MODEL: R10M-CT4E  
Plug-in Remote I/O R10 Series  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
MODBUS I/O MODULE  
(4 points, RMS sensing, clamp-on current sensor input)  
/C02: Polyurethane coating  
/C03: Rubber coating  
Functions & Features  
• Plug-in construction  
• Modbus-RTU protocol communication  
• Easy-to-install clamp-on type current sensor without  
needing a current transformer  
RELATED PRODUCTS  
• Installation base (model: R10-BS)  
• PC configurator software (model: R10CFG)  
The configurator software is downloadable at M-System’s  
web site.  
• Wide input range from 5 A up to 600 A  
• High-density mounting  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
36  
[1.42]  
• Clamp-on current sensor (model: CLSE)  
The clamp-on current sensors, not included in this product  
package, must be ordered separately. Required number  
depends upon the system configuration.  
99  
[3.90]  
125  
[4.92]  
PACKAGE INCLUDES...  
• Terminating resistor 110Ω (0.25W)  
mm [inch]  
Note: The !gure shows the combination  
of the unit and the base.  
GENERAL SPECIFICATIONS  
Construction: Plug-in  
MODEL: R10M-CT4E-R[1]  
Connection  
• Connected to base with connector  
• Base  
ORDERING INFORMATION  
• Code number: R10M-CT4E-R[1]  
Specify a code from below for [1].  
(e.g. R10M-CT4E-R/Q)  
M2.6 screw terminals (torque: 0.5 N·m)  
Applicable solderless terminal size (M3)  
Screw terminal: Nickel-plated steel  
Housing material: Flame-resistant resin (black)  
Isolation: Input to Modbus to power input to FE1  
Input waveform  
• Specify the specification for option code /Q  
(e.g. /C01)  
RMS sensing: Up to 15 % of 3rd harmonic content  
Status indicators: Power, Run, Error  
Configuration: Select sensors for 4 points (CT1, CT2, CT3,  
CT4) each with PC Configurator Software (model: R10CFG)  
■Recommended solderless terminal size - M3 (unit: mm)  
I/O TYPE  
CT4E: Clamp-on current sensor CLSE use 4 points  
POWER INPUT  
DC Power  
3max  
4min  
3.2 dia.  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
[1] OPTIONS  
(mm)  
blank: none  
/Q: With options (specify the specification)  
R10M-CT4E SPECIFICATIONS  
ES-6247 Rev.0 Page 1/7  
https://www.m-system.co.jp/  
MODEL: R10M-CT4E  
configurator software)  
MODBUS COMMUNICATION  
RS-485  
Temp. coefficient: ±0.03 %/°C (±0.02 %/°F)  
Response time: ≤ 2 sec. (0 – 90 %)  
Standard: Conforms to TIA/EIA-485-A  
Protocol: Modbus-RTU  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input to Modbus  
to power input to FE1)  
Transmission distance: 500 meters max.  
Transmission media: Shielded twisted-pair cable  
(CPEV-S 0.9 dia.)  
Status indicator LED: RD, SD  
STANDARDS & APPROVALS  
EU conformity:  
Transmission setting: PC configurator software  
EMC Directive  
EMI EN 61000-6-4  
INPUT SPECIFICATIONS  
Input setting: PC configurator software  
Clamp-on current sensor (CT1, CT2)  
Input (sensor & range)  
EMS EN 61000-6-2  
RoHS Directive  
CLSE-R5: 0 – 5 A  
CLSE-05: 0 – 50 A  
CLSE-10: 0 – 100 A  
CLSE-20: 0 – 200 A  
CLSE-40: 0 – 400 A  
CLSE-60: 0 – 600 A  
Frequency: 50 / 60 Hz (45 - 65 Hz)  
Operational range: 0 – 105 % of rating  
Overload capacity  
CLSE-R5: 10 A continuous  
CLSE-05: 60 A continuous  
CLSE-10: 120 A continuous  
CLSE-20: 240 A continuous  
CLSE-40: 480 A continuous  
CLSE-60: 720 A continuous  
Be sure that the input voltage is of 480 V or less.  
INSTALLATION  
Current consumption: ≤90 mA  
Operating temperature: -10 to +55°C (14 to 131°F)  
Storage temperature: -10 to +55°C (14 to +131°F)  
