R1C-GH2T-R [MSYSTEM]
Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE;型号: | R1C-GH2T-R |
厂家: | M-SYSTEM |
描述: | Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE 输入元件 |
文件: | 总5页 (文件大小:166K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: R1C-GH
Remote I/O R1X Series
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
THERMOCOUPLE & DC INPUT MODULE
(16 points; CC-Link Ver.1.10/Ver.2.00)
Functions & Features
/C02: Polyurethane coating
/C03: Rubber coating
• 16-point thermocouple or DC inputs
• CC-Link interface
RELATED PRODUCTS
• CC-Link Version 1.10 and 2.00 can be switched at the
startup
• Resistor module (model: REM3-250)
• R1X configurator software (model: R1CON)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
175 (6.89)
40
(1.57)
115
(4.53)
mm (inch)
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
MODEL: R1C-GH2T-[1][2]
GENERAL SPECIFICATIONS
Connection
Power input, CC-Link: Euro type connector terminal
ORDERING INFORMATION
• Code number: R1C-GH2T-[1][2]
Specify a code from below for each [1] and [2].
(e.g. R1C-GH2T-M2/Q)
(applicable wire size: 0.2 to 2.5 mm
2
(AWG24 to 12),
stripped length 7 mm)
Input: M3 screw terminals (torque 0.6 N·m)
Configurator: 2.5 dia. miniature jack; RS-232-C level
Screw terminal: Nickel-plated steel
• Specify the specification for option code /Q
(e.g. /C01)
Housing material: Flame-resistant resin (gray)
Isolation: Input to CC-Link (FG) to power
• Use Ordering Information Sheet (No. ESU-5956). Default
setting will be used if not otherwise specified.
Factory default setting
PWR indicator: Green LED blinks in normal conditions.
Input type: DC Voltage ±5 V
Burnout protection: No burnout
Cold junction compensation: No
CC-Link COMMUNICATION
Protocol: CC-Link V1.10 / V 2.00
Cable for comm. link: Specified by Mitsubishi Electric
Required nodes
FIELD TERMINAL TYPE
T: M3 screw terminals
V. 1.10: 4
V. 2.00: 1 (cyclic expansion: 4)
Station No. setting: Rotary switch
V. 1.10: Rotary switch; 1 – 61
[1] POWER INPUT
AC Power
V. 2.00: Rotary switch; 1 – 64
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
Baud rate setting: Rotary switch
L RUN indicator: Red LED turns on in normal conditions.
L ERR. indicator: Red LED turns on or blinks in an
abnormality.
47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
SD indicator: Red LED turns on when transmitting.
RD indicator: Red LED turns on when receiving.
[2] OPTIONS
blank: none
INPUT SPECIFICATIONS
■ Thermocouple or DC input, 16 points
/Q: With options (specify the specification)
(Common negative for DC input)
•Measuring range ±20 V, ±5 V, ±1 V: Atten. SW ON (3)
R1C-GH SPECIFICATIONS
ES-5956 Rev.12 Page 1/5
http://www.m-system.co.jp/
MODEL: R1C-GH
•Measuring range ±0.8 V, ±0.2 V, ±50 mV, ±10m V: Atten.
SW OFF (1)
INSTALLATION
Power consumption
•AC: Approx. 10 VA
•DC: Approx. 7 W
Input resistance: 300 kΩ
Thermocouple types: PR, K, E, J, T, B, R, S, C, N, U, L, P
Sampling rate: 150 millisec./16 points
■ A/D conversion output: 16-bit signed binary (negative
range represented by 2’s complements)
Engineering unit value is converted into A/D conversion
data as shown below.
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lb)
Input type & range: A/D data (decimal)
±20 V: ±20000
PERFORMANCE (% of measuring range)
Accuracy
±5 V: ±5000
DC input: ±0.3 %
±1 V: ±10000
Thermocouple input: See the table on the end of this
section.
±0.8 V: ±8000
±0.2 V: ±20000
Cold junction compensation error: ±3°C or ±5.4°F max.
(at 20°C ±10°C or 68°F ±18°F)
±50 mV: ±5000
±10 mV: ±10000
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
±0.05 %/°C (±0.03 %/°F) for 10 mV range and T/C B (RH)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input to CC-Link
[FG] to power to ground [FG1])
Thermocouples: Temperature × 10
In order to change input type and range after shipment, the
R1X configurator software (model: R1CON) is required.
CC-Link version selector input:
Ver. 1.10 with OFF at the startup.
Ver. 2.00 with ON at the startup.
Thermocouple Accuracy
Dry contact input (ON at detect. level ≤ 1.5 V)
Sensing: approx. 5 V DC, 1 mA
USABLE RANGE ACCURACY CONFORMANCE
T/C
(°C)
(%)
RANGE (°C)
(PR)
K (CA)
E (CRC)
J (IC)
T (CC)
B (RH)
R
0 to 1770
-270 to +1370
-270 to +1000
-210 to +1200
-270 to +400
100 to 1820
-.0 to +1760
-.0 to +1760
0 to 2320
0ꢀ.
0ꢀ3
0ꢀ7
0ꢀ7
1ꢀ0
400 to 1770
0 to 1370
0 to 1000
0 to 1200
0 to 400
700 to 1820
400 to 1760
400 to 1760
0 to 2320
0 to 1300
0 to 600
0 to 900
0 to 139.
Valid only at the moment of the power supplied to the
module. Firmware version 0B.00 or higher required.
Confirm the firmware version using the R1X configurator
software (model: R1CON) or consult M-System.
