MATP-600MY [MSYSTEM]

Lightning Surge Protectors for Electronics Equipment M-RESTER;
MATP-600MY
型号: MATP-600MY
厂家: M-SYSTEM    M-SYSTEM
描述:

Lightning Surge Protectors for Electronics Equipment M-RESTER

文件: 总3页 (文件大小:136K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: MATP  
Line: M5 screw terminal (torque: 2.5 N·m)  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
Alarm output: Tension clamp  
Applicable wire size  
Line: See the drawing below.  
Alarm output: 0.13 to 1.5 mm  
Screw terminal  
SURGE PROTECTOR FOR PHOTOVOLTAIC SYSTEM  
Functions & Features  
2, stripped length 8 mm  
• Surge protection for photovoltaic array and power  
conditioner.  
Line: Nickel-plated steel  
Alarm output: Tin-plated copper alloy  
Housing material: Flame-resistant resin (black)  
Alarm output: Trips when the thermal breaker operates.  
(N.C. contact)  
•High discharge current capacity 20 kA or 40 kA (8/20 μs)  
• Degraded head element is automatically separated from  
the power lines by the incorporated thermal breaker, and  
the LED lamp (turns off) and the relay contact alerts the  
failure status.  
Rated load:  
250 V AC @50 mA (resistive load)  
• Breakdown of the surge protector remotely detected with  
the alarm output  
24 V DC @50 mA (resistive load)  
Safety function: Thermal breaker incorporated  
Monitor LED: Green LED turns on during normal conditions  
between 150 and 600 V DC, and turns off during failure  
condition, power off and the thermal breaker operating.  
• Applicable Solderless Terminal Size  
diameter d  
d : M5 use  
B ≤ 13.0 mm  
F ≥ 7.0 mm  
(F ≥ 8.2 mm for sharing terminals)  
T ≤ 1.8 mm  
F
MODEL: MATP–600[1][2]  
INSTALLATION  
ORDERING INFORMATION  
• Code number: MATP-600[1][2]  
Specify a code from below for each [1] and [2].  
(e.g.MATP-600MA)  
Operating temperature: -25 to +80°C (-13 to +176°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: DIN Rail  
Weight  
MATP-600Mx: 200 g (0.44 lb)  
MATP-600Hx: 250 g (0.55 lb)  
OPERATIONAL VOLTAGE  
600: 600 V DC  
PERFORMANCE  
[1] MAXIMUM DISCHARGE CURRENT  
M: 20kA (8/20 μsec.)  
Max. continuous operating voltage (Uc): 600 V DC  
Discharge voltage: (Line to earth) 600 V DC  
Maximum surge voltage: 2.5 kV  
Maximum (Imax) and Nominal (In) discharge current: (8/ 20  
μs)  
H: 40kA (8/20 μsec.)  
[2] ALARM OUTPUT  
A: With  
• MATP-600Mx: 20 kA (Imax), 10 kA (In)  
• MATP-600Hx: 40 kA (Imax), 20 kA (In)  
Response time: ≤ 4 nsec  
Y: Without  
Leakage current: ≤ 1 mA  
GENERAL SPECIFICATIONS  
Construction: Standalone; terminal access at the front  
Degree of protection: IP20 (If the solderless terminals are  
covered with insulation tubes.)  
Insulation resistance: ≥ 100 MΩ with 500 V DC (line to  
alarm output)  
Dielectric strength: 2000 V AC @ 1 minute (line to alarm  
output)  
Surge protection type: Voltage limiting type one-port SPD  
Connection  
Surge protection: IEC 61643-1 Class II  
MATP SPECIFICATIONS  
ES-8150 Rev.4 Page 1/3  
http://www.m-system.co.jp/  
MODEL: MATP  
CONNECTION EXAMPLES  
CONNECTION DIAGRAM  
10m min.  
Switch Gear  
Common Enclosure  
Distribution Board  
DC  
Blocking Diode  
L+  
Photovoltaic  
Array  
L–  
AC  
*1  
L−  
L+  
L−  
L+  
SPD  
SPD  
*2, *3  
*2, *3  
*1. When the wiring distance is longer than 10 m between the power conditioner and the surge protector in the switch gear, install near the power  
conditioner.  
*2. Cable length between the branch point and the earthing: 0.5 m or less recommended  
*3. When the solar panel manufacturer requires earthing at negative line of DC side, do NOT use the earth terminal of the SPD but use the  
L- terminal. If also, earthing at positive line is necessary, earth the L+ terminal.  
CIRCUIT BREAKER POSITION  
If you want to use circuit breaker as SPD maintenance switch, insert a wiring MCCB for DC on SPD power side (diagram below).  
Even when the output current of solar cell array is low, use 20 AT or more for wiring MCCB.  
Switch Gear  
Wiring MCCB  
Blocking Diode  
L+  
Solar Cell  
Array  
L–  
L−  
L+  
L+  
Solar Cell  
Array  
SPD  
L–  
L+  
Solar Cell  
Array  
L–  
MATP SPECIFICATIONS  
ES-8150 Rev.4 Page 2/3  
http://www.m-system.co.jp/  
MODEL: MATP  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
80 (3.15)  
60 (2.36)  
50 (1.97)  
15 (.59) 15 (.59)  
5–M5 SCREW  
TERMINAL COVER  
L–  
L+  
DIN RAIL  
35mm wide  
SPECIFICATION  
MONITOR LED  
[3.4 (.13)]  
ALARM OUTPUT  
TERMINAL  
*
15 (.59)  
45°  
(WIRE INSERTION ANGLE)  
12.5 (.49)  
A0 A1 NC  
*
Only for 'Alarm output' code 'A.'  
SCHEMATIC CIRCUITRY  
L
+
L
Monitor LED  
Display  
Circuit  
ѳ
ѳ
ѳ
ѳ
A0 A1 NC  
ѳ
: Thermal breaker  
Note: Terminals A0 & A1 are available for ‘Alarm output’ code ‘A.’  
Specifications are subject to change without notice.  
MATP SPECIFICATIONS  
ES-8150 Rev.4 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

MATPH

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MATPH1000MA

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MATPH1000MY

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MATPH750MA

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MATPH750MY

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MATRIX

4x6 RF Switch Matrix 800900 MHz
ETC

MATV-0816

IC 1-CH 8-BIT PROPRIETARY METHOD ADC, PARALLEL ACCESS, DMA22, PACKAGE-22, Analog to Digital Converter
ADI

MAU01-05S05M

DC-DC CONVERTER 1W
MINMAX

MAU01-05S12M

DC-DC CONVERTER 1W
MINMAX

MAU01-05S15M

DC-DC CONVERTER 1W
MINMAX

MAU01-12S05M

DC-DC CONVERTER 1W
MINMAX

MAU01-12S12M

DC-DC CONVERTER 1W
MINMAX