MD7RB-GG2/Q [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MD7RB-GG2/Q |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总6页 (文件大小:154K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MD7RB
Lightning Surge Protectors for
Electronics Equipment M-RESTER
[2] SAFETY APPROVAL
0: None
2: CENELEC intrinsic safety (ATEX)
LIGHTNING SURGE PROTECTOR FOR RTD USE
(ultra-slim)
[3] OPTIONS
blank: none
Functions & Features
/Q: With options (specify the specification)
(CENELEC intrinsic safety (ATEX) not available)
• High discharge current capacity 20 kA (8 / 20 μs), 1 kA (10
/ 350 μs)
• Ultra-thin 7-mm-wide module can be mounted
in high density
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Excellent protection employing multi-stage SPD circuits
• DIN rail mounting and grounding
• Shield terminal provided
/C02: Polyurethane coating
• Does not affect instrumentation signal when combined
with a 3-wire RTD, thanks to the internal high accuracy
series resistors
GENERAL SPECIFICATIONS
Construction: Slim-sized front terminal structure
Degree of protection: IP20
7 (.28)
Connection: Euro terminal block (torque 0.3 N·m)
Applicable wire size: 0.2 – 2.5 mm2, stripped length 8 mm
Grounding: DIN Rail
Housing material: Flame-resistant resin (black)
95
(3.74)
INSTALLATION
Operating temperature: -25 to +85°C (-13 to +185°F)
(See Safety Parameters for use in a hazardous location.)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN Rail (TH35-7.5, 1-mm-thick)
Oxide film on the surface of an aluminium DIN rail may
lower the electric conductivity between this module and the
ground. Use a steel or copper rail.
98
(3.86)
mm (inch)
MODEL: MD7RB–[1][2][3]
Weight: 70 g (2.5 oz)
ORDERING INFORMATION
• Code number: MD7RB-[1][2][3]
Specify a code from below for each [1] through [3].
(e.g. MD7RB-FF0/Q)
For the safety approval code 2, specify the product’s
destination country using Ordering Information Sheet (No.
ESU-8057).
• Specify the specification for option code /Q
(e.g. /C01)
[1] SHIELD TERMINAL (line / earth)
FF: Floating / Floating
FG: Floating / Grounding
GF: Grounding / Floating
GG: Grounding / Grounding
MD7RB SPECIFICATIONS
ES-8054 Rev.10 Page 1/6
http://www.m-system.co.jp/
MODEL: MD7RB
PERFORMANCE
MODEL NO.
MD7RB-FF
MD7RB-FG
±ꢀ603
MD7RB-GF
MD7RB-GG
Max. continuous operating voltage (Uc)
Line to Line
±±3
Line to Earth
Line to SHLD
SHLD to Earth
Line to Line
±7.53
±ꢀ603
±7.53
±ꢀ603
short
±ꢀ603
short
±253
short
3oltage protection level (Up)
@4k3 (ꢀ.2 / 50 µs)
±253
Line to Earth
Line to SHLD
SHLD to Earth
Line to Line
±ꢁ003
±ꢁ003
short
±ꢀ2003
±ꢁ003
±253
±ꢁ003
Leakage current @Uc
Response time
≤ 5µA
≤ 5µA
Other sections
Line to Line
≤ 4 nsec.
≤ 20 nsec.
Other sections
Max. discharge current (Imax)
20kA (ꢁ / 20 µs), ꢀ.0kA (ꢀ0 / ±50 µs)
ꢀ00mA
Nominal current (I )
N
Internal series resistance
Surge protection
5.ꢀ2Ω ±0.±ꢂ, ±±0 ppm/ꢃC per line
IEC 6ꢀ64±-2ꢀ Categories Cꢀ, C2, Dꢀ
STANDARDS & APPROVALS
EU conformity:
ATEX Directive
Ex ia EN 60079-11
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EN 50581
Safety approval:
CENELEC: Intrinsic safety (ATEX)
II 1G, Ex ia IIC; T4 and T5
EN 60079-0
EN 60079-11
SAFETY PARAMETERS
■ CENELEC / ATEX IS DATA
Ui (Vmax)
7V
Ii (Imax)
any
Ci
Li
50 nF
0 µH
Temp. Class
Range
Parameter
1.3W
-25 to +40°C
-25 to +60°C
-25 to +80°C
-25 to +40°C
Pi
T4
T5
1.2W
1.0W
1.0W
MD7RB SPECIFICATIONS
ES-8054 Rev.10 Page 2/6
http://www.m-system.co.jp/
MODEL: MD7RB
DESCRIPTIONS
■ SELECTING SHIELD TERMINAL TYPE
• The surge protector has a dedicated shield terminal effective for easy shield wiring and surge protection.
• Review the shield method (grounding, non-grounding, connecting to SG, etc.) required by the protected device or system.
• There is no electrical effect to the shield by installing the surge protector, but an appropriate shield terminal type must be
selected to suit user applications.
• Refer to the flow chart below to choose.
Cable
With Shield
Without Shield
Shield to Signal
Isolated
Shield to Signal
Not Isolated
Signal to Earth
Isolated
Signal to Earth
Not Isolated
Shield
Not Grounded
Shield
Grounded
Shield
Not Grounded
Shield
Grounded
FF
FG
GF
GG
FF
GG
CONNECTION EXAMPLES
Sheath or
Protected Side
Metal Enclosure
Surge Side
Surge Side
Protected Side
Protected Device
M-RESTER
M-RESTER
RTD
A
B
B
1
2
3
7
4
5
6
8
4
5
6
8
1
2
3
7
A
B
INPUT
B
*4
SG
DIN RAIL
ADAPTOR
(SHLD)
DIN RAIL
ADAPTOR
FG
*3
Crossover Wire
*1
*1
DIN RAIL
DIN RAIL
*2
*2
*1. Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.
Use a steel or copper rail.
*2. Be sure to ground the DIN rail. Recommended grounding resistance ≤100Ω
*3. Cross-wire between the DIN rail and the metal housing of the protected device to equalize the earth potential.
Ground only the surge protector when the protected device has no ground terminal.
*4. Shield wiring method is an example. Proceed according to the system requirements.
MD7RB SPECIFICATIONS
ES-8054 Rev.10 Page 3/6
http://www.m-system.co.jp/
MODEL: MD7RB
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
8–M3 EURO
TERMINAL
WIRE INSERTION ANGLE: approx. 20°
8
6
5
4
8
DIN RAIL
ADAPTOR
6
5
DIN RAIL
4
(35 mm wide)
1
2
3
7
1
2
3
7
[1.5 (.06)]
98 (3.86)
7
(.28)
MD7RB SPECIFICATIONS
ES-8054 Rev.10 Page 4/6
http://www.m-system.co.jp/
MODEL: MD7RB
SCHEMATIC CIRCUITRY
SHIELD TERMINAL
MODEL NO.
SCHEMATIC CIRCUITRY
APPLICATIONS
Surge Side
Protected Side
•Line to SHLD: •MD7RB-FFx
Floating
•Earth to SHLD:
Floating
•Standard type
Series Resistance
DISCHARGE
ELEMENT
•To protect a device having
isolation between Signal
and Earth.
•When SHLD should be
floating against the earth.
(single-end grounding)
4
1
2
5
DISCHARGE
ELEMENT
6
8
3
7
DISCHARGE
ELEMENT
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
Surge Side
4
Protected Side
1
•Line to SHLD: •MD7RB-FGx
Floating
•Earth to SHLD:
Grounding
•To protect a device having
isolation between Signal
and Earth.
•When SHLD should be
grounded. (single- or both-
end grounding)
Series Resistance
DISCHARGE
ELEMENT
5
2
DISCHARGE
ELEMENT
6
8
3
7
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
Surge Side
4
Protected Side
1
•Line to SHLD: •MD7RB-GFx
Grounding
•Earth to SHLD:
Floating
•To protect a device having
isolation between Signal
and Earth.
•When SHLD wire should be
connected to SG terminal
of the protected device.
(SHLD is not grounded to
the earth.)
Series Resistance
DISCHARGE
ELEMENT
5
2
DISCHARGE
ELEMENT
6
8
3
7
DISCHARGE
ELEMENT
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
Surge Side
4
Protected Side
1
•Line to SHLD: •MD7RB-GGx
Grounding
•Earth to SHLD:
Grounding
•To protect a device which
does not have a good
dielectric strength between
Signal and Earth.
Series Resistance
DISCHARGE
ELEMENT
5
2
DISCHARGE
ELEMENT
6
8
3
7
(SHLD)
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
Sections enclosed with broken line may differ depending upon the models.
MD7RB SPECIFICATIONS
ES-8054 Rev.10 Page 5/6
http://www.m-system.co.jp/
MODEL: MD7RB
Specifications are subject to change without notice.
MD7RB SPECIFICATIONS
ES-8054 Rev.10 Page 6/6
http://www.m-system.co.jp/