M3LU-R4/B/Q [MSYSTEM]

Space-saving Signal Conditioners M3-UNIT Series;
M3LU-R4/B/Q
型号: M3LU-R4/B/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Space-saving Signal Conditioners M3-UNIT Series

文件: 总6页 (文件大小:158K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: M3LU  
RTD  
Space-saving Signal Conditioners M3-UNIT Series  
Pt 100, Pt 200, Pt 300, Pt 400, Pt 500, Pt 1000,  
Ni 100, Ni 120, Ni 508.4Ω, Ni-Fe 604,  
Cu 10 @25°C, Pt 50Ω, JPt 100  
Potentiometer  
UNIVERSAL TRANSMITTER  
(field- and PC-configurable)  
Functions & Features  
Total resistance 80 – 4000 Ω  
Resistance  
• Universal input: mV, V, mA, T/C, RTD, resistance and  
potentiometer  
0 – 4000 Ω  
• Easy ‘One-Step Cal’ calibration using the front three  
control buttons without needing a PC; PC software is also  
usable.  
OUTPUT – Field-selectable  
Current  
• I/O type and ranges are configurable  
• Front control button function can be locked  
0 – 20 mA DC  
Voltage  
-2.5 – +2.5 V DC  
-10 – +10 V DC  
Typical Applications  
• Signal conversion between control room and field  
instrumentation with isolation  
• Ideal for use as a fast solution, multifunctional spare part  
18 (.71)  
[1] POWER INPUT  
AC Power  
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,  
47 – 66 Hz)  
(‘/UL’ is not selectable for ‘Standards & Approvals’ code.)  
DC Power  
106  
(4.17)  
R4: 10 – 32 V DC  
(Operational voltage range 9 - 36 V, ripple 10 %p-p max.)  
110.5 (4.35)  
mm (inch)  
[2] CONFIGURATION OPTIONS  
A: PC and field configurable  
B: Field configurable  
MODEL: M3LU–[1]/[2][3]  
[3] OPTIONS (multiple selections)  
Standards & Approvals  
ORDERING INFORMATION  
• Code number: M3LU-[1]/[2][3]  
Specify a code from below for each [1] through [3].  
(e.g. M3LU-R4/A/UL/Q)  
blank: CE marking  
/UL: UL approval, CE marking  
Other Options  
• Specify the specification for option code /Q  
(e.g. /C01)  
blank: none  
/Q: Option other than the above (specify the specification)  
• Use Ordering Information Sheet (No. ESU-2652).  
Factory setting (indicated below) will be used if not  
otherwise specified.  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Input: 4 – 20 mA  
Output: 4 – 20 mA  
/C02: Polyurethane coating  
/C03: Rubber coating (UL not available)  
INPUT – Field-selectable  
DC Current & Voltage  
RELATED PRODUCTS  
Current: 0 – 20 mA DC  
• PC configurator software (model: M3CFG)  
Downloadable at M-System’s web site.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
Millivolt: -1000 – +1000 mV DC  
Voltage: -10 – +10 V DC  
Thermocouple  
(PR), K (CA), E (CRC), J (IC), T (CC), B (RH), R, S, C (WRe 5-26),  
N, U, L, P (Platinel II)  
M3LU SPECIFICATIONS  
ES-2652 Rev.20 Page 1/6  
http://www.m-system.co.jp/  
MODEL: M3LU  
Excitation: 0.2 mA ± 10 %  
GENERAL SPECIFICATIONS  
Allowable leadwire resistance: Max. 20 Ω per wire  
Resistance (2-wire, 3-wire or 4-wire)  
Excitation: 0.2 mA ±10 %  
Construction: Small-sized front terminal structure  
Connection: Euro type connector terminal  
(applicable wire size: 0.2 to 2.5 mm2, stripped length: 8  
Allowable leadwire resistance: Max. 20 Ω per wire  
■ Potentiometer  
mm)  
Housing material: Flame-resistant resin (gray)  
Isolation: Input to output to power  
Excitation: 0.2 mA ±10 %  
Allowable leadwire resistance: Max. 20 Ω per wire  
Overrange output: -15 to +115 %  
Zero adjustment: -15 to +15 % (front)  
Span adjustment: 85 to 115 % (front)  
Burnout (other than current or voltage (V) input): Upscale,  
downscale or no burnout selectable; Also detects wire  
breakdown and overrange input exceeding the electrical  
design limit for DC input.  
OUTPUT SPECIFICATIONS  
Output type and range are as follows.  
For type and range configuration, refer to the instruction  
manual.  
■ DC Current  
Linearization (thermocouple & RTD input): Standard  
Cold junction compensation (T/C): CJC sensor (included) to  
be attached to the input terminals  
Maximum range: 0 – 20 mA DC  
Minimum span: 1 mA  
Conformance range: 0 – 24 mA DC  
(Negative overrange current below 0 mA is not available.)  
Offset: Lower range can be any specific value within the  
output range provided that the minimum span is  
maintained.  
Status indicator LED: Tri-color (green/amber/red) LED;  
Blinking patterns indicate operation status of the  
transmitter.  
Configuration:  
PC Configurator: (Model: M3LUCFG) via Windows PC  
connected to th front jack.  
Load resistance: Output drive 15 V maximum at 22 mA  
DC Voltage  
Programmable features include:  
Narrow Spans  
• I/O type and range  
Maximum range: -2.5 – +2.5 V DC  
Minimum span: 250 mV  
• Zero and span adjustments  
• Burnout action  
Conformance range: -3 – +3 V DC  
Wide Spans  
• User’s linearization table setting  
• User’s T/C, RTD table setting  
Maximum range: -10 – +10 V DC  
Minimum span: 1 V  
(Refer to the instruction manual)  
‘One-Step Cal’ calibration: With I/O type and the full-scale  
range configured via the internal DIP switches, precise 0 %  
and 100 % ranges are calibrated via the front control  
buttons with a help of LED. Also I/O calibration and fine  
adjustment are available with a PC.  
Conformance range: -11.5 – +11.5 V DC  
Offset: Lower range can be any specific value within the  
output range provided that the minimum span is  
maintained.  
Load resistance: Output drive 10 mA maximum; 5 mA for  
negative output  
Configurator connection: 2.5 dia. miniature jack;  
RS-232-C level  
INSTALLATION  
Power Consumption  
INPUT SPECIFICATIONS  
Input type and range are configurable. See Table 1 for the  
available input type, the minimum span, the maximum  
range, the conformance range and the input conversion  
accuracy.  
AC:  
Approx. 4 VA at 100 V  
Approx. 5 VA at 200 V  
Approx. 6 VA at 264 V  
For type and range configuration, refer to the instruction  
manual.  
DC: Approx. 2 W  
Operating temperature: -25 to +65°C (-13 to +149°F)  
Max. 55°C (131°F) for UL approval  
Operating humidity: 0 to 95 %RH (non-condensing)  
Mounting: DIN rail  
DC current: 50 Ω resistor incorporated  
DC mV & voltage  
Input resistance: ≥ 1 MΩ  
Thermocouple  
Weight: 100 g (3.53 oz)  
Input resistance: ≥ 1 MΩ  
Burnout sensing: 130 nA ± 10 %  
RTD (2-wire, 3-wire or 4-wire)  
M3LU SPECIFICATIONS  
ES-2652 Rev.20 Page 2/6  
http://www.m-system.co.jp/  
MODEL: M3LU  
0.75°C ÷ (150 – 50)°C × 100 = 0.75 % > 0.1 %  
➠ Overall accuracy including CJC error = ±0.75 % of span  
PERFORMANCE  
Accuracy: See Table 1.  
Cold junction compensation error:  
±0.5°C maximum at 10 – 40°C  
RTD  
1) Pt 100, -200 – 800°C  
±1.0°C maximum at 0 – 50°C  
Absolute value accuracy (Table 1): 0.15°C  
0.15°C ÷ (800 – -200)°C × 100 = 0.015 % < 0.1 %  
➠ Overall accuracy = ±0.1 % of span  
±0.9°F maximum at 50 – 104°F  
±1.8°F maximum at 32 – 122°F  
Temp. coefficient:  
±0.015 %/°C [±0.008 %/°F] at -5 to +55°C [23 to 131°F] of  
max. range  
2) Pt 100, 0 – 100°C  
Absolute value accuracy (Table 1): 0.15°C  
0.15°C ÷ 100°C × 100 = 0.15 % > 0.1 %  
➠ Overall accuracy = ±0.15 % of span  
±0.03 %/°C [±0.016 %/°F] for the following conditions:  
• DC, T/C input spans ≤ 10 mV  
• RTD, potentiometer, resistance spans ≤ 80 Ω  
• in an ambient exceeding 55°C [131°F] or below -5°C  
[23°F]  
STANDARDS & APPROVALS  
EU conformity:  
Response time: ≤ 0.2 sec. (0 – 90 %, DC input)  
With the Option A, the Sync Filter set to the fastest  
frequency on the PC Configurator Software. Default is set to  
have 0.5 sec. response.  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
Burnout response: ≤ 10 sec.  
Low Voltage Directive  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength  
EN 61010-1  
Installation Category II  
Pollution Degree 2  
AC powered: 2000 V AC @ 1 minute  
(input to output to power to ground)  
DC powered: 1500 V AC @ 1 minute  
(input to output or power to ground)  
500 V AC @ 1 minute (output to power)  
Input or output to power: Reinforced insulation (300 V)  
Input to output: Basic insulation (300 V)  
RoHS Directive  
EN 50581  
Approval:  
UL/C-UL general safety requirements  
(UL 61010-1, CAN/CSA-C22.2 No.1010-1)  
CALCULATION EXAMPLES OF OVERALL ACCURACY  
■ CALCULATION EXAMPLES OF OVERALL ACCURACY IN %  
DC Voltage  
1) 0 – 200 mV  
Absolute value accuracy (Table 1): 40μV  
40μV ÷ 200000μV × 100 = 0.02 % < 0.1 %  
➠ Overall accuracy = ±0.1 % of span  
2) 0 – 4 mV  
Absolute value accuracy (Table 1): 10μV  
10μV ÷ 4000μV × 100 = 0.25 % > 0.1 %  
➠ Overall accuracy = ±0.25 % of span  
Thermocouple  
1) K thermocouple, 0 – 1000°C  
Absolute value accuracy (Table 1): 0.25°C  
CJC error (0.5°C) added: 0.75°C  
0.75°C ÷ 1000°C × 100 = 0.075 % < 0.1 %  
➠ Overall accuracy including CJC error = ±0.1 % of span  
2) K thermocouple, 50 – 150°C  
Absolute value accuracy (Table 1): 0.25°C  
CJC error (0.5°C) added: 0.75°C  
M3LU SPECIFICATIONS  
ES-2652 Rev.20 Page 3/6  
http://www.m-system.co.jp/  
MODEL: M3LU  
EXTERNAL VIEW  
FRONT VIEW  
SIDE VIEW  
LED1 (LD1)  
10 11 12  
LED2 (LD2)  
LED3 (LD3)  
MODE Button  
UP Button  
Configuration DIP SW  
7
8
9
4 3 2 1  
OFF  
ON  
DOWN Button  
SW1  
Configurator Jack  
SW2  
SW3  
8 7 6 5 4 3 2 1  
OFF  
1
JP2  
2 3  
*
4
5
6
ON  
*For Voltage Input (V) range, switch the JP2 jumper to the 2 – 3 position.  
Normal Position  
(other than DC Voltage [V] range)  
DC Voltage [V] Range Position  
JP2  
JP2  
1
2
3
1
2
3
The DIP switch setting is required to select output types before setting a precise output range using the PC configurator  
software.  
For detailed information on the configuration and calibration, refer to the instruction manual.  
M3LU SPECIFICATIONS  
ES-2652 Rev.20 Page 4/6  
http://www.m-system.co.jp/  
MODEL: M3LU  
INPUT TYPE, RANGE & ACCURACY  
INPUT TYPE, RANGE & ACCURACY  
TABLE 1  
1
*
INPUT TYPE  
DC Current  
DC Millivolt  
MIN. SPAN MAXIMUM RANGE  
ACCURACY  
±0.1ꢀ  
1mA  
4mV  
0 to 20mA  
-1000 to +1000mV  
±10µV at F.S. input ≤ 50mV  
±40µV at F.S. input ≤ 200mV  
±±0µV at F.S. input ≤ 500mV  
±ꢁ0µV at F.S. input > 500mV  
DC Voltage  
Potentiometer  
Resistance  
1V  
2ꢀ  
10Ω  
-10 to +10V  
±0.1ꢀ  
±0.1Ω  
±0.1Ω  
total resistance ꢁ0 to 4000Ω  
0 to 4000Ω  
°C  
°F  
Thermocouple  
MIN.  
MAXIMUM  
RANGE  
CONFORMANCE  
RANGE  
MIN.  
MAXIMUM  
RANGE  
CONFORMANCE  
1
1
*
*
ACCURACY  
ACCURACY  
SPAN  
SPAN  
RANGE  
(PR)  
K (CA)  
E (CRC)  
20  
20  
20  
0 to 17±0  
-270 to +1370  
-270 to +1000  
0 to 17±0  
-150 to +1370  
-170 to +1000  
±1.00  
±0.25  
±0.20  
3±  
3±  
3±  
32 to 3200  
-454 to +249ꢁ  
-454 to +1ꢁ32  
32 to 3200  
-23ꢁ to +249ꢁ  
-274 to +1ꢁ32  
±1.ꢁ0  
±0.45  
±0.3±  
J (IC)  
T (CC)  
B (RH)  
20  
20  
20  
-210 to +1200  
-270 to +400  
100 to 1ꢁ20  
-1ꢁ0 to +1200  
-170 to +400  
400 to 17±0  
±0.25  
±0.25  
±0.75  
3±  
3±  
3±  
-34± to +2192  
-454 to +752  
212 to 330ꢁ  
-292 to +2192  
-274 to +752  
752 to 3200  
±0.45  
±0.45  
±1.35  
R
20  
20  
20  
-50 to +17±0  
-50 to +17±0  
0 to 2315  
200 to 17±0  
0 to 17±0  
0 to 2315  
±0.50  
±0.50  
±0.25  
3±  
3±  
3±  
-5ꢁ to +3200  
-5ꢁ to +3200  
32 to 4199  
392 to 3200  
32 to 3200  
32 to 4199  
±0.90  
±0.90  
±0.45  
S
C(WRe 5-2±)  
N
20  
20  
20  
20  
-270 to +1300  
-200 to +±00  
-200 to +900  
0 to 1395  
-130 to +1300  
-200 to +±00  
-200 to +900  
0 to 1395  
±0.30  
±0.20  
±0.25  
±0.25  
3±  
3±  
3±  
3±  
-454 to +2372  
-32ꢁ to +1112  
-32ꢁ to +1±52  
32 to 2543  
-202 to +2372  
-32ꢁ to +1112  
-32ꢁ to +1±52  
32 to 2543  
±0.54  
±0.3±  
±0.45  
±0.45  
U
L
P (Platinel II)  
°C  
°F  
RTD  
1
1
ACCURACY*  
ACCURACY*  
MIN.SPAN  
MAXIMUM RANGE  
MIN.SPAN  
MAXIMUM RANGE  
Pt 100 (JIS ’97, IEC)  
Pt 200  
Pt 300  
20  
20  
20  
-200 to +ꢁ50  
-200 to +ꢁ50  
-200 to +ꢁ50  
±0.15  
±0.15  
±0.15  
3±  
3±  
3±  
-32ꢁ to +15±2  
-32ꢁ to +15±2  
-32ꢁ to +15±2  
±0.27  
±0.27  
±0.27  
Pt 400  
Pt 500  
Pt 1000  
20  
20  
20  
-200 to +ꢁ50  
-200 to +ꢁ50  
-200 to +ꢁ50  
±0.15  
±0.15  
±0.15  
3±  
3±  
3±  
-32ꢁ to +15±2  
-32ꢁ to +15±2  
-32ꢁ to +15±2  
±0.27  
±0.27  
±0.27  
Pt 50Ω (JIS ’ꢁ1)  
JPt 100 (JIS ’ꢁ9)  
Ni 100  
20  
20  
20  
-200 to +±49  
-200 to +510  
-ꢁ0 to +2±0  
±0.15  
±0.15  
±0.15  
3±  
3±  
3±  
-32ꢁ to +1200  
-32ꢁ to +950  
-112 to +500  
±0.27  
±0.27  
±0.27  
Ni 120  
20  
20  
20  
20  
-ꢁ0 to +2±0  
-50 to +200  
-200 to +200  
-50 to +250  
±0.15  
±0.15  
±0.15  
±0.50  
3±  
3±  
3±  
3±  
-112 to +500  
-5ꢁ to +392  
-32ꢁ to +392  
-5ꢁ to +4ꢁ2  
±0.27  
±0.27  
±0.27  
±0.90  
Ni 50ꢁ.4Ω  
Ni-Fe ±04  
Cu 10 @25°C  
*1. DC, RTD, Resistance, Potentiometer input: Or ±0.1ꢀ oꢂ span, ꢃhichever is greater.  
Thermocouple input: [Accuracy + Cold Junction Compensation Error 0.5°C (0.9°F)] or ±0.1ꢀ oꢂ span, ꢃhichever is greater.  
For current output, overall accuracy degrades another 0.1ꢀ ꢃith spans ≤ 2mA.  
M3LU SPECIFICATIONS  
ES-2652 Rev.20 Page 5/6  
http://www.m-system.co.jp/  
MODEL: M3LU  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
10 11 12  
7
8
9
DIN RAIL  
35mm wide  
1
4
2
5
3
6
110.5 (4.35)  
[5 (.20)]  
CJC SENSOR  
(model: CJM)  
*
18 (.71)  
*Used only with a thermocouple input  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
DC POWERED TYPE  
STATUS  
CONTROL BUTTONS  
2-wire  
RTD  
3-wire  
RTD  
4-wire  
RTD  
POT.  
DIP SW  
Isolation  
max.  
+
Low Drift  
Amplifier  
Input  
Circuit  
Input  
Computation  
Output  
Computation  
Output  
Driver  
+
3
A
A
A
1
7
8
OUTPUT  
DC  
T/C  
ext. wire  
B
B
2
+
+
3
10  
11  
12  
9
+
VOLT  
mA  
+
+
2
1
A
B
4
**  
DC POWER  
mV  
*
B
B
5
CJC  
SENSOR  
min.  
6
CONFIGURATOR  
JACK  
AC POWERED TYPE  
STATUS  
CONTROL BUTTONS  
2-wire  
RTD  
3-wire  
RTD  
4-wire  
RTD  
POT.  
DIP SW  
Isolation  
max.  
+
Low Drift  
Amplifier  
Input  
Circuit  
Input  
Computation  
Output  
Computation  
Output  
Driver  
+
3
A
A
A
1
7
8
OUTPUT  
DC  
T/C  
ext. wire  
B
B
2
+
+
3
10  
11  
12  
9
U
+
VOLT  
mA  
**  
AC POWER  
+
2
1
A
B
4
mV  
*
B
B
5
V
CJC  
SENSOR  
min.  
6
CONFIGURATOR  
JACK  
* Replace the Terminal Block (4 – 5 – 6) with the one  
connected with the CJC Sensor, included in the package.  
The CJC Sensor is secured to the terminal 6.  
Loosen only the terminal 4 – 5 and connect the T/C extension wires.  
** Be aware that the AC power and DC power connect to different terminals.  
Specifications are subject to change without notice.  
M3LU SPECIFICATIONS  
ES-2652 Rev.20 Page 6/6  
http://www.m-system.co.jp/  

相关型号:

M3LU-R4/B/UL

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU2

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU2-M2/A

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU2-M2/A/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU2-M2/B

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU2-M2/B/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU2-R4/A

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU2-R4/A/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU2-R4/B

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LU2-R4/B/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LV-R4/A

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM

M3LV-R4/A/Q

Space-saving Signal Conditioners M3-UNIT Series
MSYSTEM