MDP-4R/Q [MSYSTEM]

Lightning Surge Protectors for Electronics Equipment M-RESTER;
MDP-4R/Q
型号: MDP-4R/Q
厂家: M-SYSTEM    M-SYSTEM
描述:

Lightning Surge Protectors for Electronics Equipment M-RESTER

文件: 总4页 (文件大小:128K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: MDP-4R  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
INSTALLATION  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
LIGHTNING SURGE PROTECTOR FOR  
Weight: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN  
rail mounting adapter  
RS-485 / RS-422  
Functions & Features  
• Designed specifically for the network  
• No interruption of transmission signal by unplugging the  
head element module  
PERFORMANCE  
Max. continuous operating voltage (Uc):  
B to C: ±5 V  
B or C to A: 5 V  
Line to earth: ±140 V  
Voltage protection level (Up):  
• @ 2 kV (1 kA)  
Lot.NO  
MDEIJPAN1430B  
2 to 3: ±20 V  
M•STER  
MODEL  
2 or 3 to 1: 20 V  
Line to earth: ±500 V  
Response time:  
Line to line: ≤ 4 nsec.  
MODEL: MDP–4R[1]  
Line to earth: ≤ 20 nsec.  
Leakage current:  
B to C: ≤ 0.2 mA @ ±5 V DC  
B or C to A: ≤ 0.2 mA @ 5 V DC  
Line to earth: ≤ 10 μA @ ±140 V DC  
Max. discharge current (Imax): 5000 A (8 / 20 μs)  
ORDERING INFORMATION  
• Code number: MDP-4R[1]  
Specify a code from below for [1].  
(e.g. MDP-4R/A33/Q)  
Nominal current (I ): 100 mA  
N
• Specify the specification for option code /Q  
(e.g. /C01)  
Internal series resistance: Approx. 4.5 Ω including return  
Capacitance @ 1 MHz:  
Line to line: ≤ 1000 pF  
[1] OPTIONS (multiple selections)  
DIN Rail Mounting Adapter  
blank: Without  
Line to earth: ≤ 100 pF  
Input attenuation: -0.5 dB or less @ DC to 2.0 MHz, Zo =  
110 Ω  
/A33: With adapter (model A-33)  
Other Options  
Surge protection: IEC 61643-21 Categories C1, C2  
blank: none  
/Q: Option other than the above (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
/C02: Polyurethane coating  
/C03: Rubber coating  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M4 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel  
Housing material: Flame-resistant resin (black)  
MDP-4R SPECIFICATIONS  
ES-8232 Rev.8 Page 1/4  
http://www.m-system.co.jp/  
MODEL: MDP-4R  
CONNECTION EXAMPLES  
Example: Protected devices have no SG terminals  
Protected Device  
MDP-4R  
MDP-4R  
Protected Device  
+
3
C
B
A
C
3
2
1
+
LINE  
LINE  
LINE  
LINE  
2
1
B
A
SG  
2
1
*
*
G
G
G
G
4
4
*
*
3
*
Grounding  
≤100  
Grounding  
≤100  
*1. Leave Terminal A when the shielded twisted-pair cable is not provided.  
*2. Leave Terminal 1 when the protected device has no SG (Signal Ground) terminal.  
*3. Cross wire to the surge protector’s G terminal when grounding the shield wire.  
*4. Cross-over wire between G terminals of the surge protector and the protected device is required.  
Ground only the surge protector if the protected device has no G terminal.  
Example: Each SG terminal is connected with triplex cable  
Protected Device MDP-4R  
MDP-4R  
Protected Device  
+
+
LINE  
LINE  
3
C
B
A
C
3
2
1
LINE  
2
1
B
A
LINE  
SG  
SG  
G
1
G
G
G
*
3
3
*
*
2
*
Grounding  
≤100  
Grounding  
≤100  
*1. Provide electrical insulation with insulating tape and the like so that the live part is not exposed,  
as over voltage may generate on the shield wire.  
*2. Cross wire to the surge protector’s G terminal when grounding the shield wire.  
*3. Cross-over wire between G terminals of the surge protector and the protected device is required.  
Ground only the surge protector if the protected device has no G terminal.  
GROUNDING  
PROTECTED  
EQUIPMENT  
M-RESTER  
G
G
GROUNDING  
(100 ohms or less)  
CROSSOVER WIRE  
A crossover wire between M-RESTER ground and the ground or  
metallic housing of the equipment is required for protection.  
If the protected equipment has no ground terminal, ground the  
M-RESTER only.  
When the M-RESTER is mounted with DIN Rail Mounting Adapter,  
connect the grounding wire to the mounting screw of the M-RESTER.  
MDP-4R SPECIFICATIONS  
ES-8232 Rev.8 Page 2/4  
http://www.m-system.co.jp/  
MODEL: MDP-4R  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
STANDARD  
80 (3.15)  
53 (2.09)  
2–5 (.20) dia.  
MTG HOLE  
31.5 (1.24)  
27 (1.06)  
HEAD ELEMENT  
3
2
1
BASE  
6–M4 TERMINAL SCREW  
C
B
A
GROUND TERMINAL (G)  
(used as mounting bracket)  
WITH DIN RAIL MOUNTING ADAPTER  
8.5  
(.33)  
[3.3 (.13)]  
80 (3.15)  
53 (2.09)  
27 (1.06)  
31.5 (1.24)  
DIN RAIL  
35mm wide  
3
2
1
6–M4 TERMINAL SCREW  
C
B
A
2–M4 MOUNTING SCREW  
(used as ground terminal (G))  
MOUNTING REQUIREMENTS unit: mm (inch)  
2–M4 SCREW  
33 (1.30) min.  
MDP-4R SPECIFICATIONS  
ES-8232 Rev.8 Page 3/4  
http://www.m-system.co.jp/  
MODEL: MDP-4R  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
1.5W  
1.5W  
1.0 W  
1.0 W  
C
B
3
2
LINE  
LINE  
HEAD  
ELEMENT  
2.0 W  
2.0 W  
Discharge  
Element  
Surge  
Side  
Protected  
Device Side  
ZD  
ZD ZD  
ZD  
SG A  
1
SG  
BASE  
G
GROUND TERMINAL  
(used as mounting attachment)  
Specifications are subject to change without notice.  
MDP-4R SPECIFICATIONS  
ES-8232 Rev.8 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

MDP-5

暂无描述
POMONA

MDP-65-1

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-65-1/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-65-1/CE

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-65-1/N

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-65-1/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-65T

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-65T/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-65T/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-D12

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-D12/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-D12/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM