M6SXF1-S1V3-R/UL [MSYSTEM]
Tension-Clamp Ultra-Slim Signal Conditioners M6S Series;型号: | M6SXF1-S1V3-R/UL |
厂家: | M-SYSTEM |
描述: | Tension-Clamp Ultra-Slim Signal Conditioners M6S Series |
文件: | 总6页 (文件大小:205K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M6SXF1
Voltage
Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
V2: Range -10 – +10 V DC
V3: Range -5 – +5 V DC
FUNCTION MODULE
(PC programmable)
(Configurator software is used to change output over the
described range of the selected suffix code.
For changing between suffix codes, set the Output Range
Selector on the side of unit before software adjustment.)
Functions & Features
• Maintenance-free tension clamp connection
• Single input filter and function module
• 12 types of functions are PC programmable
• 5.9-mm wide ultra-slim design
• Low profile allows the M6S module mounted in a 120-mm
deep panel
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• High-density mounting
• Power and status indicator LEDs
[3] OPTIONS (multiple selections)
Standards & Approvals
5.9 (.23)
blank: CE marking
/UL: UL approval, CE marking
Other Options
94
(3.70)
blank: none
/Q: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
102
(4.02)
mm (inch)
/C02: Polyurethane coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-7847)
MODEL: M6SXF1–[1][2]–R[3]
ORDERING INFORMATION
• Code number: M6SXF1-[1][2]-R[3]
Specify a code from below for each [1] through [3].
(e.g. M6SXF1-Z1Z1-R/UL/Q)
FUNCTIONS
PC Configurator Software is used to program the function.
Filter, linearization and limiter functions can be combined.
• Filter / Lag
• Input range (e.g. 4 – 20 mA DC)
• Output range (e.g. 4 – 20 mA DC)
• Specify the specification for option code /Q
(e.g. /C01/SET)
· Moving average output
· Dead time computing
· Delay buffer (first order lag)
· Lead time computing
· Ramp buffer
[1] INPUT
Current
• Linearization
· User’s table linearization
· Inverted output
Z1: Range 0 – 50 mA DC (Input resistance 24.9 Ω)
Voltage
· Square root extraction (orifice, venturi)
S1: Range -1000 – +1000 mV DC (Input resistance 1 MΩ min.)
S2: Range -10 – +10 V DC (Input resistance 1 MΩ min.)
(Configurator software is used to change the input type and
precise range.)
· X (Palmer-Bowlus flume, Parshall flume)
2
· X 5/2 (triangular or v-notch weir)
· X 3/2 (rectangular weir)
• Limiter
· High / Low limit
[2] OUTPUT
Current
Factory default function setting
Filter: Moving average
(H = 0.1, N = 1, U = 0, L = 0)
Z1: Range 0 – 20 mA DC
M6SXF1 SPECIFICATIONS
ES-7987 Rev.8 Page 1/6
http://www.m-system.co.jp/
MODEL: M6SXF1
Linearization: None
S1: 0 – 100 mV DC
S2: 1 – 5 V DC
Limiter: Low limit = -2 %, High limit = 102 %
RELATED PRODUCTS
OUTPUT SPECIFICATIONS
■ DC Current
• PC configurator software (model: M6CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
Output range: 0 – 20 mA DC
Conformance range: 0 – 20.4 mA DC
Minimum span: 1 mA
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
Load resistance: Output drive 11 V max.
(e.g. 4 – 20 mA: 550 Ω [11 V ÷ 20 mA])
If not specified, the output range is 4 – 20 mA DC.
■ DC Voltage
GENERAL SPECIFICATIONS
Connection
Input and output: Tension clamp
Power input: Via the Installation Base (model: M6SBS)
or Tension clamp
Code V2 (wide spans)
Output range: -10 – +10 V DC
Conformance range: -10.4 – +10.4 V DC
Minimum span: 1 V
Applicable wire size: 0.2 to 2.5 mm , stripped length 8 mm
2
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Code V3 (narrow spans)
Overrange output: -2 – +102 %
Output range: -5 – +5 V DC
(Negative current output is not available.)
Zero adjustment: -2 to +2 % (PC programming)
Span adjustment: 98 to 102 % (PC programming)
Power LED: Green light turns on when the power is supplied.
Status indicator LED: Orange LED; Blinking patterns indicate
different operating status of the transmitter.
Programming: Downloaded from PC; input type and range,
output type and range, zero and span, function type and
parameters, etc.
Conformance range: -5.2 – +5.2 V DC
Minimum span: 0.5 V
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
Load resistance: Output drive 1 mA max.
(e.g. 1 – 5 V: 5000 Ω [5 V ÷ 1 mA])
If not specified, the output range is shown below.
V2: 0 – 10 V DC
For detailed information, refer to the users manual for the
PC configurator.
V3: 1 – 5 V DC
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level
INSTALLATION
Power consumption: Approx. 0.5 W
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6SBS) or DIN rail
Weight: 65 g (2.3 oz)
INPUT SPECIFICATIONS
■ DC Current: Input resistor incoporated
(If not specified, the input range is 4 – 20 mA DC.)
Input range: 0 – 50 mA DC
Minimum span: 2 mA
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
■ DC Voltage
PERFORMANCE in percentage of span
Overall accuracy
I/O gain ≤ 1: Input accuracy + Output accuracy
I/O gain > 1: [Input accuracy + Output accuracy] × I/O gain
• Input accuracy*: (% of max. input range)
-1000 – +1000 mV : ±0.01 %
•Code S1 (narrow spans)
Input range: -1000 – +1000 mV DC
Minimum span: 100 mV
•Code S2 (wide spans)
-10 – +10 V : ±0.01 %
Input range: -10 – +10 V DC
0 – 50 mA : ±0.02 %
Minimum span: 1 V
• Output accuracy*: ±0.04 % of max. output range
*Inversely proportional to the span.
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
If not specified, the input range is shown below.
See CALCULATION EXAMPLES OF OVERALL ACURACY.
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. span
M6SXF1 SPECIFICATIONS
ES-7987 Rev.8 Page 2/6
http://www.m-system.co.jp/
MODEL: M6SXF1
Response time: ≤ 0.5 sec. (0 – 90 %) without any function
setting
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example] Input Type -10 – +10 V, Input Range 1 – 5 V,
Output Type -5 – +5 V, Output Range 1 – 5 V
• Input accuracy = Max. Input Range (20 V) ÷ Span (4 V) ×
0.01 % = 0.05 %
• Output accuracy = Max. Output Range (10 V) ÷ Span (4 V)
× 0.04 % = 0.1 %
Accuracy= ±0.15 %
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
Approval:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
EXTERNAL VIEW
FRONT VIEW (with the cover open)
SIDE VIEW
5
6
7
8
Power LED
Output Range Selectors
Status Indicator LED
Configurator Jack
1
2
3
4
The DIP switch setting is required to select output types
before setting a precise output range using PC Configurator
Software (model: M6CFG).
Refer to the instruction manual for detailed procedures.
M6SXF1 SPECIFICATIONS
ES-7987 Rev.8 Page 3/6
http://www.m-system.co.jp/
MODEL: M6SXF1
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
SCREWDRIVER
*
INSERTION ANGLE
: approx. 35°
WIRE INSERTION ANGLE
: approx.35°
TEST PROBE
max. 2 (.08) dia.
5
6
7
8
DIN RAIL HOOK
DIN RAIL
35mm wide
1
2
3
4
SCREWDRIVER
INSERTION ANGLE
: approx. 40°
[0.5 (.02)]
5.9 (.23)
102 (4.02)
• When mounting, no extra space is needed between units.
*Use a minus screwdriver: tip width 3.8 mm max., tip thickness 0.5 to 0.6 mm
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
STATUS
IND. LED
DIP SW
Isolation
24.9Ω
+
Digital
Computation
Output
Driver
+
–
1
2
3
4
5
6
CURRENT
(Z1)
OUTPUT
POWER
Low Drift
Amplifier
–
–
VOLTAGE
(S1, S2)
POWER LED
+
+
–
7
8
CONFIGURATOR
JACK
POWER
M6SXF1 SPECIFICATIONS
ES-7987 Rev.8 Page 4/6
http://www.m-system.co.jp/
MODEL: M6SXF1
FUNCTIONS
■ MOVING AVERAGE OUTPUT
INPUT
The module samples input signals every H seconds and,
excluding U numbers of highest-value samples and L
numbers of lowest-value samples, outputs proportionally to
the average of the rest [N – (U + L)] of sampled data. When
a new input is sampled after another H seconds, it gives up
the oldest sample and calculates a new average including
the latest sample and outputs proportionally.
t
H
H
N numbers
N numbers
average
When the number of samples to be calculated equals 0 or
less, it outputs an error.
OUTPUT
Parameters
H: Sampling cycle
(0.1000 to 100.0000 seconds)
N: Number of samples to be calculated
(1 to 128)
t
U: Number of highest-value samples to be cut off
(0 to 127)
L: Number of lowest-value samples to be cut off
(0 to 127)
■ DEAD-TIME COMPUTING
The module does not respond to an input signal for a
preset dead-time* duration.
•
Step input with dead-time
INPUT
In addition, with adjusting a time constant T, it generates
a first order lag output after the dead-time.
e –HNs
0
X0 (s) = ––––––– X1 (s)
1 + Ts
t
OUTPUT
where
X1: Input
X0: Output
0
Dead time = H x N (s)
t
H x N
Parameters
H: Sampling cycle (0.1000 to 100.0000 seconds)
N: Numbers of samples to be calculated (1 to 128)
T: Time constant (0.0000 or 0.5000 to 100.0000 seconds)
•
Step input with dead-time plus time constant
INPUT
*Output is refreshed every sampling cycle. The response
time may be delayed by 1 cycle at the maximum.
0
t
OUTPUT
0
t
H x N
T
■ DELAY BUFFER
The module generates a first order lag output.
•
Step input with time constant
INPUT
1
X0 (s) = ––––––– X1 (s)
1 + Ts
0
where
X1: Input
X0: Output
t
OUTPUT
Parameters
T: Time constant (0.5000 to 100.0000 seconds)
0
t
T
M6SXF1 SPECIFICATIONS
ES-7987 Rev.8 Page 5/6
http://www.m-system.co.jp/
MODEL: M6SXF1
LEAD-TIME COMPUTING
The module operates a lead-time equation.
•
Step input with lead-time constant
X0 (s) = (1 + Ts) X1 (s)
INPUT
where
X1: Input
X0: Output
0
t
Parameters
T: Lead-time constant (0.5000 to 100.0000 seconds)
OUTPUT
0
t
T
RAMP BUFFER
•
Step input with rate-of-change limits
The modules output does not change faster than a preset
maximum rate, positive CP and negative CN, no matter
how fast its input changes.
INPUT
CP: Maximum rate of positive output change
(0.0000 to 200.0000%/second)
CN: Maximum rate of negative output change
(0.0000 to 200.0000%/second)
0
t
OUTPUT
0
t
CP
CN
X 2 OUTPUT (Palmer-Bowlus flume, Parshall flume)
HIGH / LOW LIMIT
The output does not go above the preset high limit or
below the preset low limit.
X0 = X1 2 / 100
where
X1: Input (%)
High and Low limits are independently selectable.
X0: Output (%)
X 5/2 OUTPUT (triangular or V-notch weir)
USER’S TABLE LINEARIZATION
The input is converted into a linearized output according
to the user specified segment data table, defined with pairs
of X (input) and Y (output) values.
X0 = X1 5/2 / 1000
where
X1: Input (%)
2 to 101 segment points can be specified.
X0: Output (%)
X 3/2 OUTPUT (rectangular weir)
INVERTED OUTPUT
The output is inversely proportional to the input.
X0 = X1 3/2 / 10
X0 = 100 – X1
where
X1: Input (%)
X0: Output (%)
where
X1: Input (%)
X0: Output (%)
OTHER FUNCTIONS
The low-end cutout point can be set within
0.0000 – 99.9999% of input signal.
SQUARE ROOT EXTRACTION (orifice, venturi)
The output is square root of input.
___
X0 = 10
√
X1
where
X1: Input (%)
X0: Output (%)
Specifications are subject to change without notice.
M6SXF1 SPECIFICATIONS
ES-7987 Rev.8 Page 6/6
http://www.m-system.co.jp/
相关型号: