M7EASDY-3-M2 [MSYSTEM]
Super-mini Signal Conditioners with LCD Display M7E-UNIT Series;型号: | M7EASDY-3-M2 |
厂家: | M-SYSTEM |
描述: | Super-mini Signal Conditioners with LCD Display M7E-UNIT Series CD |
文件: | 总5页 (文件大小:153K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: M7EASDY
Super-mini Signal Conditioners with
LCD Display M7E-UNIT Series
[1] OUTPUT
2: 4 points; N.O. or make contact
3: 4 points; N.C. or break contact
5: 2 points; SPDT or transfer contact
TWO-WIRE TRANSMITTER ALARM
(dual or quad alarm trip)
[2] POWER INPUT
Functions & Features
AC Power
• Provides relay outputs at preset DC input levels
• Quad or dual trip
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
• Powers a 4 – 20 mA DC current loop
• Shortcircuit protection
DC Power
R: 24 V DC
• Applicable to smart transmitters
• Linearization or square root extraction programmable
• Front LCD display indicating values in scaled engineering
unit range is used to program the module
• Adjustable deadband (hysteresis)
• Software lock
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS (multiple selections)
Standards & Approvals
blank: Without CE
• ON delay time selectable
/CE: CE marking
• Hi/Lo trip and energized/de-energized coil independently
selectable for each setpoint
Other Options
blank: none
• Enclosed relays
/Q: Option other than the above (specify the specification)
• Relays can be powered by 200 V AC and 100 V DC
• High-density mounting on DIN rail
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
29.5
[1.16]
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
83
[3.27]
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-7763)
Up
Mod
e
Do
wn
124
Set
[4.88]
mm [inch]
MODEL: M7EASDY-[1]-[2][3]
ORDERING INFORMATION
• Code number: M7EASDY-[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. M7EASDY-2-R/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01/SET)
INPUT
Current
4 – 20 mA DC
(Selectable within 0 – 20 mA DC)
M7EASDY SPECIFICATIONS
ES-7763 Rev.12 Page 1/5
https://www.m-system.co.jp/
MODEL: M7EASDY
Decimal point position
FACTORY DEFAULT SETTING
· Linearization (linear, square root, user table: 128 points)
· Alarm output (L1...L4 independently)
Setpoint (scaled value)
INPUT CALIBRATION
LOW CUT POINT
4
20 mA DC
0.00
MOVING AVERAGE
SCALING RANGE
NONE
-
0.0
100.0
Trip action (Hi or Lo)
DECIMAL POINT
XXX.X
°C
Deadband (hysteresis) (scaled value)
Relay coil (energized or de-energized)
· Power ON delay time (0 to 99 sec.)
· Alarm ON delay time (0 to 999 sec.)
· Latching or not
SCALING UNIT
LINEARIZATION
Linear
L1 ALARM VALUE
20.0
L1 ALARM TRIP OPERATION
L1 ALARM HYSTERESIS
L1 ALARM COIL AT ALARM
L2 ALARM VALUE
Lo alarm trip
1.0
· LCD Contrast
Coil energized
80.0 (2 point alarm)
Back Light (On, Off, Off timer)
30.0 (4 point alarm)
L2 ALARM TRIP OPERATION
Hi alarm trip (2 point alarm)
LCD DISPLAY
Lo alarm trip (4 point alarm)
L2 ALARM HYSTERESIS
L2 ALARM COIL AT ALARM
L3 ALARM VALUE
1.0
Display functions: Displays and sets measured range,
engineering unit, alarm operation
Effective visual area: Approx. 15.6 × 18.9 mm (0.61” ×
0.74”)
Coil energized
70.0
L3 ALARM TRIP OPERATION
L3 ALARM HYSTERESIS
L3 ALARM COIL AT ALARM
L4 ALARM VALUE
Hi alarm trip
1.0
Number of pixels: 68 × 95 (horizontal × vertical)
Character color: Black
Coil energized
80.0
Backlight: LED (orange in normal status, red when an alarm
is tripped.)
L4 ALARM TRIP OPERATION
L4 ALARM HYSTERESIS
L4 ALARM COIL AT ALARM
POWER ON DELAY TIMER
ALARM ON DELAY TIMER
LATCHING
Hi alarm trip
1.0
Coil energized
Backlight life: Approx. 50 000 hours
(Expected time for the LCD brightness to be reduced by half
when the LCD is used continuously in 50 % brightness in
25°C)
5
0
Invalid
50
LCD CONTRAST
LCD type: Transreflective FSTN
LCD BACK LIGHT
Off Timer
10
Display range: -9999 to +9999
LCD BACK LIGHT OFF TIME
Decimal point position: Selectable
Display rate: 150 msec.
RELATED PRODUCTS
• PC configurator software (model: M7CFG)
SUPPLY OUTPUT
Downloadable at M-System’s web site.
■ SUPPLY OUTPUT (across the terminals 1 – 2)
Output voltage: 24 – 28 V DC with no load
19 V DC minimum at 20 mA
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
Current rating: ≤ 22 mA DC
Permissible load resistance:
LR (Ω) ≤ (19 – Min. Operational Voltage)V ÷ 0.02 A
• Shortcircuit Protection
GENERAL SPECIFICATIONS
Construction: Plug-in
Current limited: 26 – 35 mA
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless
steel
Protected time duration: No limit
INPUT SPECIFICATIONS
■ Input Signal: Input resistor incorporated
Maximum range: 0 – 20 mA DC
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Programming: Front buttons or PC software
Programmable parameters:
Ex-factory setting: 4 – 20 mA DC
Minimum span: 2 mA
· Input range
Offset: Lower range can be any specific value within the
maximum range provided that
· Input fine adjustments
· Moving average (None, 4, 8, 16 or 32 samples)
· Scale Range: -9999 to +9999
the minimum span is maintained.
Unit: User specific unit programmable.
M7EASDY SPECIFICATIONS
ES-7763 Rev.12 Page 2/5
https://www.m-system.co.jp/
MODEL: M7EASDY
OUTPUT SPECIFICATIONS
■ Quad Alarm
LINEARIZATION
■ Linearization Types
Relay rating: 100 V AC @ 1 A (cos ø = 1)
120 V AC @ 1 A (cos ø = 1)
Linear: No linearization
Square root: The input is square root extracted.
User table
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Calibration points: Max. 128 points; the input % and
linearized value in scaling are specified in pairs.
Selectable range: -7.5 to +107.5 % as input %; -9999 to
+9999 as linearized values
Maximum switching voltage: 250 V AC or 125 V DC
(Limited to the max. voltage 150 V AC or to the use for
Measurement Category I in order to conform with EU
Directive)
■ Low-end Cutout: Low-end cutout (Low Cut) point
selectable within the range of 0 to 100 %.
With the linear or user table output type,
the output signal is forcibly set to 0 % for the input lower
than the low-cut point. With the square root extraction, the
output signal is linear to the input when the latter is lower
than the low-cut point.
Maximum switching power: 120 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Mechanical life: 5 × 10
7
cycles
■ DUAL ALARM
Relay rating: 100 V AC @ 4 A (cos ø = 1)
120 V AC @ 4 A (cos ø = 1)
240 V AC @ 2 A (cos ø = 1)
• Linear or User Table
• Square Root
30 V DC @ 4 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC
(Limited to the max. voltage 150 V AC or to the use for
Measurement Category I in order to conform with EU
Directive)
Low-end cutout
point
Low-end cutout
point
Maximum switching power: 480 VA or 150 W
Minimum load: 5 V DC @ 10 mA
0
0
INPUT
INPUT
Mechanical life: 5 × 10 cycles
7
Alarm Trip Operation Terminal No. in parentheses
INSTALLATION
Power consumption
• Example Quad N.O. contacts (LL, L, H, HH)
•AC: Approx. 5 VA at 100 V
Approx. 7 VA at 200 V
Approx. 8.5 VA at 264 V
•DC: Approx. 3 W
ON OFF
ON OFF
L1 (3–6)
L2 (5–7)
L3 (5–8)
L4 (3–9)
OFF ON
OFF ON
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Input
%
0
50
100
LL
L
H
HH
With 4-point alarm type, leave extra 1-unit space on both
sides of the unit if all 4 relay coils are to be energized in
normal conditions.
Trip operation in power failure
Output code 2 : All relays turn OFF.
Output code 3 : All relays turn ON.
Weight: 200 g (0.44 lb)
Output code 5 : Terminals 3 – 9, 5 – 8 turn ON.
PERFORMANCE in percentage of FS input
Setpoint accuracy (trip point accuracy):
±(0.1 % of FS + 1 digit) (gain ≤1)
±(0.1 % × gain of FS + 1 digit) (gain >1)
Display accuracy: ±(0.1 % of FS + 1 digit)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
to power to ground)
M7EASDY SPECIFICATIONS
ES-7763 Rev.12 Page 3/5
https://www.m-system.co.jp/
MODEL: M7EASDY
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (output)
Installation Category II (power)
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
(When 150 V AC max. load voltage or measurement
category I, applicable as reinforced insulation)
RoHS Directive
EXTERNAL VIEW
Refer to the instruction manual for the setting procedure.
LCD Display
Up Button
Mode Button
Set Button
Down Button
Up
Mode
Set
PC Configurator
Jack
Down
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
6 [.23]
3
2
5
1
4
2–4.2x5
[.17x.20]
6
MTG HOLE
6 [.24] deep
DIN RAIL
35mm wide
9
8
7
11–M3
SCREW
11 10
22 [.87]
29 [1.14]
94 [3.70]
124 [4.88]
29.5 [1.16]
8
(4 [.16])
[.31]
• When mounting, no extra space is needed between units.
M7EASDY SPECIFICATIONS
ES-7763 Rev.12 Page 4/5
https://www.m-system.co.jp/
MODEL: M7EASDY
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■OUTPUT CODE 2: N.O. Relay
■OUTPUT CODE 3:
N.C. Relay
2-WIRE
TRANSMITTER
Shortcircuit
Portection
24V DC
Supply
Ry
Ry
+
+
–
1
2
L4 OUTPUT
L1 OUTPUT
COM
L4 OUTPUT
L1 OUTPUT
COM
9
6
9
6
3
8
7
5
–
Digital
Computation
Circuit
200Ω
+
MONITOR
4
3
V
(1 – 5VDC)
–
50Ω
Ry
Ry
L3 OUTPUT
L2 OUTPUT
COM
L3 OUTPUT
L2 OUTPUT
COM
8
CONFIGURATOR
JACK
7
Digital
Computation
5
U(+)
10
11
CONTROL SW
POWER
V(–)
Base Socket
■OUTPUT CODE 5: SPDT Relay
2-WIRE
TRANSMITTER
N.C.
N.O.
COM
N.C.
N.O.
COM
U(+)
V(–)
9
6
Shortcircuit
Portection
24V DC
Supply
Ry
Ry
+
+
–
1
2
L1 OUTPUT
–
3
Digital
Computation
Circuit
200Ω
+
8
MONITOR
4
V
(1 – 5VDC)
–
50Ω
L2 OUTPUT
POWER
7
CONFIGURATOR
JACK
5
10
11
Digital
Computation
CONTROL SW
Base Socket
■
When 24V DC is Not Used
■Relay Protection
• AC Powered
• DC Powered
Inductive
Load (Coil)
Inductive
Load (Coil)
No Connection
1
2
4
Diode, Varistor or
CR Circuit
Varistor or Spark
Quenching Circuit
+
LOAD
LOAD
200Ω
INPUT
–
U
50Ω
Specifications are subject to change without notice.