MODEL: MDP-PA  
Lightning Surge Protectors for  
Electronics Equipment M-RESTER  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
Connection: M4 screw terminals (torque 0.8 N·m)  
Screw terminal: Nickel-plated steel  
Housing material: Flame-resistant resin (black)  
LIGHTNING SURGE PROTECTOR FOR  
PROFIBUS-PA  
Functions & Features  
INSTALLATION  
• Designed specifically for the network  
• No interruption of transmission signal by unplugging the  
head element module  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 100 g (0.22 lb), standard; 125 g (0.28 lb), with DIN  
rail mounting adapter  
Lot.NO  
        4
PERFORMANCE  
Max. continuous operating voltage (Uc):  
M•STER  
MODEL  
Line to line: 27 V  
Line to earth: ±160 V  
SHLD to earth: ±160 V  
Voltage protection level (Up):  
• @ 2 kV (1 kA)  
MODEL: MDP–PA[1]  
Line to line: ±60 V  
ORDERING INFORMATION  
• Code number: MDP-PA[1]  
Specify a code from below for [1].  
(e.g. MDP-PA/A33/Q)  
Line to earth: ±600 V  
SHLD to earth: ±600 V  
Response time:  
Line to line: ≤ 4 nsec.  
• Specify the specification for option code /Q  
(e.g. /C01)  
Line or SHLD to earth: ≤ 20 nsec.  
Leakage current:  
Line to line: ≤ 5 μA @ ±27 V  
Line to earth: ≤ 5 μA @ ±160 V  
SHLD to earth: ≤ 5 μA @ ±160 V  
Max. discharge current (Imax): 5000 A (8 / 20 μs)  
[1] OPTIONS (multiple selections)  
DIN Rail Mounting Adapter  
blank: Without  
Nominal current (I ): 500 mA  
N
/A33: With adapter (model A-33)  
Other Options  
Internal series resistance: ≤ 3.3 Ω including return  
Capacitance @ 1 MHz:  
blank: none  
Line to line: ≤ 1500 pF  
/Q: Option other than the above (specify the specification)  
Line to earth: ≤ 100 pF  
SHLD to earth: ≤ 100 pF  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
Surge protection: IEC 61643-21 Categories C1, C2  
/C02: Polyurethane coating  
/C03: Rubber coating  
APPLICABLE NETWORK  
PROFIBUS-PA , Foundation Fieldbus and other networks  
complied with IEC 61158-2  
Note 1: This unit is not approved for classified locations.  
Note 2: Power supply to the bus must be limited to 500 mA  
or less.  
MDP-PA SPECIFICATIONS  
ES-8207 Rev.9 Page 1/4  
http://www.m-system.co.jp/  
MODEL: MDP-PA  
CONNECTION EXAMPLES  
CONNECTION DIAGRAM  
M-RESTER  
Protected Device  
+
A
C
B
1
3
2
PA  
BUS  
*1  
SHLD  
*2  
G
G
Cross wiring  
Grounding  
≤ 100Ω  
*1. Cross wire to the surge protectors ‘G’ terminal when grounding the shield wire.  
If the shield wire is not to be grounded, connect it to ‘B’ terminal.  
*2. Follow instructions provided with the protected device whether ‘2’ terminal  
should be connected or not. However, if the shield terminal of the protected  
device is not isolated from PA BUS, DO NOT connect ‘2’ terminal to the  
protected device.  
NETWORK CONFIGURATION  
M-RESTER  
*1  
G
G
G
G
Crossover Wire  
Protected  
Devices  
(Nodes)  
M-RESTER  
G
G
G
Protected  
Devices  
(Nodes)  
Crossover Wire  
*1. Fieldbus devices complying with IEC 61158-2 operate by a supply voltage between  
9V and 32V DC.  
Take the MDP-PAs internal series resistance into consideration when determining the  
cable distance if there is a large current flow on the bus line.  
When the distance between nodes are relatively long (e.g. grouped and separated by cabinets),  
install the MDP-PA by each group of devices. Insert the MDP-PA at the surge side of the network.  
For detailed information on the network, refer to that provided by PROFIBUS International or  
Fieldbus Foundation.  
MDP-PA SPECIFICATIONS  
ES-8207 Rev.9 Page 2/4  
http://www.m-system.co.jp/  
MODEL: MDP-PA  
GROUNDING  
PROTECTED  
EQUIPMENT  
M-RESTER  
G
G
GROUNDING  
(100 ohms or less)  
CROSSOVER WIRE  
A crossover wire between M-RESTER ground and the ground or  
metallic housing of the equipment is required for protection.  
If the protected equipment has no ground terminal, ground the  
M-RESTER only.  
When the M-RESTER is mounted with DIN Rail Mounting Adapter,  
connect the grounding wire to the mounting screw of the M-RESTER.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
STANDARD  
80 (3.15)  
2–5 (.20) dia.  
31.5 (1.24)  
MTG HOLE  
53 (2.09)  
27 (1.06)  
HEAD ELEMENT  
3
2
1
BASE  
6–M4 TERMINAL SCREW  
C
B
A
GROUND TERMINAL (G)  
(used as mounting bracket)  
WITH DIN RAIL MOUNTING ADAPTER  
8.5  
(.33)  
[3.3 (.13)]  
80 (3.15)  
53 (2.09)  
27 (1.06)  
31.5 (1.24)  
DIN RAIL  
35mm wide  
3
2
1
6–M4 TERMINAL SCREW  
C
B
A
2–M4 MOUNTING SCREW  
(used as ground terminal (G))  
MDP-PA SPECIFICATIONS  
ES-8207 Rev.9 Page 3/4  
http://www.m-system.co.jp/  
MODEL: MDP-PA  
MOUNTING REQUIREMENTS unit: mm (inch)  
2–M4 SCREW  
33 (1.30) min.  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
1.5 W  
+
+
A
1
3
PA BUS  
PA BUS  
1.5 W  
– C  
HEAD  
ELEMENT  
Surge  
Side  
Protected  
Device Side  
Discharge  
Element  
Voltage  
Limiter  
SHIELD B  
2
SHIELD  
BASE  
G
GROUND TERMINAL  
(used as mounting attachment)  
Specifications are subject to change without notice.  
MDP-PA SPECIFICATIONS  
ES-8207 Rev.9 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

MDP-PA/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-PM

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-PM/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-PM/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-RB

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-RB/A33

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-RB/Q

Lightning Surge Protectors for Electronics Equipment M-RESTER
MSYSTEM

MDP-S-0

Interconnection Device
POMONA

MDP-S-2

Interconnection Device
POMONA

MDP-S-9

Interconnection Device
POMONA

MDP-ST

Interconnection Device
POMONA

MDP-ST-0

Interconnection Device
POMONA