M6NXM-1V2-R/UL [MSYSTEM]
Screw Terminal Ultra-Slim Signal Conditioners M6N Series;型号: | M6NXM-1V2-R/UL |
厂家: | M-SYSTEM |
描述: | Screw Terminal Ultra-Slim Signal Conditioners M6N Series |
文件: | 总4页 (文件大小:145K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M6NXM
described range of the selected suffix code.
Screw Terminal Ultra-Slim Signal Conditioners M6N Series
For changing between suffix codes, set the Output Range
Selector on the side of unit before software adjustment.)
POTENTIOMETER TRANSMITTER
(PC programmable)
POWER INPUT
Functions & Features
DC Power
• 7.5-mm wide ultra-slim design
• Low profile allows the M6N module mounted in
a 120-mm deep panel
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Provides a DC output proportional to a potentiometer or
slidewire position input
[2] OPTIONS (multiple selections)
Standards & Approvals
• Linearization and burnout protection
• PC programmable
blank: CE marking
• High-density mounting
/UL: UL approval, CE marking
Other Options
• Power indicator LED
blank: none
/Q: Option other than the above (specify the specification)
7.5 (.30)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
102
(4.02)
/C02: Polyurethane coating
RELATED PRODUCTS
102
• PC configurator software (model: M6CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
(4.02)
mm (inch)
MODEL: M6NXM–1[1]–R[2]
ORDERING INFORMATION
• Code number: M6NXM-1[1]-R[2]
Specify a code from below for each [1] and [2].
(e.g. M6NXM-1Z1-R/UL/Q)
GENERAL SPECIFICATIONS
Connection
Input and output: M3 screw terminal (torque 0.5 N·m)
Power input: Via the Installation Base (model: M6NBS)
or M3 screw terminal (torque 0.5 N·m)
Recommended solderless terminal: Max. 5.8 mm (0.23”)
wide; Ones with insulation sleeve do not fit.
• Potentiometer range (total resistance) (e.g. 0 – 1000 Ω)
• Output range (e.g. 4 – 20 mA DC)
• Specify the specification for option code /Q
(e.g. /C01)
Applicable wire size: 0.2 – 2.5 mm
2
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
INPUT
1: Total resistance 100 – 5000 Ω
Overrange output: -2 – +102 %
(Configurator software is used to change the input range.)
(Negative current output is not available.)
Zero adjustment: -2 to +2 % (PC programming)
Span adjustment: 98 to 102 % (PC programming)
Burnout: Upscale standard; downscale or no burnout
optional by programming
[1] OUTPUT
Current
Z1: Range 0 – 20 mA DC
Voltage
Power LED: Green light turns on when the power is supplied.
Status indicator LED: Orange LED; Blinking patterns indicate
different operating status of the transmitter.
Programming: Downloaded from PC; input type (range),
V2: Range -10 – +10 V DC
V3: Range -5 – +5 V DC
(Configurator software is used to change output over the
M6NXM SPECIFICATIONS
ES-7909 Rev.10 Page 1/4
http://www.m-system.co.jp/
MODEL: M6NXM
output type and range, zero and span, burnout type, user’s
linearization table, etc.
V2: 0 – 10 V DC
V3: 1 – 5 V DC
For detailed information, refer to the users manual for the
PC configurator.
INSTALLATION
Power consumption: Approx. 0.5 W
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6NBS) or DIN rail
Weight: 65 g (2.3 oz)
■Recommended solderless terminal (unit: mm (inch))
5.5 max.
(.22)
4 min.
(.16)
3.2 (.13) dia.
PERFORMANCE in percentage of span
Overall accuracy: Input accuracy + output accuracy
Inversely proportional to the span.
See CALCULATION EXAMPLES OF OVERALL ACURACY.
• Input accuracy: (% of range)
INPUT SPECIFICATIONS
Sensing current: ≤ 0.15 mA
Minimum span of each range
0 – 100 Ω : 10 Ω
0 – 100 Ω : ±0.05 %
0 – 300 Ω : ±0.05 %
0 – 600 Ω : ±0.03 %
0 – 300 Ω : 30 Ω
0 – 1200 Ω : ±0.03 %
0 – 600 Ω : 60 Ω
0 – 2500 Ω : ±0.01 %
0 – 1200 Ω : 120 Ω
0 – 5000 Ω : ±0.01 %
0 – 2500 Ω : 250 Ω
• Output accuracy: ±0.04 % of max. output range
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. span
Response time: ≤ 1 sec. (0 – 90 %)
Burnout response: ≤ 10 sec.
0 – 5000 Ω : 500 Ω
If not specified, the input range is 0 – 1200 Ω.
OUTPUT SPECIFICATIONS
■ DC Current
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
Output range: 0 – 20 mA DC
Conformance range: 0 – 20.4 mA DC
Minimum span: 1 mA
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example] Total Resistance 0 – 1200 Ω, Input Range 250–
750 Ω, Output Type -5 – +5 V, Output Range 1 – 5 V
Max. Input Range (1200 Ω) ÷ Span (500 Ω) × 0.01 %
+ Max. Output Range (10 V) ÷ Span (4 V) × 0.04 %
= 0.18 %
Load resistance: Output drive 11 V max.
(e.g. 4 – 20 mA: 550 Ω [11 V ÷ 20 mA])
If not specified, the output range is 4 – 20 mA DC.
■ DC Voltage
Code V2 (wide spans)
STANDARDS & APPROVALS
EU conformity:
Output range: -10 – +10 V DC
Conformance range: -10.4 – +10.4 V DC
Minimum span: 1 V
EMC Directive
EMI EN 61000-6-4
Code V3 (narrow spans)
EMS EN 61000-6-2
Output range: -5 – +5 V DC
RoHS Directive
Conformance range: -5.2 – +5.2 V DC
Minimum span: 0.5 V
EN 50581
Approval:
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D hazardous locations
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
Load resistance: Output drive 1 mA max.
(e.g. 1 – 5 V: 5000 Ω [5 V ÷ 1 mA])
If not specified, the output range is shown below.
M6NXM SPECIFICATIONS
ES-7909 Rev.10 Page 2/4
http://www.m-system.co.jp/
MODEL: M6NXM
EXTERNAL VIEW
FRONT VIEW (with the cover open)
SIDE VIEW
5
6
7
8
Power LED
Status Indicator LED
Configurator Jack
Output Range Selectors
1
2
3
4
The DIP switch setting is required to select output types
before setting a precise output range using PC Configurator
Software (model: M6CFG).
Refer to the instruction manual for detailed procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCREWDRIVER
INSERTION ANGLE
: approx. 55°
*
WIRE INSERTION ANGLE
: approx. 35°
8–M3
SCREW TERMINAL
DIN RAIL HOOK
5
6
7
8
DIN RAIL
35mm wide
1
2
3
4
[1 (.04)]
SCREWDRIVER
INSERTION ANGLE
: approx. 40°
7.5 (.30)
102 (4.02)
*Screwdriver stem diameter: 6 mm (.24”) or less
• When mounting, no extra space is needed between units.
M6NXM SPECIFICATIONS
ES-7909 Rev.10 Page 3/4
http://www.m-system.co.jp/
MODEL: M6NXM
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS LED
DIP SW
Isolation
POTENTIOMETER
max.
Digital
Computation
Output
Driver
+
–
1
5
6
+
–
3
2
1
OUTPUT
POWER
Low Drift
Amplifier
2
POWER LED
4
7
8
+
–
min.
3
JACK
CONFIGURATOR
POWER
Specifications are subject to change without notice.
M6NXM SPECIFICATIONS
ES-7909 Rev.10 Page 4/4
http://www.m-system.co.jp/