MODEL: M6SXAP  
N: 12 V pulse (100 kHz for FM, 1 kHz for PWM)  
Tension-Clamp Ultra-Slim Signal Conditioners M6S Series  
P: 24 V pulse (100 kHz for FM, 1 kHz for PWM)  
Output modulation type and range are configurable with the  
configure software. The output signal type is configurable  
with the DIP switches.  
DC/FREQUENCY CONVERTER  
(PC programmable)  
Function & features  
• Maintenance-free tension clamp connection  
• 5.9-mm wide ultra-slim design  
• Low profile allows the M6S module mounted in a 120-mm  
deep panel  
POWER INPUT  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
• Converts a DC input into a FM (frequency modulation) or  
PWM (pulse width modulated) signal  
• PC programmable  
[3] OPTIONS  
blank: none  
• High-density mounting  
• Power and status indicator LEDs  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
5.9 (.23)  
/C02: Polyurethane coating  
EX-FACTORY SETTING  
94  
(3.70)  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-7837)  
102  
(4.02)  
RELATED PRODUCTS  
• PC configurator software (model: M6CFG)  
Downloadable at M-System’s web site.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
mm (inch)  
MODEL: M6SXAP–[1][2]–R[3]  
ORDERING INFORMATION  
• Code number: M6SXAP-[1][2]-R[3]  
Specify a code from below each [1] through [3].  
(e.g. M6SXAP-Z1A-R/Q)  
GENERAL SPECIFICATIONS  
Connection  
Input and output: Tension clamp  
Power input: Via the Installation Base (model: M6SBS)  
or Tension clamp  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
Applicable wire size: 0.2 to 2.5 mm , stripped length 8 mm  
2
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
[1] INPUT  
Current  
Zero adjustment: -2 to +2 % (PC programming)  
Span adjustment: 98 to 102 % (PC programming)  
Power LED: Green light turns on when the power is supplied.  
Status indicator LED: Orange LED; Blinking patterns indicate  
different operating status of the transmitter.  
Programming: Downloaded from PC  
Z1: Range 0 – 50 mA DC (Input resistance 25 Ω)  
Voltage  
S1: Range -1000 – +1000 mV DC (Input resistance 1 MΩ min.)  
S2: Range -10 – +10 V DC (Input resistance 1 MΩ min.)  
(Configurator software is used to change the input type and  
precise range.)  
• Input type and range  
• Modulation type (FM, PWM)  
[2] OUTPUT  
A: Open collector (100 kHz for FM, 1 kHz for PWM)  
• Output range  
• Zero and span  
M: 5 V pulse (100 kHz for FM, 1 kHz for PWM)  
• User’s linearization table (max. 101 points, specified  
M6SXAP SPECIFICATIONS  
ES-7996 Rev.4 Page 1/4  
http://www.m-system.co.jp/  
MODEL: M6SXAP  
within -2 to +102 %)  
• ≥ 2.4 kΩ for 12 V  
• ≥ 4.8 kΩ for 24 V  
• Others  
(Refer to the instruction manual for details)  
Configurator connection: 2.5 dia. miniature jack;  
RS-232-C level  
Factory default: 0 to 10 kHz, Frequency modulation  
INSTALLATION  
Power consumption: Approx. 1 W  
INPUT SPECIFICATIONS  
DC Current: Input resistor incoporated  
(If not specified, the input range is 4 – 20 mA DC.)  
Input range: 0 – 50 mA DC  
Operating temperature: -20 to +55°C (-4 to +131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Installation Base (model: M6SBS) or DIN rail  
Weight: 65 g (2.3 oz)  
Minimum span: 2 mA  
Offset: Lower range can be any specific value within the  
input range provided that the minimum span is maintained.  
DC Voltage  
PERFORMANCE in percentage of span  
Accuracy: Input accuracy + output accuracy  
Inversely proportional to the span.  
•Code S1 (narrow spans)  
Input accuracy in percentage of input span:  
• ±0.01 % for -1000 to +1000 mV  
Input range: -1000 – +1000 mV DC  
Minimum span: 100 mV  
• ±0.01 % for -10 to +10 V  
•Code S2 (wide spans)  
• ±0.02 % for 0 to 50 mA  
Input range: -10 – +10 V DC  
Output accuracy at max. frequency (FM):  
• ±0.10 % for ≤ 10 kHz  
Minimum span: 1 V  
Offset: Lower range can be any specific value within the  
input range provided that the minimum span is maintained.  
If not specified, the input range is shown below.  
S1: 0 – 100 mV DC  
• ±0.05 % for ≤ 5 kHz  
• ±0.02 % for ≤ 1 kHz  
• For 10 kHz to 100 kHz output accuracy is following.  
Output accuracy (%) = Max. frequency (kHz) x 0.01  
Output accuracy (PWM): ±0.2 %  
S2: 1 – 5 V DC  
See CALCULATION EXAMPLES OF OVERALL ACCURACY.  
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. input  
span  
OUTPUT SPECIFICATIONS  
■ Modulation  
Frequency modulation  
Response time: 0.1 sec. + 1 pulse cycle of 100 % output  
The time between the moment when the input changes 0 %  
to 100 % and the moment when the first pulse changes.  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @1 minute (input to output  
to power to ground)  
Output range: 0 to 100 %  
Max. frequency: 100 kHz  
Min. span: 0.01 Hz  
(The output frequency changes according to the input  
signal. Duty rate is approx. 50 %)  
Pulse width modulation  
Output range: 1 to 99 %  
Usable frequency: 0.008 Hz to 1 kHz  
(According to the input signal, the output pulse width (duty  
rate) changes without change of its frequency. The  
frequency is configurable with PC Configurator software,  
M6CFG.).  
CALCULATION EXAMPLES OF OVERALL ACCURACY  
1. Frequency modulation  
E.g.: Input range -10 to +10 V, input span 1 to 5 V, max.  
frequency 10 kHz  
Input accuracy = Input range (20 V) ÷ Input span (4 V) x  
Input accuracy (0.01 %) = 0.05 %  
Output accuracy = 0.10 %  
Open Collector  
50 V DC @ 100 mA (resistive load)  
Maximum frequency: 100 kHz  
Saturation voltage: 0.5 V DC  
(Factory default: 0 to 10 kHz, frequency modulation)  
Voltage Pulse  
Overall accuracy = ±0.15 %  
2. Pulse width modulation  
E.g.: Input range -10 to +10 V, input span 1 to 5 V,  
frequency 1 kHz  
High level: Rating (5, 12 or 24 V) ±10 %  
Low level: ≤ 0.5 V  
Input accuracy = 0.05 % (same as above)  
Output accuracy = 0.20 %  
Load resistance:  
Overall accuracy = ±0.25 %  
• ≥ 1.0 kΩ for 5 V  
M6SXAP SPECIFICATIONS  
ES-7996 Rev.4 Page 2/4  
http://www.m-system.co.jp/  
MODEL: M6SXAP  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
EN 50581  
EXTERNAL VIEW  
FRONT VIEW (with the cover open)  
SIDE VIEW  
5
6
7
8
Power LED  
Output Range Selectors  
Status Indicator LED  
Configurator Jack  
1
2
3
4
The output signal type is configurable with the DIP switches. Refer to the installation manual for detailed procedure.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
SCREWDRIVER  
*
INSERTION ANGLE  
: approx. 35°  
WIRE INSERTION ANGLE  
: approx.35°  
TEST PROBE  
max. 2 (.08) dia.  
5
6
7
8
DIN RAIL HOOK  
DIN RAIL  
35mm wide  
1
2
3
4
SCREWDRIVER  
INSERTION ANGLE  
: approx. 40°  
[0.5 (.02)]  
5.9 (.23)  
102 (4.02)  
• When mounting, no extra space is needed between units.  
*Use a minus screwdriver: tip width 3.8 mm max., tip thickness 0.5 to 0.6 mm  
M6SXAP SPECIFICATIONS  
ES-7996 Rev.4 Page 3/4  
http://www.m-system.co.jp/  
MODEL: M6SXAP  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
STATUS  
IND. LED  
Isolation  
DIP SW  
25 Ω  
+
Digital  
Computation  
Output  
Driver  
+
1
5
6
CURRENT  
(Z1)  
OUTPUT  
POWER  
Low Drift  
Amplifier  
2
VOLTAGE  
(S1, S2)  
POWER LED  
3
+
+
7
8
4
CONFIGURATOR  
JACK  
POWER  
Output Connection Examples  
Open Collector  
Voltage Pulse  
5
6
+
+
5
6
+
+
Specifications are subject to change without notice.  
M6SXAP SPECIFICATIONS  
ES-7996 Rev.4 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

M6SXAP-S2A-R

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-S2A-R/Q

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-S2M-R

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-S2M-R/Q

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-S2N-R

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-S2N-R/Q

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-S2P-R

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-S2P-R/Q

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-Z1A-R

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-Z1A-R/Q

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-Z1M-R

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM

M6SXAP-Z1M-R/Q

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
MSYSTEM