0ꢀ7
0ꢀ7
0ꢀ7
0ꢀ7
0ꢀ.
0ꢀ.
0ꢀ3
0ꢀ.
■ A/D CONVERSION DATA
15
14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
S
SIGN
BIT
RWr n+0
RWr n+1
RWr n+2
RWr n+3
INPUT 1 A/D CONVERSION DATA
INPUT 2 A/D CONVERSION DATA
INPUT 3 A/D CONVERSION DATA
INPUT 4 A/D CONVERSION DATA
C (WRe .-26
)
N
-270 to +1300
-200 to +600
-200 to +900
0 to 139.
SIGN
BIT
U
L
SIGN
BIT
P
(Platinel II)
SIGN
BIT
USABLE RANGE ACCURACY CONFORMANCE
T/C
(PR)
(°F)
(%)
RANGE (°F)
32 to 3218
-4.4 to +2498
-4.4 to +1832
-346 to +2192
-4.4 to +7.2
212 to 3308
-.8 to +3200
-.8 to +3200
32 to 4208
0ꢀ.
0ꢀ3
0ꢀ7
0ꢀ7
1ꢀ0
7.2 to 3218
32 to 2498
32 to 1832
32 to 2192
32 to 7.2
1292 to 3308
7.2 to 3200
7.2 to 3200
32 to 4208
32 to 2372
32 to 1112
32 to 16.2
32 to 139.
K (CA)
E (CRC)
SIGN
BIT
RWr n+7
RWr n+11
RWr n+15
INPUT 8 A/D CONVERSION DATA
INPUT 12 A/D CONVERSION DATA
INPUT 16 A/D CONVERSION DATA
J (IC)
T (CC)
B (RH)
0ꢀ7
0ꢀ7
0ꢀ7
0ꢀ7
0ꢀ.
0ꢀ.
0ꢀ3
0ꢀ.
R
SIGN
BIT
S
C (WRe .-26
)
N
U
L
-4.4 to +2372
-328 to +1112
-328 to +16.2
32 to 139.
SIGN
BIT
P
(Platinel II)
Note: CJC error is not includedꢀ
R1C-GH SPECIFICATIONS
ES-5956 Rev.12 Page 2/5
http://www.m-system.co.jp/
MODEL: R1C-GH
EXTERNAL VIEW
A
B
C
D
E
F G
T8 T7 T6
DA DB DG FG SLD
NAME
FUNCTIONS
A
B
Power terminal block
For power input
Network terminal block
For wiring to CC-Link
SETTING
BAUD RATE
C
Baud rate setting
0
1
2
156 kbps (factory default)
625 kbps
2.5 Mbps
3
5 Mbps
10 Mbps
Not valid; L ERR. turns on as a transmission error.
4
Other than 0 – 4
D
E
Station No. setting
V. 1.10: Selectable within 1 – 61. (factory set to: 00)
V. 2.00: Selectable within 1 – 64. (factory set to: 00)
ID (color)
FUNCTIONS
Status indicator LED
L RUN (red)
ON: Normal communication
blinking: Transmission data error
OFF:
Communication down (time-out error)
Transmission data error
Transmission data error
Normal transmission
ON:
blinking:
L ERR. (red)
OFF:
SD (red)
ON when transmitting
ON when receiving
FUNCTIONS
RD (red)
ID (color)
PWR (green)
F
Power LED
ON:
Abnormality
blinking, high speed: CC-Link Ver. 1.10
blinking, low speed: CC-Link Ver. 2.00
Master Version 2.00 with long ON time
Master Version 1.10 with long OFF time
G
Con!gurator jack
2.5 dia. miniature jack; RS-232-C level
R1C-GH SPECIFICATIONS
ES-5956 Rev.12 Page 3/5
http://www.m-system.co.jp/
MODEL: R1C-GH
CONNECTION DIAGRAM
DC INPUT T/C INPUT
+
+
Comm.
Circuit
+
1
DA
DB
ext. wire
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
INPUT 8
INPUT 9
INPUT 10
INPUT 11
INPUT 12
INPUT 13
INPUT 14
INPUT 15
INPUT 16
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
2
–
–
To Other
CC-Link Devices
3
DG
SLD
FG
4
5
6
Power
Circuit
7
T6
T7
T8
U (+)
POWER
V (–)
8
9
FG1
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
CONFIGURATOR
JACK
Input
Circuit
CJC
Sensor
+
CC-Link VERSION SELECTOR INPUT
–
Note 1: This device is not designed to cancel noise included in the input signals.
Be careful to eliminate such noise by using shielded cables.
Note 2: Be sure to maintain the same potential at all the common negative terminals for DC input.
Note 3: CC-Link version selector input is valid only at the moment of the power turned on.
Firmware version 0B.00 or higher. Use the R1X Configurator Software (model: R1CON)
or consult M-System to confirm the firmware version.
Caution: FG1 terminal is NOT a protective conductor terminal.
R1C-GH SPECIFICATIONS
ES-5956 Rev.12 Page 4/5
http://www.m-system.co.jp/
MODEL: R1C-GH
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
175 (6.89)
165 (6.50)
15.5 (.61)
3–5 (.20) dia.
MTG HOLES
DIN RAIL
35 mm wide
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35
3 (.12)
40 (1.57)
163 (6.42)
[6 (.24)]
FOR WALL MOUNT.
CJC SENSOR (model: CJM)
6.2 (.24)
36–M3 INPUT TERMINALS
Specifications are subject to change without notice.
R1C-GH SPECIFICATIONS
ES-5956 Rev.12 Page 5/5
http://www.m-system.co.jp/
相关型号: