MDM2A24 [MSYSTEM]
Lightning Surge Protectors for Electronics Equipment M-RESTER;型号: | MDM2A24 |
厂家: | M-SYSTEM |
描述: | Lightning Surge Protectors for Electronics Equipment M-RESTER |
文件: | 总3页 (文件大小:113K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: MDM2A-24
Housing material: Flame-resistant resin (black)
Lightning Surge Protectors for
Electronics Equipment M-RESTER
Alarm indicators
PWR: The green LED turns on while the power is supplied.
ALM: Tricolor LED (green/amber/red)
LIGHTNING SURGE PROTECTOR FOR
· Remains off when the power supply is first turned on.
· Green: The unit has received one or more surges.
· Amber: Replacement is recommended.
STANDARD SIGNAL LINE & PULSE USE
(life monitor, 24 V DC line voltage)
· Red: The life span has ended.
Functions & Features
Degradation judged: When the leakage current at the
voltage limiter exceed approx. 7.5 μA.
• Designed specifically for 4 – 20 mA DC and
pulse signal line including both 4-wire and 2-wire
transmitters
Life time judged: When the number of discharges of the
discharge element reaches the expected life span.
Alarm output: The N.C. contact is on when the life span of
the discharge elements has ended, when the voltage limiter
has degraded, and/or when the power supply is removed.
Rating: 125 V AC @ 0.5 A (cos ø = 1)
• Absorbs surges only without affecting instrumentation
signal
• Life monitor function helps you to decide when you should
replace the surge protector; reduces maintenance and
prevents downtime
30 V DC @ 1 A (resistive load)
• LED display and alarm contact output indicate the
degradation and life span of the surge protection circuits
Maximum switching voltage: 125 V AC or 110 V DC
Maximum switching power: 62.5 VA or 30 W
Minimum load: 5 V DC @ 1 mA
29.5 [1.16]
INSTALLATION
Power consumption
M
od
el
76
[2.99]
•AC: Approx. 2 VA at 100 V
Approx. 3 VA at 200 V
Approx. 4 VA at 240 V
PW
R
AL
M
124
•DC: Approx. 1.5 W
[4.88]
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lb)
mm [inch]
MODEL: MDM2A–24–[1]
PERFORMANCE
Discharge voltage (peak voltage)
ORDERING INFORMATION
• Code number: MDM2A-24-[1]
Specify a code from below for [1].
(e.g. MDM2A-24-M2)
Line to line: 30 V min.
Line to ground: ±300 V min.
Maximum surge voltage
Line to line: 45 V max.
[1] POWER INPUT
AC Power
Line to ground: ±650 V max.
(The maximum voltage that could pass through M-RESTER.
Protected equipment must be able to withstand this voltage
for very short time period.)
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
Response time: ≤ 0.1 μsec.
R: 24 V DC
Leakage current:
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P: 110 V DC
Line to line: ≤ 5 μA @ 30 V DC
Line to ground: ≤ 5 μA @ ±140 V DC
Discharge current capacity: 5000 A (8 / 20 μsec.)
Max. load current: 100 mA
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
GENERAL SPECIFICATIONS
Construction: Plug-in
Insulation resistance: ≥ 100 MΩ with 500 V DC
(surge protector circuit to alarm output to power)
Dielectric strength: 2000 V AC @ 1 minute
Connection: M3 screw terminals (torque 0.8 N·m)
MDM2A-24 SPECIFICATIONS
ES-8214 Rev.8 Page 1/3
https://www.m-system.co.jp/
MODEL: MDM2A-24
(surge protector circuit to power to ground)
Internal series resistance: 20 Ω ±10 % (including return)
Maximum line voltage: 30 V
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (alarm output)
Installation Category II (power)
Pollution degree 2
Surge protector circuit to power:
Reinforced insulation (300 V)
RoHS Directive
CONNECTION EXAMPLES
M-RESTER
Protected Equipment
4 – 20mA
+
–
+
–
+
–
+
–
7
8
9
4
5
6
CABLE SIDE
(surge side)
V
U
FG
FG
G
1
(–) (+)
11 10
PWR
Crossover
Wiring
V
U
2
Grounding
(100Ω or less)
ALARM OUTPUT
To POWER
SOURCE
G
Crossover Wiring
Surge Protector
for Power Supply Line
Be sure to cross-wire as indicated above.
GROUNDING
PROTECTED
EQUIPMENT
M-RESTER
G
G
GROUNDING
(100 ohms or less)
CROSSOVER WIRE
A crossover wire between M-RESTER ground and ground or metallic
housing of equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
MDM2A-24 SPECIFICATIONS
ES-8214 Rev.8 Page 2/3
https://www.m-system.co.jp/
MODEL: MDM2A-24
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
6 [.24]
DIN RAIL
35mm wide
3
2
5
1
4
6
2–4.2x5
[.17x.20]
MTG HOLE
6 [.24] deep
9
8
7
11–M3
SCREW
11 10
21.5 [.85] 10 [.39]
84 [3.31]
114 [4.49]
22 [.87]
(4 [.16])
29.5 [1.16]
• When mounting, no extra space is needed between units.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
20Ω
7
8
4
5
+
–
+
–
PROTECTED
EQUIPMENT
Discharge
Elements
CABLE SIDE
Voltage Limiter
CT
9
6
G
FG
PWR LED
ALM LED
10
11
U(+)
V(–)
Leakage Current
Detector
Surge
Counter
1
2
POWER
Ry
ALARM OUTPUT
Base Socket
Specifications are subject to change without notice.
MDM2A-24 SPECIFICATIONS