Output drive 1 mA max.
(e.g. 1 – 5 V: 5000 Ω [5 V ÷ 1 mA])
If not specified, the output range is shown below.
V1: 0 – 1 V DC
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -15 to +115 %
(Negative current output is not provided.)
Manual zero adjustments: -5 to +5 %
(factory setting: 0 %)
V2: 1 – 5 V DC
Manual span adjustments: 95 to 105 %
(factory setting: 100 %)
INSTALLATION
Power Consumption
Programming: Downloaded from PC; linearization (100
points), input range (total resistance), output range, zero
and span, simulating output, etc.
•AC:
Approx. 3 VA at 100 V
Approx. 4 VA at 200 V
Burnout: Upscale standard; downscale or no burnout
optional by programming
Approx. 5 VA at 264 V
•DC: Approx. 2 W
Status indicator LED: Blinking patterns indicate different
operating status of the transmitter.
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
Operating temperature: -30 to +60°C (-22 to +140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 120 g (0.26 lb)
INPUT SPECIFICATIONS
•Potentiometer: 100 Ω – 10 kΩ
Range : Minimum span
PERFORMANCE in percentage of span
Accuracy: Input accuracy + output accuracy
Inversely proportional to the span.
Input accuracy: (% of max. input range)
(Range)
0 – 100 Ω : 2.5 Ω
0 – 300 Ω : 3.0 Ω
0 – 1000 Ω : 10 Ω
0 – 100 Ω : ±0.02 %
0 – 10 kΩ : 10 Ω
0 – 300 Ω : ±0.02 %
Excitation: ≤ 0.5 V DC at 1000 Ω
If not specified, default value is 1000 Ω.
0 – 1000 Ω : ±0.01 %
0 – 10 kΩ : ±0.02 %
Output accuracy: ±0.04 % of max. output range
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span
at -5 to +55°C [23 to 131°F]
OUTPUT SPECIFICATIONS
■ DC Current
Response time: ≤ 0.9 sec. (0 – 90 %)
Burnout response time: ≤ 30 sec.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
Operational range: 0 – 24 mA DC
Output range: 0 – 20 mA DC
Minimum span: 1 mA
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
Load resistance: Output drive 15 V max.
(e.g. 4 – 20 mA: 750 Ω [15 V ÷ 20 mA])
If not specified, the output range is 4 – 20 mA DC.
■ DC Voltage
CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example] Input Type 0 – 1000 Ω, Input Range 250 – 750 Ω
,Output Type 0 – 20 mA, Output Range 4 – 20 mA
Max. Input Range (1000 Ω) ÷ Span (500 Ω) × 0.01 %
= 0.02 %
Code V1 (narrow spans)
Operational range: -3 – +3 V DC
Output range: -2.5 – +2.5 V DC
Minimum span: 250 mV
Max. Output Range (20 mA) ÷ Span (16 mA) × 0.04 %
= 0.05 %
Code V2 (wide spans)
Overall accuracy = 0.02 % + 0.05 % = ±0.07 %
Operational range: -11.5 – +11.5 V DC
M2XM2 SPECIFICATIONS
ES-5093 Rev.10 Page 2/4
http://www.m-system.co.jp/
MODEL: M2XM2
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
RoHS Directive
EN 50581
Approval:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
EXTERNAL VIEW
■ LEFT SIDE VIEW
(with cover removed)
■ FRONT VIEW (with cover open)
ATT
SW3
[e.g.]
Output code V1
V
I
Configurator Jack
Status Indicator LED
Zero/Span Selector
SW6
SW2
8
7
6
5
4
3
2
1
Top: SPAN
Middle: OFF
Bottom: ZERO
V
I
N
O
SW7
SW4
UP/DOWN Switches
Output Range Selectors
The front cover cannot be turned open by 180 deg.
when there is no extra space between units.
Refer to the instruction manual for detailed procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
6 (.23)
DIN RAIL
35mm wide
4
1
5
8
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
12
9
8–M3
SCREW
14 13
21.5 (.85) 7.3 (.29)
86.7 (3.41)
116.7 (4.59)
15 (.59)
[4 (.16)]
23 (.91)
• When mounting, no extra space is needed between units.
M2XM2 SPECIFICATIONS
ES-5093 Rev.10 Page 3/4
http://www.m-system.co.jp/
MODEL: M2XM2
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS
ZERO/SPAN
SELECTOR
OUTPUT RANGE
SELECTORS
Isolation
POTENTIOMETER
max.
Digital
Computation
Output
Driver
+
1
9
+
3
2
1
Low Drift
Amplifier
& Burnout
OUTPUT
POWER
4
12
13
14
–
UP/DOWN
SWITCHES
–
5
U(+)
V(–)
min.
8
JACK
CONFIGURATOR
Base Socket
Specifications are subject to change without notice.
M2XM2 SPECIFICATIONS
ES-5093 Rev.10 Page 4/4
http://www.m-system.co.jp/
相关型号:
©2020 ICPDF网 联系我们和版权申明