MD7PM-FG0 [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MD7PM-FG0 |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总6页 (文件大小:157K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MD7PM
Lightning Surge Protectors for
Electronics Equipment M-RESTER
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
(CENELEC intrinsic safety (ATEX) not available)
LIGHTNING SURGE PROTECTOR FOR
POTENTIOMETER USE
(ultra-slim)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
Functions & Features
• High discharge current capacity 20 kA (8 / 20 μs), 1 kA
(10 / 350 μs)
/C02: Polyurethane coating
• Ultra-thin 7-mm-wide module can be mounted
in high density
GENERAL SPECIFICATIONS
Construction: Slim-sized front terminal structure
Degree of protection: IP20
• Excellent protection employing multi-stage SPD circuits
• DIN rail mounting and grounding
• Shield terminal provided
Connection: Euro terminal block (torque 0.3 N·m)
Applicable wire size: 0.2 – 2.5 mm2, stripped length: 8 mm
Grounding: DIN Rail
7 (.28)
Housing material: Flame-resistant resin (black)
INSTALLATION
Operating temperature: -25 to +85°C (-13 to +185°F)
(See Safety Parameters for use in a hazardous location.)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN Rail (TH35-7.5, 1-mm-thick)
Oxide film on the surface of an aluminium DIN rail may
lower the electric conductivity between this module and the
ground. Use a steel or copper rail.
95
(3.74)
98
(3.86)
mm (inch)
Weight: 70 g (2.5 oz)
MODEL: MD7PM–[1][2][3]
ORDERING INFORMATION
• Code number: MD7PM-[1][2][3]
Specify a code from below for each [1] through [3].
(e.g. MD7PM-FF0/Q)
For the safety approval code 2, specify the product’s
destination country using Ordering Information Sheet (No.
ESU-8057).
• Specify the specification for option code /Q
(e.g. /C01)
[1] SHIELD TERMINAL (line / earth)
FF: Floating / Floating
FG: Floating / Grounding
GF: Grounding / Floating
GG: Grounding / Grounding
[2] SAFETY APPROVAL
0: None
2: CENELEC intrinsic safety (ATEX)
MD7PM SPECIFICATIONS
ES-8055 Rev.9 Page 1/6
http://www.m-system.co.jp/
MODEL: MD7PM
PERFORMANCE
MODEL NO.
MD7PM-FF
MD7PM-FG
MD7PM-GF
MD7PM-GG
±7.5V
Max. continuous operating voltage (Uc) Line to Line
7.5V
Line to Earth
Line to SHLD
SHLD to Earth
±±16V
±±16V
±7.5V
±±16V
short
±±16V
short
Voltage protection level (Up)
@4kV (±.2 / 56 µs)
Line to Line
25V
Line to Earth
Line to SHLD
SHLD to Earth
Line to Line
±866V
±25V
±±266V
±866V
±866V
short
±25V
±866V
short
Leakage current @Uc
Response time
≤5µA
≤5µA
Other sections
Line to Line
≤4 nsec.
Other sections
≤26 nsec.
Max. discharge current (Imax)
26kA (8 / 26 µs), ±.6kA (±6 / 356 µs)
±66mA
Nominal current (I
N)
Internal series resistance
4.7Ω ±±60 per line
STANDARDS & APPROVALS
EU conformity:
ATEX Directive
Ex ia EN 60079-11
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
Safety approval:
CENELEC: Intrinsic safety (ATEX)
II 1G, Ex ia IIC; T4 and T5
EN 60079-0
EN 60079-11
Surge protection: IEC 61643-21
(Categories C1, C2, D1)
SAFETY PARAMETERS
■ CENELEC / ATEX IS DATA
Ui (Vmax)
16V
any
Ii (Imax)
Ci
Li
35 nF
0 µH
Temp. Class
Range
Parameter
1.3W
-25 to +40°C
-25 to +60°C
-25 to +80°C
-25 to +40°C
Pi
T4
T5
1.2W
1.0W
1.0W
MD7PM SPECIFICATIONS
ES-8055 Rev.9 Page 2/6
http://www.m-system.co.jp/
MODEL: MD7PM
DESCRIPTIONS
■ SELECTING SHIELD TERMINAL TYPE
• The surge protector has a dedicated shield terminal effective for easy shield wiring and surge protection.
• Review the shield method (grounding, non-grounding, connecting to SG, etc.) required by the protected device or system.