Operating humidity: 10 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: Installation Base (model: R10BS)  
Weight: 120 g (0.26 lb) except base  
PERFORMANCE  
Conversion accuracy: ±1 % except the sensor accuracy  
Conversion rate: 14 ms  
Data range  
CLSE-R5: Integer that engineering unit value (A) multiplied  
by 1000  
CLSE-05, CLSE-10, CLSE-20: Integer that engineering unit  
value (A) multiplied by 100  
CLSE-40, CLSE-60: Integer that engineering unit value (A)  
multiplied by 10  
(Scaling of converted data is configurable with the  
R10M-CT4E SPECIFICATIONS  
ES-6247 Rev.0 Page 2/7  
https://www.m-system.co.jp/  
MODEL: R10M-CT4E  
CONFIGURATOR SOFTWARE SETTING  
The following parameters can be set with using PC Configurator Software (model: R10CFG)  
Refer to the users manual for the R30CFG for detailed operation of the software program.  
INPUT SETTING  
Each channel can be set independently.  
ITEM  
Clamp-on Current Sensor  
Zero Input  
SETTING RANGE  
CLSE-R5 / CLSE-05 / CLSE-10 / CLSE-20 / CLSE-40 / CLSE-60  
CLSE-R5: 0.000 - 5.000 (≤ full input)  
CLSE-05: 0.00 - 50.00 (≤ full input)  
CLSE-10: 0.00 - 100.00 (≤ full input)  
CLSE-20: 0.00 - 200.00 (≤ full input)  
CLSE-40: 0.00 - 400.00 (≤ full input)  
CLSE-60: 0.00 - 600.00 (≤ full input)  
CLSE-R5: 0.000 - 5.000 (≥ zero input)  
CLSE-05: 0.00 - 50.00 (≥ zero input)  
CLSE-10: 0.00 - 100.00 (≥ zero input)  
CLSE-20: 0.00 - 200.00 (≥ zero input)  
CLSE-40: 0.00 - 400.00 (≥ zero input)  
CLSE-60: 0.00 - 600.00 (≥ zero input)  
-320.00 - 320.00  
DEFAULT SETTING  
CLSE-R5  
0.000  
Full Input  
0.000  
Zero Fine Adjust  
Gain Zero Adjust  
Zero Scaling  
Full Scaling  
0.00 (%)  
1.0000  
0
-3.2000 - 3.2000  
-32000 - 32000  
-32000 - 32000  
10000  
1.0 (%)  
Cutout  
0.0 - 5.0 (%)  
MODBUS SETTING  
ITEM  
Data Mode  
SETTING RANGE  
Modbus-RTU / Modbus-ASCII  
1 - 247  
DEFAULT SETTING  
Modbus-RTU  
1
Address  
Baud Rate  
38400 / 19200 / 9600 / 4800 bps  
None / Odd / Even  
38400 bps  
None  
Parity  
Communication timeout duration  
0.1 - 3200.0 (sec.)  
3.0 sec.  
Depending on data mode and parity bit setting, data bit and stop bit are as following.  
DATA MODE  
Modbus-RTU  
PARITY BIT  
None  
DATA BIT  
STOP BIT  
8
8
7
7
2
1
2
1
Odd or Even  
None  
Modbus-ASCII  
Odd or Even  
EXTERNAL VIEW  
Specications (side)  
Status Indicator LED  
Congurator Jack  
R10M-CT4E SPECIFICATIONS  
ES-6247 Rev.0 Page 3/7  
https://www.m-system.co.jp/  
MODEL: R10M-CT4E  
MODBUS WIRING CONNECTION  
WIRING COMMUNICATION WITH HOST PC  
MODBUS  
I/O  
MODBUS  
I/O  
HOST PC  
MODULE  
MODULE  
TERMINATOR  
TERMINATOR  
DA  
DA  
DB  
DA  
DB  
DG  
DB  
DG  
SLD  
FE  
DG  
SLD  
FE  
Note: The terminator must be connected across “DAand “DB” at both ends of communication line.  
TERMINAL ASSIGNMENTS  
BASE  
PIN NO.  
ID  
K1  
K2  
K3  
K4  
NC  
L1  
L2  
L3  
L4  
NC  
FUNCTION  
Input 1-K  
PIN NO.  
11  
ID  
FE  
DB  
DA  
NC  
FE1  
FUNCTION  
Modbus grounding  
DB  
1
K1  
2
K2  
3
K3  
4
K4  
5
1
2
NC  
10  
NC  
Input 2-K  
Input 3-K  
Input 4-K  
Unused  
12  
6
L1  
7
L2  
8
L3  
9
L4  
3
13  
DA  
4
14  
Unused  
5
15  
Power grounding  
6
Input 1-L  
Input 2-L  
Input 3-L  
Input 4-L  
Unused  
16  
SLD Shield  
7
17  
DG  
NC  
DG  
8
18  
Unused  
9
19  
24V Power supply 24V DC  
0V Power supply 0V DC  
10  
20  
11  
FE  
16  
SLD DG NC 24V 0V  
12  
DB DA NC FE1  
17 18 19 20  
13  
14  
15  
* Base does not come with the unit. Please order separately.  
MODBUS FUNCTION CODES & SUPPORTED CODES  
Modbus function codes are shown below  
DATA AND CONTROL FUNCTIONS  
CODE  
02  
NAME  
Read Input Status  
Read Input Registers  
