MODEL: M3SVS  
GW: -1 – +1 mA DC (Input resistance 1000 Ω)  
Super-space-saving Signal Conditioners  
M3S-UNIT Series  
FW: -10 – +10 mA DC (Input resistance 100 Ω)  
Z: Specify current (See INPUT SPECIFICATIONS)  
Voltage  
SIGNAL TRANSMITTER  
Functions & Features  
1: 0 – 10 mV DC (Input resistance 10 kΩ min.)  
15: 0 – 50 mV DC (Input resistance 10 kΩ min.)  
16: 0 – 60 mV DC (Input resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Input resistance 100 kΩ min.)  
3: 0 – 1 V DC (Input resistance 1 MΩ min.)  
4: 0 – 10 V DC (Input resistance 1 MΩ min.)  
5: 0 – 5 V DC (Input resistance 1 MΩ min.)  
6: 1 – 5 V DC (Input resistance 1 MΩ min.)  
4W: -10 – +10 V DC (Input resistance 1 MΩ min.)  
5W: -5 – +5 V DC (Input resistance 1 MΩ min.)  
0: Specify voltage (See INPUT SPECIFICATIONS)  
• Accepts a DC mV, V or mA input and provides an isolated  
DC signal  
• Universal AC/DC power input  
• High-density mounting  
Typical Applications  
• Signal conversion between control room and field  
instrumentation with isolation  
• Ideal for use as a fast solution, multifunctional spare part  
[2] OUTPUT  
12 (.47)  
Current  
A: 4 – 20 mA DC (Load resistance 550 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1100 Ω max.)  
C: 1 – 5 mA DC (Load resistance 2200 Ω max.)  
D: 0 – 20 mA DC (Load resistance 550 Ω max.)  
E: 0 – 16 mA DC (Load resistance 680 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1100 Ω max.)  
G: 0 – 1 mA DC (Load resistance 11 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
106  
(4.17)  
110.5 (4.35)  
mm (inch)  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 1000 Ω min.)  
4: 0 – 10 V DC (Load resistance 10 kΩ min.)  
5: 0 – 5 V DC (Load resistance 5000 Ω min.)  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
4W: -10 – +10 V DC (Load resistance 10 kΩ min.)  
5W: -5 – +5 V DC (Load resistance 5000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
MODEL: M3SVS–[1][2]–[3][4]  
ORDERING INFORMATION  
• Code number: M3SVS-[1][2]-[3][4]  
Specify a code from below for each of [1] through [4].  
(e.g. M3SVS-6A-M2/K/Q)  
• Special input and output ranges (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01)  
[3] POWER INPUT  
AC Power  
[1] INPUT  
Current  
M2: 100 – 240 V AC (Operational voltage range 90 – 264 V,  
47 – 66 Hz)  
A: 4 – 20 mA DC (Input resistance 250 Ω)  
A1: 4 – 20 mA DC (Input resistance 50 Ω)  
B: 2 – 10 mA DC (Input resistance 500 Ω)  
C: 1 – 5 mA DC (Input resistance 1000 Ω)  
D: 0 – 20 mA DC (Input resistance 50 Ω)  
E: 0 – 16 mA DC (Input resistance 62.5 Ω)  
F: 0 – 10 mA DC (Input resistance 100 Ω)  
G: 0 – 1 mA DC (Input resistance 1000 Ω)  
H: 10 – 50 mA DC (Input resistance 100 Ω)  
J: 0 – 10 μA DC (Input resistance 1000 Ω)  
K: 0 – 100 μA DC (Input resistance 1000 Ω)  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
Universal  
AD: 100 – 240 V AC / 24 – 240 V DC (universal)  
(Operational voltage range 90 - 264 V AC, 47 - 66 Hz /  
21.6 - 264 V DC, ripple 10 %p-p max.)  
M3SVS SPECIFICATIONS  
ES-7718 Rev.9 Page 1/3  
http://www.m-system.co.jp/  
MODEL: M3SVS  
Approx. 2 VA at 100 V  
Approx. 3 VA at 200 V  
Approx. 4 VA at 264 V  
DC: Approx. 1 W  
[4] OPTIONS (multiple selections)  
Response Time (0 – 90 %)  
blank: Standard (≤ 0.5 sec.)  
/K: Fast Response (Approx. 25 msec.)  
Other Options  
Operating temperature: -10 to +55°C (14 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: DIN rail  
blank: none  
/Q: Option other than the above (specify the specification)  
Weight: 100 g (0.22 lb)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
PERFORMANCE in percentage of span  
Accuracy: ±0.1 %  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
to power to ground)  
/C02: Polyurethane coating  
/C03: Rubber coating  
GENERAL SPECIFICATIONS  
Construction: Small-sized front terminal structure  
Connection: Euro type connector terminal  
STANDARDS & APPROVALS  
EU conformity:  
Applicable wire size: 0.2 to 2.5 mm , stripped length 8 mm  
2
Housing material: Flame-resistant resin (gray)  
Isolation: Input to output to power  
EMC Directive  
EMI EN 61000-6-4  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
EMS EN 61000-6-2  
Low Voltage Directive  
Span adjustment: 95 to 105 % (front)  
EN 61010-1  
Measurement Category II (input)  
Installation Category II (power)  
Pollution Degree 2  
INPUT SPECIFICATIONS  
DC Current: Input resistor incorporated  
Specify input resistance value for code Z.  
Input or output to power: Reinforced insulation (300 V)  
Input to output: Basic insulation (300 V)  
RoHS Directive  
(R ≤ 0.25 W ÷ [F.S. Current] )  
2
DC Voltage: -300 – +300 V DC  
Minimum span: 3 mV  
EN 50581  
Offset: Max. 1.5 times span  
Input resistance  
Span 3 – 10 mV : ≥ 10 kΩ  
Span 10 – 100 mV : ≥ 10 kΩ  
Span 0.1 – 1 V : ≥ 100 kΩ  
Span ≥ 1 V : ≥ 1 MΩ  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 11 V max.  
DC Voltage: -10 – +11 V DC  
Minimum span: 5 mV  
Offset: Max. 1.5 times span  
Load resistance: Output drive 1 mA maximum; at ≥ 0.5 V  
INSTALLATION  
Power consumption  
AC:  
M3SVS SPECIFICATIONS  
ES-7718 Rev.9 Page 2/3  
http://www.m-system.co.jp/  
MODEL: M3SVS  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
7
5
8
6
DIN RAIL  
35mm wide  
1
3
2
4
12  
(.47)  
110.5 (4.35)  
[5 (.20)]  
• When mounting, no extra space is needed between units.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Z
S
Isolation  
Low Drift  
Amplifier  
Output  
Driver  
+
+
3
4
1
2
5
6
7
8
INPUT  
OUTPUT  
*
U(+)  
V(–)  
POWER  
*Shunt resistor incoporated for current input.  
Specifications are subject to change without notice.  
M3SVS SPECIFICATIONS  
ES-7718 Rev.9 Page 3/3  
http://www.m-system.co.jp/  

M3SVS-A12-AD/Q 相关器件

型号 制造商 描述 价格 文档
M3SVS-A12-M2 MSYSTEM Super-space-saving Signal Conditioners M3S-UNIT Series 获取价格
M3SVS-A12-M2/K MSYSTEM Super-space-saving Signal Conditioners M3S-UNIT Series 获取价格
M3SVS-A12-M2/Q MSYSTEM Super-space-saving Signal Conditioners M3S-UNIT Series 获取价格
M3SVS-A12-R MSYSTEM Super-space-saving Signal Conditioners M3S-UNIT Series 获取价格
M3SVS-A12-R/K MSYSTEM Super-space-saving Signal Conditioners M3S-UNIT Series 获取价格
M3SVS-A12-R/Q MSYSTEM Super-space-saving Signal Conditioners M3S-UNIT Series 获取价格
M3SVS-A13-AD MSYSTEM Super-space-saving Signal Conditioners M3S-UNIT Series 获取价格
M3SVS-A13-AD/K MSYSTEM Super-space-saving Signal Conditioners M3S-UNIT Series 获取价格
M3SVS-A13-AD/Q MSYSTEM Super-space-saving Signal Conditioners M3S-UNIT Series 获取价格
M3SVS-A13-M2 MSYSTEM Super-space-saving Signal Conditioners M3S-UNIT Series 获取价格

M3SVS-A12-AD/Q 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8