MEWT-322-D

更新时间:2024-10-29 22:26:11
品牌:MSYSTEM
描述:Plug-in Signal Conditioners M-UNIT

MEWT-322-D 概述

Plug-in Signal Conditioners M-UNIT

MEWT-322-D 数据手册

通过下载MEWT-322-D数据手册来全面了解它。这个PDF文档包含了所有必要的细节,如产品概述、功能特性、引脚定义、引脚排列图等信息。

PDF下载
MODEL: MEWT  
4: 220 V / 5 A AC  
Plug-in Signal Conditioners M-UNIT  
A: 100 V / 200 V / 1 A AC (single-phase / 3- wire)  
B: 100 V / 200 V / 5 A AC (single-phase / 3- wire)  
WATT TRANSDUCER  
Functions & Features  
[3] OUTPUT  
Current  
• Providing a DC output signal in proportion to AC active  
power  
A: 4 – 20 mA DC (Load resistance 600 Ω max.)  
B: 2 – 10 mA DC (Load resistance 1200 Ω max.)  
C: 1 – 5 mA DC (Load resistance 2400 Ω max.)  
D: 0 – 20 mA DC (Load resistance 600 Ω max.)  
E: 0 – 16 mA DC (Load resistance 750 Ω max.)  
F: 0 – 10 mA DC (Load resistance 1200 Ω max.)  
G: 0 – 1 mA DC (Load resistance 12 kΩ max.)  
GW: -1 – +1 mA DC (Load resistance 10 kΩ max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
• Measuring bidirectional power flow  
• DC output containing little ripple is ideal for computer  
input  
• "Time division multiplication" method accepts distorted  
waveforms  
• Isolation up to 2000 V AC  
• High-density mounting  
Typical Applications  
• Centralized monitoring and control of power management  
system in a manufacturing facility or building  
• SCR – Silicon Controlled Rectifier  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 1000 Ω min.)  
4: 0 – 10 V DC (Load resistance 10 kΩ min.)  
5: 0 – 5 V DC (Load resistance 5000 Ω min.)  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
1W: -10 – +10 mV DC (Load resistance 10 kΩ min.)  
2W: -100 – +100 mV DC (Load resistance 100 kΩ min.)  
3W: -1 – +1 V DC (Load resistance 1000 Ω min.)  
4W: -10 – +10 V DC (Load resistance 10 kΩ min.)  
5W: -5 – +5 V DC (Load resistance 5000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
50  
(1.97)  
80  
(3.15)  
136  
(5.35)  
mm (inch)  
[4] POWER INPUT  
AC Power  
MODEL: MEWT–[1][2][3]–[4][5]  
B: 100 V AC  
C: 110 V AC  
D: 115 V AC  
F: 120 V AC  
G: 200 V AC  
H: 220 V AC  
J: 240 V AC  
ORDERING INFORMATION  
• Code number: MEWT-[1][2][3]-[4][5]  
Specify a code from below for each of [1] through [5].  
(e.g. MEWT-11A-B/Q)  
• Calibration range (e.g. 0 – 1000 W)  
• VT ratio, CT ratio (e.g. VT 3300/110 V, CT 250/5 A)  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01/S01)  
DC Power  
S: 12 V DC  
R: 24 V DC  
V: 48 V DC  
P: 110 V DC  
[1] CONFIGURATION  
1: 3-phase / 3-wire  
2: Single-phase / 2-wire  
3: Single-phase / 3-wire  
[5] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
[2] INPUT (unbalanced load)  
1: 110 V / 5 A AC  
2: 110 V / 1 A AC  
3: 220 V / 1 A AC  
MEWT SPECIFICATIONS  
ES-1921 Rev.7 Page 1/5  
http://www.m-system.co.jp/  
MODEL: MEWT  
• 3-phase / 3-wire  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
VOLTAGE INPUT CURRENT INPUT  
BURDEN BURDEN  
0.1VA 2  
STD  
RANGE  
AVAILABLE  
RANGE  
1A  
5A  
1A  
5A  
200W  
1000W  
400W  
100W – 240W  
500W – 1200W  
200W – 480W  
×
/C02: Polyurethane coating  
110V 0.2VA 2  
×
0.5VA 2  
×
/C03: Rubber coating  
0.1VA 2  
×
220V 0.4VA 2  
×
TERMINAL SCREW MATERIAL  
/S01: Stainless steel  
0.5VA 2  
×
2000W 1000W – 2400W  
• Single-phase / 2-wire  
VOLTAGE INPUT CURRENT INPUT  
STD  
RANGE  
AVAILABLE  
RANGE  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
BURDEN  
BURDEN  
0.1VA  
1A  
5A  
1A  
5A  
100W  
500W  
50W – 120W  
250W – 600W  
100W – 240W  
500W – 1200W  
110V 0.2VA  
Connection: M3.5 screw terminals  
0.5VA  
Screw terminal: Chromated steel (standard) or stainless  
steel  
0.1VA  
200W  
220V 0.4VA  
0.5VA  
1000W  
Housing material: Flame-resistant resin (black)  
Isolation: Voltage input to current input to output to power  
Computation: Time division multiplication  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
• Single-phase / 3-wire  
VOLTAGE INPUT CURRENT INPUT  
BURDEN BURDEN  
0.1VA 2  
STD  
RANGE  
AVAILABLE  
RANGE  
1A  
5A  
200W  
100W – 240W  
500W – 1200W  
×
100/  
0.2VA 2  
×
200V *1  
0.5VA 2  
×
1000W  
100/200V: 100V = phase voltage  
200V = line voltage except the grounding.  
INPUT SPECIFICATIONS  
Frequency: 50 or 60 Hz  
Current Input  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC and ± 1 mA  
Minimum span: 1 mA  
Operational range: 0 – 120 % of rating  
Overload capacity: 1000 % of rating for 3 sec., 200 % for 10  
sec., 120 % continuous  
Offset: Max. 1.5 times span  
Load resistance: Output drive 12 V maximum; 10 V for [±]  
output  
Voltage Input  
Operational range: 0 – 120 % of rating  
Overload capacity: 150 % of rating for 10 sec., 120 %  
continuous  
DC Voltage: -10 – +12 V DC  
Minimum span: 5 mV  
How To Determine Wattage Range  
Calibration Range [W] = Measuring Wattage ÷ ((VT Ratio) ×  
(CT Ratio))  
Offset: Max. 1.5 times span  
Load resistance: Output drive 1 mA max. at ≥ 0.5 V  
OPERATION DIAGRAM (example)  
Check that the required calibration range is within the  
available range in the table. Specify this range when  
ordering.  
OUT  
OUT  
10 V  
20 mA  
12  
4
5
[example]  
3-phase / 3-wire, measuring wattage 750 kW,  
VT 3300/110 V, CT 250/5 A  
0
500  
1000 W  
0
500  
1000 W  
750 × 10 [W] ÷ ((3300÷110) × (250÷5))= 0 – 500 [W]  
3
OUT  
20 mA  
OUT  
+10 V  
12  
4
0
-10 V  
-1000 W  
-1000 W  
0
+1000 W  
0
+1000 W  
MEWT SPECIFICATIONS  
ES-1921 Rev.7 Page 2/5  
http://www.m-system.co.jp/  
MODEL: MEWT  
INSTALLATION  
Power input  
AC: Operational voltage range: rating ±10 %,  
50/60 ±2 Hz, approx. 2 VA  
DC: Operational voltage range: rating ±10 %,  
or 85 – 150 V for 110 V rating, ripple 10 %p-p max.,  
approx. 2 W (18 mA at 110 V)  
Operating temperature: -5 to +60°C (23 to 140°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Surface or DIN rail  
Weight: 400 g (0.88 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.5 %  
Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)  
Response time: ≤ 1 sec. (0 – 90 %)  
Ripple: 0.5 %p-p max. (50/60 Hz)  
The output ripple may increase when there is great  
difference between the frequencies of input signal and  
power supply.  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(voltage input to current input to output to power to ground)  
MEWT SPECIFICATIONS  
ES-1921 Rev.7 Page 3/5  
http://www.m-system.co.jp/  
MODEL: MEWT  
CONNECTION DIAGRAM  
3-PHASE/3-WIRE  
SINGLE-PHASE/2-WIRE  
SOURCE  
3
SOURCE  
1
1
2
2
VT  
VT  
FUSE  
FUSE  
U
V
u
v
P1  
P2  
U
u
P1  
P2  
P3  
3
9
4
1
2
5
6
1
2
+
+
OUTPUT  
OUTPUT  
V
V
v
v
U
u
K
K
K
L
k
1S  
1L  
3S  
3L  
k
l
1S  
1L  
5
6
7
8
7
8
k
CT  
*
*
*
CT  
10  
11  
10  
11  
U(+)  
V(–)  
U(+)  
V(–)  
l
l
L
L
POWER**  
POWER**  
LOAD  
LOAD  
*CT Protector (model: CTM) attached to these terminals.  
*CT Protector (model: CTM) attached to these terminals.  
SINGLE-PHASE/3-WIRE  
SOURCE  
N 2  
1
**The transducer can be powered from the input voltage  
when the voltage is sufficiently stable and meets  
other supply voltage requirements.  
VT  
FUSE  
U
u
P1  
P0  
P2  
3
9
4
1
2
+
OUTPUT  
V
V
v
v
U
u
K
K
k
1S  
1L  
2S  
2L  
5
6
7
8
k
*
*
CT  
10  
11  
U(+)  
V(–)  
l
l
L
L
POWER**  
LOAD  
*CT Protector (model: CTM) attached to these terminals.  
EXTERNAL DIMENSIONS unit: mm (inch)  
CLAMP  
(top & bottom)  
7.8 (.31)  
DIN RAIL  
35mm wide  
8
9
7
6
5
4
2–  
4.5 (.18) dia.  
MTG HOLE  
25 (.98) deep  
3
2
10 11  
1
11  
M3.5  
SCREW  
50 (1.97)  
107 (4.21)  
136 (5.35)  
40 (1.57)  
50 (1.97)  
[3.3 (.13)]  
• When mounting, no extra space is needed between units.  
MEWT SPECIFICATIONS  
ES-1921 Rev.7 Page 4/5  
http://www.m-system.co.jp/  
MODEL: MEWT  
TERMINAL ASSIGNMENTS unit: mm (inch)  
CT PROTECTOR  
(model: CTM)  
Positions of CTM  
2
1
2
2
For Single-phase / 2-wire  
For Three-phase / 3-wire  
or Single-phase / 3-wire  
1
8
7
6
5
4
9
3
2
10 11  
1
Specifications are subject to change without notice.  
MEWT SPECIFICATIONS  
ES-1921 Rev.7 Page 5/5  
http://www.m-system.co.jp/  

MEWT-322-D 相关器件

型号 制造商 描述 价格 文档
MEWT-322-D/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
MEWT-322-F MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
MEWT-322-F/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
MEWT-322-G MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
MEWT-322-G/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
MEWT-322-H MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
MEWT-322-H/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
MEWT-322-J MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
MEWT-322-J/Q MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格
MEWT-322-P MSYSTEM Plug-in Signal Conditioners M-UNIT 获取价格

MEWT-322-D 相关文章

  • HARTING(浩亭)圆形连接器产品选型手册
    2024-10-31
    6
  • HYCON(宏康科技)产品选型手册
    2024-10-31
    6
  • GREEGOO整流二极管和晶闸管产品选型手册
    2024-10-31
    7
  • 西门子豪掷106亿美元,战略收购工程软件巨头Altair
    2024-10-31
    8