Status of digital inputs to the slave (read only)  
04  
Collected data from the fi eld by the slave (read only)  
EXCEPTION CODES  
CODE  
NAME  
01  
02  
03  
Illegal Function  
Illegal Data Address  
Illegal Data Value  
Function code is not allowable for the slave  
Address is not available within the slave  
Data is not valid for the function  
R10M-CT4E SPECIFICATIONS  
ES-6247 Rev.0 Page 4/7  
https://www.m-system.co.jp/  
MODEL: R10M-CT4E  
MODBUS I/O ASSIGNMENT  
ADDRESS  
DATA TYPE  
DATA  
Input (0X)  
1
2
3
4
1
2
3
4
Analog input 1 error (input range error)  
Analog input 2 error (input range error)  
Analog input 3 error (input range error)  
Analog input 4 error (input range error)  
Analog Input (analog input 1)  
Input Register (3X)  
I
I
I
I
Analog Input (analog input 2)  
Analog Input (analog input 3)  
Analog Input (analog input 4)  
Note: DO NOT access addresses other than the ones mentioned above. Such access may cause problems such as malfunction.  
DATA TYPE  
I: Integer, 0  
- 65535  
STATUS  
1 bit: indicates input status.  
input range error ( (Input range is out of the range)  
0: Normal  
1: Error  
DATA CONVERSION  
ENGINEERING UNIT CONVERSION  
CLSE-R5 is multipled by 1000, CLSE-10 and CLSE-20 is multipled 100, CLSE-40 and CLSE-60 is multipled by 10, expressed in 16 bits  
(0 - 65535).  
SCALED ANALOG DATA (16-bit) CONVERSION  
15  
0
The data is 0 to 10000 for scaling 0 to 100% setting.  
If the input range is 0 to +105% (0 to +10500) and that is out of range, the data is fixed to 0 or 10500.  
DATA ERROR STATUS  
Data error status is indicated by 1 bit.  
0: OFF  
1: ON  
EXTERNAL DIMENSIONS unit: mm [inch]  
36 [1.42]  
80 [3.15]  
45 [1.77]  
[4 [.16]]  
DIN rail  
(35mm wide)  
• When mounting, no extra space is needed between units.  
R10M-CT4E SPECIFICATIONS  
ES-6247 Rev.0 Page 5/7  
https://www.m-system.co.jp/  
MODEL: R10M-CT4E  
MOUNTING REQUIREMENTS unit: mm [inch]  
2-M4  
* Mounting requirements for base.  
TERMINAL ASSIGNMENTS  
BASE  
1
6
2
7
3
8
4
9
5
10  
11 12 13 14 15  
16 17 18 19 20  
* Base does not come with the unit. Please order separately.  
R10M-CT4E SPECIFICATIONS  
ES-6247 Rev.0 Page 6/7  
https://www.m-system.co.jp/  
MODEL: R10M-CT4E  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Status Indicator LED  
Communication  
Circuit  
Jack  
1
12 DB  
Configurator Jack  
Isolation  
K1  
13  
DA  
CT INPUT 1  
Control  
Circuit  
K2  
6
17 DG  
11 FE  
16 SLD  
To other Modbus devices  
K3  
CT INPUT 2  
K4  
2
7
Input  
Circuit  
3
L1  
CT INPUT 3  
L2  
19 24V DC  
20 0V  
POWER  
8
4
L3  
CT INPUT 4  
L4  
15 FE1  
14 NC  
9
5
NC  
18 NC  
NC 10  
Base  
INPUT CONNECTION  
SOURCE  
k
Kn  
Ln  
CLAMP-ON SENSOR  
l
LOAD  
Specifications are subject to change without notice.  
R10M-CT4E SPECIFICATIONS  
ES-6247 Rev.0 Page 7/7  
https://www.m-system.co.jp/  

相关型号:

R10M-US2

Plug-in Remote I/O R10 Series MODBUS I/O MODULE
MSYSTEM

R10M-US2-R

Plug-in Remote I/O R10 Series MODBUS I/O MODULE
MSYSTEM

R10M-US2-R/Q

Plug-in Remote I/O R10 Series MODBUS I/O MODULE
MSYSTEM

R10N11D01

ROTARY POTENTIOMETER
PRODUCTWELL

R10N11H01

ROTARY POTENTIOMETER
PRODUCTWELL

R10S-E1W1AC

General Purpose Relays Industrial Relays
MACOM

R10S-E1W1DC

General Purpose Relays Industrial Relays
MACOM

R10S-E1W2AC

General Purpose Relays Industrial Relays
MACOM

R10S-E1W2DC

General Purpose Relays Industrial Relays
MACOM

R10S-E1W3AC

General Purpose Relays Industrial Relays
MACOM

R10S-E1W3DC

General Purpose Relays Industrial Relays
MACOM

R10S-E1X1AC

General Purpose Relays Industrial Relays
MACOM