• There is no electrical effect to the shield by installing the surge protector, but an appropriate shield terminal type must be
selected to suit user applications.
• Refer to the flow chart below to choose.
Cable
With Shield
Without Shield
Shield to Signal
Isolated
Shield to Signal
Not Isolated
Signal to Earth
Isolated
Signal to Earth
Not Isolated
Shield
Not Grounded
Shield
Grounded
Shield
Not Grounded
Shield
Grounded
FF
FG
GF
GG
FF
GG
CONNECTION EXAMPLES
Metal Enclosure
Protected Side
POT
Surge Side
Surge Side
Protected Side
Protected Device
M-RESTER
max.
M-RESTER
max.
INPUT
min.
1
4
5
6
8
4
5
6
8
1
2
3
7
+
+
2
3
–
min.
*4
7
SG
(SHLD)
DIN RAIL
ADAPTOR
DIN RAIL
ADAPTOR
FG
*3
Crossover Wire
*3
Crossover Wire
*1
*1
DIN RAIL
DIN RAIL
*2
*2
*1. Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.
Use a steel or copper rail.
*2. Be sure to ground the DIN rail. Recommended grounding resistance ≤100Ω
*3. Cross-wire between the DIN rail and the metal housing of the protected device to equalize the earth potential.
Ground only the surge protector when the protected device has no ground terminal.
*4. Shield wiring method is an example. Proceed according to the system requirements.
MD7PM SPECIFICATIONS
ES-8055 Rev.9 Page 3/6
http://www.m-system.co.jp/
MODEL: MD7PM
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
8–M3 EURO
TERMINAL
WIRE INSERTION ANGLE: approx. 20°
8
6
5
4
8
DIN RAIL
ADAPTOR
6
5
DIN RAIL
4
(35 mm wide)
1
2
3
7
1
2
3
7
[1.5 (.06)]
98 (3.86)
7
(.28)
MD7PM SPECIFICATIONS
ES-8055 Rev.9 Page 4/6
http://www.m-system.co.jp/
MODEL: MD7PM
SCHEMATIC CIRCUITRY
SHIELD TERMINAL
MODEL NO.
SCHEMATIC CIRCUITRY
APPLICATIONS
Surge Side
Protected Side
•Line to SHLD: •MD7PM-FFx
Floating
•Earth to SHLD:
Floating
•Standard type
•To protect a device having
isolation between Signal
and Earth.
•When SHLD should be
floating against the earth.
(single-end grounding)
Series Resistance
+
+
–
4
5
1
2
+
+
–
DISCHARGE
ELEMENT
DISCHARGE
ELEMENT
6
8
3
7
DISCHARGE
ELEMENT
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
Surge Side
Protected Side
•Line to SHLD: •MD7PM-FGx
Floating
•Earth to SHLD:
Grounding
•To protect a device having
isolation between Signal
and Earth.
•When SHLD should be
grounded. (single- or both-
end grounding)
Series Resistance
+
+
–
4
5
1
2
+
+
–
DISCHARGE
ELEMENT
DISCHARGE
ELEMENT
6
8
3
7
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
Surge Side
Protected Side
•Line to SHLD: •MD7PM-GFx
Grounding
•Earth to SHLD:
Floating
•To protect a device having
isolation between Signal
and Earth.
•When SHLD wire should be
connected to SG terminal
of the protected device.
(SHLD is not grounded to
the earth.)
Series Resistance
+
+
–
4
5
1
2
+
+
–
DISCHARGE
ELEMENT
DISCHARGE
ELEMENT
6
8
3
7
DISCHARGE
ELEMENT
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
Surge Side
Protected Side
•Line to SHLD: •MD7PM-GGx
Grounding
•Earth to SHLD:
Grounding
•To protect a device which
does not have a good
dielectric strength between
Signal and Earth.
Series Resistance
+
+
–
4
5
1
2
+
+
–
DISCHARGE
ELEMENT
DISCHARGE
ELEMENT
6
8
3
7
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
Sections enclosed with broken line may differ depending upon the models.
MD7PM SPECIFICATIONS
ES-8055 Rev.9 Page 5/6
http://www.m-system.co.jp/
MODEL: MD7PM
Specifications are subject to change without notice.
MD7PM SPECIFICATIONS
ES-8055 Rev.9 Page 6/6
http://www.m-system.co.jp/
相关型号: