MD7FB-FG0/Q [MSYSTEM]

Lightning Surge Protectors for Electronics Equipment M-RESTER;
MD7FB-FG0/Q
型号: MD7FB-FG0/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Lightning Surge Protectors for Electronics Equipment M-RESTER

文件: 总3页 (文件大小:127K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: MD7FB  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
LIGHTNING SURGE PROTECTOR FOR  
FOUNDATION Fieldbus  
(ultra-slim)  
APPLICABLE NETWORK  
FOUNDATION Fieldbus and other networks complied with  
IEC 61158-2  
Functions & Features  
• High discharge current capacity 20 kA (8 / 20 μs), 1 kA (10  
/ 350 μs)  
Caution: Power supply to the bus must be limited to 400 mA  
or less.  
• Ultra-thin 7-mm-wide module can be mounted in high  
density  
• Excellent protection employing multi-stage SPD circuits  
• DIN rail mounting and grounding  
• Shield terminal provided  
GENERAL SPECIFICATIONS  
Construction: Slim-sized front terminal structure  
Degree of protection: IP20  
Connection: Euro terminal block (torque 0.3 N·m)  
Applicable wire size: 0.2 – 2.5 mm  
2, stripped length 8 mm  
7 [.28]  
Grounding: DIN Rail  
Housing material: Flame-resistant resin (black)  
INSTALLATION  
95  
[3.74]  
Operating temperature: -25 to +85°C (-13 to +185°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: DIN Rail (TH35-7.5, 1-mm-thick)  
Oxide film on the surface of an aluminium DIN rail may  
lower the electric conductivity between this module and the  
ground. Use a steel or copper rail.  
98  
[3.86]  
mm [inch]  
Weight: 70 g (2.5 oz)  
MODEL: MD7FB–[1]0[2]  
PERFORMANCE  
LINE TO  
LINE  
LINE TO  
EARTH  
SHLD TO  
EARTH  
ORDERING INFORMATION  
• Code number: MD7FB-[1]0[2]  
Specify a code from below for each of [1] and [2].  
(e.g. MD7FB-FF0/Q)  
Max. continuous  
operating voltage (Uc)  
±±32  
±602  
≤ 5µA  
±ꢀ602  
±ꢁ002  
≤ 5µA  
±ꢀ602*ꢀ  
±ꢁ002*ꢀ  
≤ 5µA*ꢀ  
2oltage protection level  
(Up) @4k2 (.3 / 50 µs)  
• Specify the specification for option code /Q  
(e.g. /C01)  
Leakage current @Uc  
Response time  
≤ 4 nsec. ≤ 30 nsec. ≤ 30 nsec.*ꢀ  
Approx. capacitance  
@ꢀ0 kHz  
ꢀ500 pF  
ꢀ00 pF  
ꢀ00 pF*ꢀ  
[1] SHIELD TERMINAL (to earth)  
FF: Floating  
Max. discharge current  
(Imax)  
30kA (ꢁ / 30 µs)  
.0kA (ꢀ0 / ±50 µs)  
400mA  
FG: Grounding  
Nominal current (IN)  
Internal series resistance  
Surge protection  
.5Ω ±ꢀ0% per line  
IEC 6ꢀ64±-3ꢀ Categories Cꢀ, C3, Dꢀ  
SAFETY APPROVAL  
*. 2alues for the $oating type (FF). Shortcircuited for the ground-  
0: None  
ing type (FG).  
[2] OPTIONS  
blank: none  
/Q: Options other than the above (specify the specification)  
MD7FB SPECIFICATIONS  
ES-8066 Rev.9 Page 1/3  
https://www.m-system.co.jp/  
MODEL: MD7FB  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]  
8–M3 EURO  
WIRE INSERTION ANGLE: approx. 20°  
TERMINAL  
8
6
5
4
8
DIN RAIL  
ADAPTOR  
6
5
DIN RAIL  
4
(35 mm wide)  
1
2
3
7
1
2
3
7
(1.5 [.06])  
98 [3.86]  
7
[.28]  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
CONNECTION DIAGRAM  
Surge Side  
4
Protected Side  
M-RESTER  
Protected Device  
Series Resistance  
+
1
DISCHARGE  
ELEMENT  
Bus Line  
5
6
8
2
3
7
*2  
SHLD  
(SHLD)  
DISCHARGE  
ELEMENT  
*1  
DIN RAIL ADAPTOR  
(for grounding)  
FG  
*3  
*5  
Crossover Wire  
DIN RAIL  
*4  
Grounding  
*1. Choose the grounding (FG) when the shield wire is to be grounded.  
*2. When SHLD is not isolated from the bus line, DO NOT connect the surge protector’s terminal 7 to SHLD.  
*3. Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.  
Use a steel or copper rail.  
*4. Be sure to ground the DIN rail. Recommended grounding resistance max. 100 ohms.  
*5. Cross-wire from the DIN rail to the metal housing of the protected device to equalize the ground potential.  
Ground only the surge protector when the protected device has no grounding terminal.  
MD7FB SPECIFICATIONS  
ES-8066 Rev.9 Page 2/3  
https://www.m-system.co.jp/  
MODEL: MD7FB  
NETWORK CONFIGURATION  
M-RESTER  
*1  
G
G
G
G
Crossover Wire  
Protected  
Devices  
(Nodes)  
M-RESTER  
G
G
G
Protected  
Devices  
(Nodes)  
Crossover Wire  
*1. Fieldbus devices complying with IEC 61158-2 operate by a supply voltage between  
9V and 32V DC.  
Take the M-RESTER’s internal series resistance into consideration when determining the  
cable distance if there is a large current flow on the bus line.  
When the distance between nodes are relatively long (e.g. grouped and separated by cabinets),  
install the M-RESTER by each group of devices. Insert the M-RESTER at the surge side of the network.  
For detailed information on the network, refer to that provided by Fieldbus Foundation.  
Specifications are subject to change without notice.  
MD7FB SPECIFICATIONS  
ES-8066 Rev.9 Page 3/3  
https://www.m-system.co.jp/  

相关型号:

MD7IC18120GNR1

Single W-CDMA RF LDMOS Wideband Integrated Power Amplifier, 1805-1880 MHz, 30 W Avg., 28 V
NXP

MD7IC18120NR1

Single W-CDMA RF LDMOS Wideband Integrated Power Amplifier, 1805-1880 MHz, 30 W Avg., 28 V
NXP

MD7IC1812GNR1

RF/MICROWAVE NARROW BAND HIGH POWER AMPLIFIER
NXP

MD7IC1812NR1

Single W-CDMA RF LDMOS Wideband Integrated Power Amplifier, 1805-2170 MHz, 1.3 W Avg., 28 V
NXP

MD7IC2012GNR1

RF LDMOS Wideband Integrated Power Amplifiers
NXP

MD7IC2012N

RF LDMOS Wideband Integrated Power Amplifiers
NXP

MD7IC2012NR1

RF LDMOS Wideband Integrated Power Amplifiers
NXP

MD7IC2050GNR1

RF LDMOS Wideband Integrated Power Amplifiers
FREESCALE

MD7IC2050GNR1

Single W-CDMA RF LDMOS Wideband Integrated Power Amplifier, 1880-2100 MHz, 10 W Avg., 28 V
NXP

MD7IC2050NBR1

RF LDMOS Wideband Integrated Power Amplifiers
FREESCALE

MD7IC2050NR1

RF LDMOS Wideband Integrated Power Amplifiers
FREESCALE

MD7IC2050NR1

Single W-CDMA RF LDMOS Wideband Integrated Power Amplifier, 1880-2100 MHz, 10 W Avg., 28 V
NXP