PDF下载MODEL: M6NVS
4W: -10 – +10 V DC (Input resistance 1 MΩ min.)
Screw Terminal Ultra-Slim Signal Conditioners M6N Series
5W: -5 – +5 V DC (Input resistance 1 MΩ min.)
0: Specify voltage (See INPUT SPECIFICATIONS)
SIGNAL TRANSMITTER
Functions & Features
[2] OUTPUT
Current
• 7.5-mm wide ultra-slim design
• Low profile allows the M6N module mounted in a 120-mm
deep panel
A: 4 – 20 mA DC (Load resistance 550 Ω max.)
D: 0 – 20 mA DC (Load resistance 550 Ω max.)
G: 0 – 1 mA DC (Load resistance 11 kΩ max.)
Z: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
• Galvanically isolates process instrumentation signals
• High-density mounting
• Power indicator LED
3: 0 – 1 V DC (Load resistance 1000 Ω min.)
4: 0 – 10 V DC (Load resistance 10 kΩ min.)
5: 0 – 5 V DC (Load resistance 5000 Ω min.)
6: 1 – 5 V DC (Load resistance 5000 Ω min.)
4W: -10 – +10 V DC (Load resistance 20 kΩ min.)
5W: -5 – +5 V DC (Load resistance 10 kΩ min.)
0: Specify voltage (See OUTPUT SPECIFICATIONS)
7.5 (.30)
102
(4.02)
[3] POWER INPUT
AC Power
102
(4.02)
mm (inch)
M2: 100 – 240 V AC (Operational voltage range 90 – 264 V,
47 – 66 Hz)
(UL not available)
DC Power
MODEL: M6NVS-[1][2]-[3][4]
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
ORDERING INFORMATION
• Code number: M6NVS-[1][2]-[3][4]
Specify a code from below for each [1] through [4].
(e.g. M6NVS-4W4W-R/K/UL/Q)
[4] OPTIONS (multiple selections)
Response Time (0 – 90 %)
blank: Standard (≤ 0.5 sec.)
• Special input and output ranges (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01)
/K: Fast Response (Approx. 3.5 msec. voltage output;
Approx. 25 msec. current output)
Standards & Approvals
blank: CE marking
[1] INPUT
Current
/UL: UL approval, CE marking
Other Options
A: 4 – 20 mA DC (Input resistance 50 Ω)
B: 2 – 10 mA DC (Input resistance 100 Ω)
C: 1 – 5 mA DC (Input resistance 200 Ω)
D: 0 – 20 mA DC (Input resistance 50 Ω)
E: 0 – 16 mA DC (Input resistance 50 Ω)
F: 0 – 10 mA DC (Input resistance 100 Ω)
G: 0 – 1 mA DC (Input resistance 1000 Ω)
H: 10 – 50 mA DC (Input resistance 20 Ω)
Z: Specify current (See INPUT SPECIFICATIONS)
Voltage
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
GENERAL SPECIFICATIONS
Connection
3: 0 – 1 V DC (Input resistance 1 MΩ min.)
4: 0 – 10 V DC (Input resistance 1 MΩ min.)
5: 0 – 5 V DC (Input resistance 1 MΩ min.)
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
Input and output: M3 screw terminal (torque 0.5 N·m)
Power input: Via the Installation Base (model: M6NBS) (not
available for AC power input)
M6NVS SPECIFICATIONS
ES-7906 Rev.9 Page 1/4
http://www.m-system.co.jp/
MODEL: M6NVS
or M3 screw terminal (torque 0.5 N·m)
PERFORMANCE in percentage of span
Accuracy: ±0.1 %
Recommended solderless terminal: Max. 5.8 mm (0.23”)
wide; Ones with insulation sleeve do not fit.
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
Applicable wire size: 0.2 – 2.5 mm
2
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Zero adjustment: -2 to +2 % (front)
(Output code 4W, 5W: Adjustable at 0V. No output below
0 mA for the code D.)
STANDARDS & APPROVALS
EU conformity:
Span adjustment: 98 to 102 % (front)
Power LED: Green light turns on when the power is supplied.
■Recommended solderless terminal (unit: mm (inch))
EMC Directive
EMI EN 61000-6-4
5.5 max.
(.22)
4 min.
(.16)
EMS EN 61000-6-2
3.2 (.13) dia.
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
RoHS Directive
INPUT SPECIFICATIONS
■ DC Current: Input resistor incorporated
Specify input resistance value among followings for code Z.
20Ω, 50Ω, 100Ω, 200Ω, 249Ω, 1000Ω
EN 50581
Approval:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D
(0.125 W ≥ [Input current] × R)
2
■ DC Voltage: -30 – +30 V DC
Minimum span: 100 mV
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
Offset: Max. 1.5 times span
Input resistance: 1 MΩ min. (10 kΩ min. with no power
supplied)
OUTPUT SPECIFICATIONS
■ DC Current: 0 – 20 mA DC
Minimum span: 1 mA
Offset: Max. 1.5 times span
Load resistance: Output drive 11 V max.
■ DC Voltage: 0 – 10 V DC
Minimum span: 1 V
Offset: Max. 1.5 times span
Load resistance: Output drive 1 mA max.; at ≥ 1 V
INSTALLATION
Power Consumption
•AC: Max. 2 VA
•DC: Approx. 0.5 W
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6NBS) or DIN rail
Weight: 60 g (2.1 oz)
M6NVS SPECIFICATIONS
ES-7906 Rev.9 Page 2/4
http://www.m-system.co.jp/
MODEL: M6NVS
EXTERNAL VIEW
(With the cover open)
Power LED
Zero Adj.
Span Adj.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCREWDRIVER
INSERTION ANGLE
: approx. 55°
*
WIRE INSERTION ANGLE
: approx. 35°
8–M3
SCREW TERMINAL
DIN RAIL HOOK
5
6
7
8
DIN RAIL
35mm wide
1
2
3
4
[1 (.04)]
SCREWDRIVER
INSERTION ANGLE
: approx. 40°
7.5 (.30)
102 (4.02)
*Screwdriver stem diameter: 6 mm (.24”) or less
• When mounting, no extra space is needed between units.
M6NVS SPECIFICATIONS
ES-7906 Rev.9 Page 3/4
http://www.m-system.co.jp/
MODEL: M6NVS
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Z
S
Isolation
Low Drift
Amplifier
Output
Driver
+
–
1
2
3
4
5
6
+
–
*
INPUT
OUTPUT
POWER
POWER LED
7
8
U(+)
V(–)
**
POWER
* Input shunt resistor incorporated for current input.
** Available only for DC power input type
Specifications are subject to change without notice.
M6NVS SPECIFICATIONS
ES-7906 Rev.9 Page 4/4
http://www.m-system.co.jp/
M6NVS-Z4-M2/Q 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
M6NVS-Z4-M2/UL | MSYSTEM | Screw Terminal Ultra-Slim Signal Conditioners M6N Series | 获取价格 | |
M6NVS-Z4-R | MSYSTEM | Screw Terminal Ultra-Slim Signal Conditioners M6N Series | 获取价格 | |
M6NVS-Z4-R/K | MSYSTEM | Screw Terminal Ultra-Slim Signal Conditioners M6N Series | 获取价格 | |
M6NVS-Z4-R/Q | MSYSTEM | Screw Terminal Ultra-Slim Signal Conditioners M6N Series | 获取价格 | |
M6NVS-Z4-R/UL | MSYSTEM | Screw Terminal Ultra-Slim Signal Conditioners M6N Series | 获取价格 | |
M6NVS-Z4W-M2 | MSYSTEM | Screw Terminal Ultra-Slim Signal Conditioners M6N Series | 获取价格 | |
M6NVS-Z4W-M2/K | MSYSTEM | Screw Terminal Ultra-Slim Signal Conditioners M6N Series | 获取价格 | |
M6NVS-Z4W-M2/Q | MSYSTEM | Screw Terminal Ultra-Slim Signal Conditioners M6N Series | 获取价格 | |
M6NVS-Z4W-M2/UL | MSYSTEM | Screw Terminal Ultra-Slim Signal Conditioners M6N Series | 获取价格 | |
M6NVS-Z4W-R | MSYSTEM | Screw Terminal Ultra-Slim Signal Conditioners M6N Series | 获取价格 |
M6NVS-Z4-M2/Q 相关文章
- 2024-09-20
- 5
- 2024-09-20
- 8
- 2024-09-20
- 8
- 2024-09-20
- 6